Stationary acetylene gas generators shall be installed in a suitable building which shall be constructed and maintained in accordance with the building provisions of this Code applicable to buildings housing such apparatus.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
The connections from generators to service pipes shall be made with right and left thread nipples or long thread nipples with locknuts or approved unions. Unions depending on gaskets to make tight are prohibited in pipe sizes under two and one-half inches. Piping shall be arranged so that any moisture will drain to the generator, drip pots or seals. Each generator shall be provided with a gas escape or relief pipe to take care of over- or after-generation. Such gas escape or relief pipes shall be of galvanized iron of the following sizes:
Size of Machine (pounds) | Minimum Diameter of Pipe |
Up to 25 inclusive | 3/4 inch |
26 to 100 inclusive | 1 1/4 inch |
101 to 200 inclusive | 1 1/4 inch |
Over 200 | 1 1/2 inch |
The relief pipe shall be made as short and as free from bends as practicable. However, if it is more than 50 feet in length or has more than four right-angle bends, a pipe of one size larger than that required by this table shall be used. It shall be substantially installed without traps and in such manner that any condensation will drain back to the generator or its component parts. It shall be carried to a suitable point outside the building and shall terminate in an approved hood or bend at least 12 feet above the ground and remote from windows or other openings into buildings, and shall be so constructed that it cannot be obstructed by rain, snow, ice, insects or birds.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
In cases where the generators are supplied with water from city mains or house pipes, and where dangerous pressures might be built up, no direct pipe connection with the generator shall be permitted. In such cases the supply pipe shall terminate some distance above the regularly provided opening for filling, so that water can be observed as it enters the generator.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
“Portable generator” means an acetylene generator of not more than 30 pounds carbide capacity, which has been approved for portable use by the Underwriters Laboratories and included in the “List of Inspected Gas, Oil and Miscellaneous Appliances” dated November, 1973, of low-pressure and medium pressure acetylene generators.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
Portable generators shall not be installed or used inside of buildings unless a permit for such use in said location shall first be secured from the fire commissioner. It shall be the duty of the fire commissioner to inspect the premises wherein such generator is to be used, before issuing such permit. The person applying for a permit shall pay the comptroller a fee of $3.00 for such inspection. Should the inspection show compliance with the provisions of this section, the fire commissioner shall issue a permit for such installation and use.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616; Amend Coun. J. 11-16-11, p. 13798, Art. I, § 11; Amend Coun. J. 5-18-16, p. 24131, § 150)
Portable generators shall not be used in rooms of total volume less than 35 times the nominal aggregate gas-generating capacity per hour of all such generators in the room. Portable generators shall not be used in any room containing flammable liquids or gases, or in which any dust-producing process is carried on, or in which any highly combustible or explosive materials are contained. Portable generators shall not be used in any poorly ventilated room.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
Before any cutting or welding process, the floor shall be swept clean and, if of wood, shall be sprinkled with water. The scene of such work shall be inspected 30 minutes after every cutting or welding operation and all smoldering sparks shall be extinguished.
Extra gas cylinders shall not be stored in the same room in which a portable generator is used.
Generators shall be cleaned and recharged and the air mixture shall be blown off outside of the building. Generators, when charged, shall not be moved by crane or derrick. When not in use they shall not be stored in any room in which open lights or fires are used unless free of carbide and thoroughly purged of gas.
Storage rooms for portable generators shall be thoroughly ventilated.
Cutting and welding operations shall not be carried on within ten feet of any combustible material other than the floor.
Generators shall not be placed where water will freeze. Salt or other corrosive chemicals shall not be used as a protection against freezing.
Not more than one cutting or welding flame shall be used with any portable generator unless permanently attached and piped as required under Section 15-26-480 for semiportable installations.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
Portable generators shall not be installed in a permanent or semipermanent location unless provided with vent and relief piping, equipped with approved interlocking devices, to the open air outside of buildings.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)