The provisions of Article 830 of NFPA 70 are adopted by reference with the following modifications:
1. Revise subsection 830.110(A)(2) to read:
"Communications Raceways. Low-power network-powered broadband communication cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general- purpose communications raceways, selected in accordance with Table 800.154(b), listed in accordance with 800.182, and installed in accordance with 800.113."
2. Revise subsection 830.110(C) to read:
"Cable Routing Assemblies. Low-power network-powered broadband communications cables shall be permitted to be installed in riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with Table 800.154(c), listed in accordance with 800.182, and installed in accordance with 800.110(C) and 800.113."
3. Revise subsections 830.113 (B) through (I) to read:
"(B) Ducts Specifically Fabricated for Environmental Air. Wires and cables installed in ducts specifically fabricated for environmental air shall be installed in accordance with.22(B).
(C) Other Spaces Used for Environmental Air (Plenums). Wires and cables installed in other spaces used for environmental air (plenums) shall be installed in accordance with 300.22(C).
(D) Risers – Cables in Vertical Runs. The following cables shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft:
(1) Types BLP, BMR, and BLR
(2) Types BLP and BLR installed in the following:
a. Plenum communications raceways
b. Riser communications raceways
c. Riser cable routing assemblies
Informational Note: See 830.26 for firestop requirements for floor penetrations.
(E) Risers – Cables and Innerducts in Metal Raceways. The following cables and innerducts shall be permitted in a metal raceway in a riser with firestops at each floor:
(1) Types BLP, BMR, BLR, BM, BL, and BLX
(2) Types BLP, BLR, and BL installed in the following:
a. Plenum communications raceways (innerduct)
b. Riser communications raceways (innerduct)
c. General-purpose communications raceways (innerduct)
Informational Note: See 830.26 for firestop requirements for floor penetrations.
(F) Risers – Cables in Fireproof Shafts. The following cables shall be permitted to be installed in fireproof riser shafts with firestops at each floor:
(1) Types BLP, BMR, BLR, BM, BL, and BLX
(2) Types BLP, BLR, and BL installed in the following:
a. Plenum communications raceways
b. Riser communications raceways
c. Riser cable routing assemblies
d. General-purpose communications raceways
e. General-purpose cable routing assemblies
Informational Note: See 830.26 for firestop requirements for floor penetrations.
(G) Risers – One- and Two-Family Dwellings. The following cables shall be permitted in one- and two-family dwellings:
(1) Types BLP, BMR, BLR, BM, BL, and BLX less than 10 mm (3/8 in.) in diameter
(2) Types BLP, BLR, and BL installed in the following:
a. Plenum communications raceways
b. Riser communications raceways
c. Riser cable routing assemblies
d. General-purpose communications raceways
e. General-purpose cable routing assemblies
Informational Note: See 830.26 for firestop requirements for floor penetrations.
(H) Cable Trays. The following cables shall be permitted to be supported by cable trays:
(1) Types BLP, BMR, BLR, BM, and BL
(2) Types BLP, BLR, and BL installed in the following:
a. Plenum communications raceways
b. Riser communications raceways
c. General-purpose communications raceways
(I) Other Building Locations. The following cables shall be permitted to be installed in building locations other than those covered in 830.113(B) through(H):
(1) Types BLP, BMR, BLR, BM, and BL
(2) Types BLP, BMR, BLR, BM, BL, and BLX installed in raceways recognized in Chapter 3
(3) Types BLP, BLR, and BL installed in the following:
a. Plenum communications raceways
b. Riser communications raceways
c. Riser cable routing assemblies
d. General-purpose communications raceways
e. General-purpose cable routing assemblies
(4) Type BLX less than 10 mm (3/8 in.) in diameter in one-and two-family dwellings
(5) Types BMU and BLU entering the building from outside and run in rigid metal conduit (RMC) or intermediate metal conduit (IMC) where the conduit is connected by a bonding conductor or grounding electrode conductor in accordance with 830.100(B)
Informational Note: This provision limits the length of Type BLX cable to 15.2 m (50 ft), while 830.90(B) requires that the primary protector, or NIU with integral protection, be located as close as practicable to the point at which the cable enters the building. Therefore, in installations requiring a primary protector, or NIU with integral protection, Type BLX cable may not be permitted to extend 15.2 m (50 ft) into the building if it is practicable to place the primary protector closer than 15.2 m (50 ft) to the entrance point.
(6) A maximum length of 15.2 m (50 ft), within the building, of Type BLX cable entering the building from outside and terminating at an NIU or a primary protection location."
4. Revise Table 830.154(a) to read:
"Applications of Listed Network-Powered Broadband Cables in Buildings
Applications | Listed Coaxial Cable Type
| |||||||
BLP | BLR | BL | BMR | BM | BLX | BMU, BLU
|
Applications | Listed Coaxial Cable Type
| |||||||
BLP | BLR | BL | BMR | BM | BLX | BMU, BLU
| ||
In ducts specifically fabricated for environmental air as described in 300.22(B) | In fabricated ducts as described in 300.22(B) | N | N | N | N | N | N | N |
In metal raceway that complies with 300.22(B) | Y* | Y* | Y* | Y* | Y* | Y* | N | |
In other spaces used for environmental air as described in 300.22(C) | In other spaces used for environmental air as described in 300.22(C) | N | N | N | N | N | N | N |
In metal raceway that complies with 300.22(C) | Y* | Y* | Y* | Y* | Y* | Y* | Y* | |
In risers | In vertical runs | Y* | Y* | N | Y* | N | N | N |
In metal raceways | Y* | Y* | Y* | Y* | Y* | Y* | N | |
In fireproof shafts | Y* | Y* | Y* | Y* | Y* | Y* | N | |
In plenum communications raceways | Y* | Y* | N | N | N | N | N | |
In riser communications raceways | Y* | Y* | N | N | N | N | N | |
In riser cable routing assemblies | Y* | Y* | N | N | N | N | N | |
In one- and two-family dwellings | Y* | Y* | Y* | Y* | Y* | Y* | N | |
Within buildings in other than air-handling spaces and risers | General | Y* | Y* | Y* | Y* | Y* | Y* | N |
In one- and two-family dwellings | Y* | Y* | Y* | Y* | Y* | Y* | N | |
Supported by cable trays | Y* | Y* | Y* | Y* | Y* | N | N | |
In rigid metal conduit (RMC) and intermediate metal conduit (IMC) | Y* | Y* | Y* | Y* | Y* | Y* | Y* | |
In any raceway recognized in Chapter3 | Y* | Y* | Y* | Y* | Y* | Y* | N | |
In plenum communications raceways | Y* | Y* | Y* | N | N | N | N | |
In riser communications raceways | Y* | Y* | Y* | N | N | N | N | |
In riser cable routing assemblies | Y* | Y* | Y* | N | N | N | N | |
In general-purpose communications raceways | Y* | Y* | Y* | N | N | N | N | |
In general-purpose cable routing assemblies | Y* | Y* | Y* | N | N | N | N | |
Note: An "N" indicates that the cable type shall not be permitted to be installed in the application. A "Y*" indicates that the cable type shall be permitted to be installed in the application subject to the limitations described in 830.113.
Informational Note No. 1: Part V of Article 830 covers installation methods within buildings. This table covers the applications of listed network-powered broadband communications cables in buildings. The definition of Point of Entrance is in 830.2.
Informational Note No. 2: For information on the restrictions to the installation of network-powered broadband communications cables in ducts specifically fabricated for environmental air, see 830.113(B)."