Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
CHAPTER 14E-1 GENERAL
CHAPTER 14E-2 WIRING AND PROTECTION
CHAPTER 14E-3 GENERAL REQUIREMENTS FOR WIRING METHODS AND MATERIALS
CHAPTER 14E-4 EQUIPMENT FOR GENERAL USE
CHAPTER 14E-5 SPECIAL OCCUPANCIES
CHAPTER 14E-6 SPECIAL EQUIPMENT
CHAPTER 14E-7 SPECIAL CONDITIONS
CHAPTER 14E-8 COMMUNICATIONS SYSTEMS
CHAPTER 14E-9 TABLES
CHAPTER 14E-10 INFORMATIVE ANNEXES
CHAPTER 18-27 RESERVED*
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
14E-5-504  Intrinsically safe systems.
   The provisions of Article 504 of NFPA 70 are adopted by reference without modification.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-505  Zone 0, 1, and 2 locations.
   The provisions of Article 505 of NFPA 70 are adopted by reference without modification.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-506  Zone 20, 21, and 22 locations for combustible dusts or ignitable fibers/flyings,
   The provisions of Article 506 of NFPA 70 are adopted by reference with the following modifications.
1.   Revise subsection 506.15(A) by deleting items (3) and (4).
2.   Revise subsection 506.15(C) item (3) to read:
   “Type MI cable with listed termination fittings.”
3.   Revise subsection 506.15(C) by deleting items (4), (5), and (6).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-510  Hazardous (classified) locations – Specific.
   The provisions of Article 510 of NFPA 70 are adopted by reference without modification.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-511  Commercial garages, repair and storage.
   The provisions of Article 511 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 511.7(A)(1) to read:
   “Fixed Wiring Above Class I Locations. All fixed wiring above Class I locations shall be in metal raceways, flexible metal conduit, liquidtight flexible metal conduit, or shall be Type MI, or PLTC cable in accordance with Article 725, or Type TC cable or Type ITC cable in accordance with Article 727.”
2.   Revise section 511.8 to read:
   “Underground Wiring. Underground wiring shall be installed in threaded rigid metal conduit or threaded intermediate metal conduit.”
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-513  Aircraft hangars.
   The provisions of Article 513 of NFPA 70 are adopted by reference with the following modification:
1.   Revise subsection 513.7(A) to read:
   “Fixed Wiring. All fixed wiring in a hangar but not installed in a Class I location as classified in 513.3 shall be installed in metal raceways or shall be Type MI cable.”
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-514  Motor fuel dispensing facilities.
   The provisions of Article 514 of NFPA 70 are adopted by reference with the following modification:
1.   Revise section 514.8 to delete Exception No. 2.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-515  Bulk storage plants.
   The provisions of Article 515 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 515.7(A) to read:
   “Fixed Wiring. All fixed wiring above Class I locations shall be in metal raceways, or Type MI, Type TC, or Type PLTC and Type PLTC-ER cable in accordance with the provisions of Article 725, or Type ITC and Type ITC-ER cable as permitted in 727.4. The cable shall be terminated with listed fittings.”
2.   Revise subsection 515.8(A) to read:
   “Wiring Method. Underground wiring shall be installed in threaded rigid metal conduit or threaded steel intermediate metal conduit.”
3.   Delete subsection 515.8(C).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-5-516  Spray application, dipping, coating, and printing processes using flammable or combustible materials.
   The provisions of Article 516 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 516.7(A) to read:
   “Wiring. All fixed wiring above the Class I and II locations shall be in metal raceways; where cables are used, they shall be Type MI or Type TC. Cellular metal floor raceways shall only be permitted to supply ceiling outlets or as extensions to the area below the floor of a Class I or II location. Where cellular metal floor raceways are used, they shall not have connections leading into or passing through the Class I or II location unless suitable seals are provided.”
2.    Revise subsection 516.38(A) to read:
   “Wiring. All fixed wiring above the Class I and II locations shall be in metal raceways; where cables are used, they shall be Type MI or Type TC cable. Cellular metal floor raceways shall only be permitted to supply ceiling outlets or as extensions to the area below the floor of a Class I or II location. Where cellular metal raceways are used, they shall not have connections leading into or passing through the Class I or II location unless suitable seals are provided.”
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)