15-26-460  Portable generator – Prohibited locations.
   Portable generators shall not be used in rooms of total volume less than 35 times the nominal aggregate gas-generating capacity per hour of all such generators in the room. Portable generators shall not be used in any room containing flammable liquids or gases, or in which any dust-producing process is carried on, or in which any highly combustible or explosive materials are contained. Portable generators shall not be used in any poorly ventilated room.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)