13-76-101  Sprayed fire-resistant materials.
   The bond strength of sprayed fire-resistant materials (SFRM) installed throughout the building shall be in accordance with Table 13-76-101.
Table 13-76-101
Minimum Bond Strength
 
Height of Building(a)
SFRM Minimum Bond Strength
80 to 420 feet
430 psf
Greater than 420 feet
1,000 psf
 
(a) Determined in accordance with Section 13-48-020.
(Added Coun. J. 9-6-17, p. 55278, Art. VII, § 9)