14E-5-530  Motion picture and television studios and similar locations.
   The provisions of Article 530 of NFPA 70 are adopted by reference with the following modification:
1.   Revise section 530.11 to read:
   “Permanent Wiring. The permanent wiring shall be Type MI cable, or in approved raceways.
   Exception: Communications circuits; audio signal processing, amplification, and reproduction circuits; Class 1, Class 2, and Class 3 remote-control or signaling circuits and power-limited fire alarm circuits shall be permitted to be wired in accordance with Articles 640, 725, 760, and 800.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)