Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
ARTICLE I.  GENERAL (15-26-010 et seq.)
15-26-010  Licenses, permits and special exit requirements.
   For licensing provisions and permit requirements, see Chapter 15-4. For special exit requirements, see Chapter 13-112.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-020  Definitions.
   For purposes of this chapter, the following definitions apply.
   Fume or Flammable Compressed Gas Building, Rooms and Gases.
      (a)   “Fume or flammable compressed gas building” means a building, or part of a building, designed, intended or used for the purpose of manufacturing, compressing or storing any fume hazard gas or any flammable compressed gas, either at a pressure of more than 15 pounds per square inch or in a quantity of more than 2,500 cubic feet.
      (b)   “Fume or flammable compressed gas room” means a room designed, intended or used for any of the purposes described under subsection (a) of this section and which is located in a building other than a fume or flammable compressed gas building.
      (c)   “Fume hazard gases” means ammonia gas, chlorine gas, phosgene gas, sulphur dioxide gas, chlororipicrin gas, cyanogen gas, hydrogen cyanide gas, nitrogen peroxide gas and other gas which has an equal or greater danger to life; and any other gas which, as determined by the committee on standards and tests, is in fact a poisonous irritant or corrosive gas and is not susceptible to fire or explosion, shall each be defined as a fume hazard gas.
      (d)   Flammable compressed gases, acetylene gas, ammonia gas, ether gas, ethyl chloride gas, ethylene gas, liquefied hydrocarbon gases, liquefied petroleum gases, hydrogen gas, illuminating gas, methyl chloride gas and any other gas which is a poisonous, irritant or corrosive gas and is also a gas susceptible to explosion under any condition or is not a poisonous, irritant or corrosive gas but is a gas susceptible to burning under any condition shall each be defined as a flammable compressed gas.
   Fume or Flammable Compressed Gas. No sprinkler system shall be required for any fume or flammable compressed gas building of Type IA, IB or IC construction, nor for any room intended for the storage and use of chlorine gas for no purpose other than the operation of a water purification plant or refrigerating unit, nor for any unit of noncombustible construction used exclusively for the production of manufactured gas.
   The following definitions shall apply to sections regulating liquefied petroleum gas only:
      1.   “Containers” means all vessels, such as tanks, cylinders or drums used for transportation or storing of liquefied petroleum gas.
      2.   “Capacity of container” means the amount of liquefied petroleum gas that a container will hold. For Interstate Commerce Commission or Department of Transportation approved containers, this is expressed in pounds of liquefied petroleum gas. For American Society of Mechanical Engineers approved containers, this is expressed in gallons of water capacity.
      3.   “Liquefied petroleum gas” means and includes any material which is composed predominately of any of the following hydrocarbons, or mixtures of them: propane, propylene, butane (normal butane or isobutane) and butylenes.
      4.   “Excess flow valve” means a valve intended to prevent a flow rate greater than the maximum preset flow rate.
      5.   “Filling density” means the ratio of the weight of gas in a container to the weight of water the container will hold at 60 degrees Fahrenheit expressed as a percentage.
      6.   “Safety relief valve” means a valve intended to open upon buildup of excess pressure in the container.
      7.   “Vaporizer” means a device intended to change liquefied petroleum gas from a liquid state to a gaseous state.
      8.   “Used” or “in use” means connected to a system for use.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-030  Manufactured gas buildings – Exempted from chapter requirements – When.
   Any building used exclusively for the production, distribution or storage of manufactured gas as a public utility shall be exempt from the requirements of this part of this chapter dealing with construction except the provisions of Section 15-24-170 for tanks for flammable liquids; provided, however, that such buildings shall be constructed, as provided in Section 13-104-020, entirely of noncombustible materials, with interior framing member either with or without fireproof covering.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-040  Public utility company rules.
   Every system of gas supplied by a public utility company shall be installed and maintained in accordance with the rules of that public utility company.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-050  Acetylene lighting prohibited.
   No system of artificial lighting and no lamp, torch or other device for illumination which employs acetylene shall be installed in any new or existing building.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-060  Portable acetylene lamps and stoves.
   It shall be unlawful to use portable self-generating acetylene lamps or stoves inside of any completed building in the city.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
ARTICLE II.  BUILDINGS AND ROOMS (15-26-070 et seq.)
Loading...