15-28-190  Breathing apparatus required.
   The name and address of the manufacturer or the nearest producer of the specific hazardous material being used and a placard outlining emergency first aid directions shall be posted and remain posted in a conspicuous place at the points of unloading and use and in at least one other approved location.
   Oxygen-generating or self-contained air or oxygen masks having a United States Bureau of Mines or National Institute of Occupational Safety and Health approval for a minimum of one-half hour protection shall be maintained in a readily accessible location, outside the areas of probable contamination and sufficient for all personnel associated with the operation.
   Additional air or oxygen containers which will provide for a minimum of one hour use of each mask shall be kept at the location of each gas mask. All personnel that may be required to use gas masks must be required at reasonable intervals to practice their application and use. Gas masks must be kept in condition, ready for immediate use at all times with fully charged containers.
   An approved repair kit with all the necessary tools, appurtenances and material required to repair a leak or replace a defective valve or other part, shall be kept in a location accessible to the tank car and outside the probable area of contamination.
   Protective clothing suitable for use with the materials stored shall be provided and kept in good condition where its use will provide effective protection against the hazardous material.
   Gas masks, repair kit and duplicate wrenches shall be kept in a conspicuous location and shall be conspicuously labeled for immediate identification.
(Prior code §  92-14.5)
ARTICLE III.  OXIDIZING MATERIALS (15-28-200 et seq.)
15-28-200  Storage requirements.
   Oxidizing materials shall be stored, kept or handled in rooms or buildings complying with the requirements for hazardous chemicals, except as permitted in Section 15-28-220 and except that the area of such buildings shall comply with Sections 13-48-070 and 13-48-080 for industrial or storage occupancies in buildings permitted in Chapter 13-112. The maximum heights of such buildings shall be determined by Chapter 13-112. Such buildings and rooms shall be equipped with a standard system of automatic sprinklers. Ventilation of such rooms shall be in accordance with Section 15-28-080 of this Code.
(Prior code §  92-15)
15-28-210  Safety clearances.
   No oxidizing material building shall be located nearer than 100 feet to any building in which there is an institutional, assembly or open air assembly unit, except as otherwise provided.