14E-5-515  Bulk storage plants.
   The provisions of Article 515 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 515.7(A) to read:
   “Fixed Wiring. All fixed wiring above Class I locations shall be in metal raceways, or Type MI, Type TC, or Type PLTC and Type PLTC-ER cable in accordance with the provisions of Article 725, or Type ITC and Type ITC-ER cable as permitted in 727.4. The cable shall be terminated with listed fittings.”
2.   Revise subsection 515.8(A) to read:
   “Wiring Method. Underground wiring shall be installed in threaded rigid metal conduit or threaded steel intermediate metal conduit.”
3.   Delete subsection 515.8(C).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)