The provisions of Article 411 of NFPA 70 are adopted by reference with the following modification:
1. Revise section 411.3 to read:
"Low-Voltage Lighting Systems.
(A) General. Lighting systems operating at 30 volts ac or 60 dc shall consist of an isolating power supply, the low-voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply shall be rated for 25 amperes maximum under all load conditions.
(B) Class 2. Listed Class 2 lighting equipment shall be rated in conformance with Chapter 9, Table 11(A) or Table 11(B)."