See Table 18-28-403.3, Ventilating Requirements.
For a printer-friendly PDF version of Table 18-28-403.3, please click here.
* S = Mechanical Supply; E = Mechanical Exhaust From Room; RO = Relief Opening; NR = No Requirement; NV = Natural Ventilation; Vent opening = percentage of floor area.
Room Purpose | Vent Opening Percent of Floor Area | Mechanical Ventil. CFM/SF | Remarks | ||
Less Than | Not Less Than | S, Supply | E, Room Exhaust |
Room Purpose | Vent Opening Percent of Floor Area | Mechanical Ventil. CFM/SF | Remarks | ||
Less Than | Not Less Than | S, Supply | E, Room Exhaust | ||
Correctional | |||||
Cell rooms | 4 | 0 | 0 | ||
4 | 1.2 | 1.2 | |||
Dry Cleaners/Laundries | |||||
Dry Cleaning | 4 | 0 | 4 | See 18-28-403.3.3. | |
4 | 1.5 | 4 | |||
Laundries (Residential for less than 30 units) | 4 | 0 | 0 | ||
4 | 0 | 1 | |||
Laundries serving general public | 1.5 | 1.5 | See 18-28-403.3.3. | ||
Linen Rooms | 0.5 | 0.5 | |||
Education | |||||
Music Rooms | 4 | 0 | 0 | ||
4 | 1.5 | 0.75 | |||
Class Rooms/Auditoriums | 4 | 0 | 0 | ||
4 | 1.5 | 0.75 | |||
Cooking Rooms for Instruction only | 4 | 0 | 1.5 | ||
4 | 1.0 | 1.5 | |||
Libraries/Reading Rooms | 4 | 0 | 0 | ||
4 | 1.2 | 0.6 | |||
Food and Beverage Service | |||||
Cafeterias/Food Courts | 4 | 0 | 0 | ||
4 | 1.5 | 2.0 | |||
Public Dining Rooms - no cooking equipment | 4 | 0 | 0 | ||
4 | 1.5 | 1.5 | |||
Public Dining Rooms - with cooking equipment | 4 | 0 | 2 | ||
4 | 1.5 | 2 | |||
Grills | 1 | 0 | 2 | ||
1 | 1.5 | 2 | |||
Kitchen, public | 3 | 0 | 4 | See Note 5. | |
3 | 1.2 | 4 | |||
Lounges/Bars | 4 | 0 | 0 | ||
4 | 1.0 | 1.5 | |||
Health Care | |||||
Anesthesia Storage Rooms | 1.2 | 1.2 | See Note 5. | ||
Autopsy Rooms | 1.5 | 3.0 | See Note 5. | ||
Doctor's - Dentist exam rooms | 4 | 0 | 0 | ||
4 | 0.6 | 0.3 | |||
Delivery Rooms/Birthing Rooms | 2.0 | 1.0 | |||
Intensive Care | 2.0 | 1.0 | No recirculation within room. | ||
Morgues | 1.5 | 3.0 | See Note 5. | ||
Nurseries | 2.0 | 1.0 | |||
Operating Rooms | 2.0 | 1.0 | No recirculation within room. | ||
Patient Rooms | 4 | 0 | 0 | May exhaust through toilet room. | |
4 | 0.3 | 0.3 | |||
Physiotherapy | 4 | 0 | 0 | ||
4 | 0.6 | 0.3 | |||
Recovery Rooms | 1.0 | 1.0 | No recirculation within room. | ||
Sterilizing Equipment Rooms | 1.6 | 1.6 | No recirculation within room. See Note 5. | ||
Treatment Rooms | 0.6 | 0.3 | |||
X-Ray operator's rooms | 0.6 | 0.3 | |||
Hotels, Motels and Dormitories | |||||
Banquet Halls/Assembly Pre-function | 2.0 | 1.5 | |||
Hotels (Lobby) | 4 | 0 | 0 | ||
4 | 1.0 | NR | |||
Sleeping Rooms | 4 | 0 | 0 | ||
4 | 0.3 | 0.3 | |||
Toilet Rooms / Bathrooms – Private | See Note 6. | ||||
Foyers except the above | 0 | 0 | |||
Sleeping Rooms (Dormitories) | 4 | NV | NV | ||
Offices | |||||
Lunch Rooms - no cooking | 4 | 0 | 0 | ||
4 | 1.5 | 1.5 | |||
Offices and computer rooms | 4 | 0 | 0 | ||
4 | 0.6 | 0.3 | |||
Entrance lobby | 4 | 0 | 0 | ||
4 | 1.0 | NR | |||
Private Dwellings (Single and Multiple) | |||||
Living Quarters | NV | NV | |||
Living Quarters (Kitchen) | 4 | 0 | 0 | See Note 7. | |
4 | 0 | 1.5 | |||
Toilet Rooms / Bathrooms – Private | See Note 6. | ||||
Multi-Purpose Rooms | NR | NR | 0.3 | 0.3 or R.O. | |
Public Spaces | |||||
Corridors | NR | NR | |||
Dressing Rooms | 4 | 0 | 0 | ||
4 | 1.0 | 1.2 | |||
Janitor's Closet | 0 | 2.0 | See Note 5. | ||
Locker Rooms | 4 | 0 | 0 | See Note 5. | |
4 | 0.3 | 1.2 | |||
Pedestrian Passageways (below grade) | 1.5 | 1.0 | |||
Pedestrian Passageways (above grade) | 4 | 0 | 0 | ||
4 | 1.5 | 1.0 | |||
Shower Rooms | 4 | 0 | 0 | ||
Smoking Rooms | 4 | 0 | 0 | See Note 5. | |
4 | 1.0 | 1.5 | |||
Toilet Rooms | 4 | 0 | 0 | See Note 5. | |
4 | 0 | 2.0 | |||
Waiting Rooms | 4 | 0 | 0 | ||
4 | 1.0 | 1.0 | |||
Retail Stores | |||||
Malls | 4 | 0 | 0 | ||
4 | 1.0 | 1.0 | |||
Retail Stores | 4 | 0 | 0 | ||
4 | 1.0 | 1.0 | |||
Specialty Shops | |||||
Auto and vehicle washing (attended) | 1.0 | 1.0 | See Note 5. | ||
Auto repair shops | 1.0 | 1.0 | See Note 5. | ||
Photo materials and engraving | 4 | 0 | 0 | See 18-28-403.3.3. | |
4 | 1.0 | 1.0 | |||
Beauty Parlors/Barber Shops | 4 | 0 | 0 | See Note 5. | |
4 | 1.2 | 1.2 | |||
Theaters | |||||
Auditoriums (including stage) | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Concert Halls | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Foyers in Theaters | 1.0 | 1.0 | |||
4 | 2.0 | 1.0 | |||
Studios – motion picture, radio, TV | 1.5 | 0.75 | Or RO. | ||
Theatrical Community Centers | 4 | 0 | 0 | ||
4 | 1.5 | 0.75 | |||
Workrooms | |||||
Workshops not otherwise classified | 4 | 0 | 0 | See 18-28-403.3.3. | |
4 | 1.2 | 1.2 | |||
Wood working shop | 0 | 4 | 0 | 0 | See Article 5 - Makeup air is required when direct exhaust > 5, 000 CFM. |
4 | 1.2 | 1.2 | |||
Spray Finishing | 4 | See Article 5 - Makeup air is required when direct exhaust > 5, 000 CFM. | |||
4 | 1.5 | 1.2 | |||
Spray Booths | 4 | See Article 5 - Makeup air is required when direct exhaust > 5, 000 CFM. | |||
4 | 1.5 | 1.5 | |||
Bank Vaults Attended | 0.6 | 0.3 | |||
Battery Charging - Dry Cell Batteries | NR | 0.5 | 3 or more batteries. | ||
- Other Batteries | NR | 1.0 | |||
Sports and Amusement | |||||
Bowling Alleys (seating areas) | 4 | 0 | 0 | ||
4 | 1.7 | 0.85 | |||
Ball Rooms | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Cabarets | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Dance Halls/Discos | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Game Rooms/Arcades | 4 | 0 | 0 | ||
4 | 1.6 | 1.6 | |||
Gymnasiums | 4 | 0 | 0 | Or RO. | |
4 | 2.0 | 1.5 | |||
Natatoriums (deck and seating) | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Recreation Rooms | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Skating Rinks, Ice Arenas | 4 | 0 | 0 | ||
4 | 1.5 | 1.5 | |||
Skating Rinks, Roller | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Storage | |||||
Storage inactive | 0 | 0 | |||
Storage active | 0.5 | 0.5 | |||
Storage cold (no permanent occupancy) | 0 | 0 | |||
Vault, Storage | NR | NR | |||
Laboratories | |||||
Laboratories | 5 | 0 | 0 | ||
5 | 1.2 | 1.2 | |||
Animal Rooms | 0 | 1.5 | |||
Religious | |||||
Auditoriums for worship/Chapels | 4 | 0 | 0 | Or RO. | |
4 | 1.5 | 0.75 | |||
Special Use | |||||
Convention Halls | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Council Chambers | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Court Rooms | 4 | 0 | 0 | ||
4 | 2.0 | 1.5 | |||
Exhibition Rooms | 1.5 | 0.75 | Or RO. | ||
Fraternal Rooms | 1.5 | 0.75 | Or RO. | ||
Lodge Halls | 1.5 | 0.75 | Or RO. | ||
Museums | 0.6 | NR | Or RO. | ||
Garages/Parking Structures | See Miscellaneous | ||||
Garages, 6 or more cars | 0.75 | 1.0 | |||
RO | 1.0 | ||||
Private Garages (less than 6 cars) | RO | RO | 1.0 sf of opening per car. | ||
Garages in or attached to Hospitals | 0.75 | 1.0 | Exhaust duct, 14 gauge. | ||
RO | 1.0 | ||||
Note 1. [Reserved.]
Note 2. [Reserved.]
Note 3. [Reserved.]
Note 4. Corridor make-up air system for residential building over 55 feet in height shall be sized to equal the total of toilet, kitchen and dryer air exhaust requirements.
Note 5. There shall be no recirculation permitted from these spaces.
Note 6. For each private toilet room or bathroom: 20 CFM when the exhaust system is designed to operate continuously when the associated living quarters are occupied; 50 CFM when the exhaust system is designed to operate intermittently. For intermittent operation, either an automatic control or ready access to a manual control shall be provided within the room.
Note 7. For each residential kitchen: 50 CFM when the kitchen is enclosed and the exhaust system is designed to operate continuously when the associated living quarters are occupied; 100 CFM vented range hood or 300 CFM mechanical exhaust (including downdraft) when the kitchen is unenclosed or the exhaust system is designed to operate intermittently. For intermittent operation, either an automatic control or ready access to a manual control shall be provided within the room.
(Amend Coun. J. 9-14-16, p. 31143, § 8; Amend Coun. J. 3-29-17, p. 45477, § 12; Amend Coun. J. 4-10-19, p. 100029, Art. XII, § 5; Amend Coun. J. 9-14-21, p. 35949, Art. IV, § 4; Amend Coun. J. 9-21-22, p. 52080, Art. II, § 8)