18-28-506.3.11 Duct enclosure.
   A grease duct serving a Type I hood that penetrates a ceiling, wall or floor shall be enclosed from the point of penetration to the outlet terminal. A duct shall only penetrate exterior walls at locations where unprotected openings are permitted by the Chicago Building Code. Ducts shall be enclosed in accordance with building code requirements for shaft construction. The duct enclosure shall be sealed around the duct at the point of penetration and vented to the outside of the building through the use of weather-protected openings. The enclosure shall be separated from the duct by a minimum of 6 inches (152 mm) and a maximum of 12 inches (305 mm) and shall serve a single grease exhaust duct system. See Section 18-28-506.3.7.
   Exceptions:
      1.   The shaft enclosure provisions of this section shall not be required where a duct penetration is protected with a through-penetration firestop system classified in accordance with ASTM E 814 and having an "F" and "T" rating equal to the fire-resistance rating of the assembly being penetrated and where the surface of the duct is continuously covered on all sides from the point at which the duct penetrates a ceiling wall or floor to the outlet terminal with a classified and labeled material, system, method of construction or product specifically evaluated for such purpose, in accordance with a nationally recognized standard for such enclosure materials.
      2.   A duct enclosure shall not be required for a grease duct that penetrates only a nonfireresistance-rated roof/ceiling assembly.
(Amend Coun. J. 9-14-21, p. 35949, Art. V, § 14)