Skip to code content (skip section selection)
Compare to:
San Francisco Overview
San Francisco Building Inspection Commission (BIC) Codes
SAN FRANCISCO BUILDING INSPECTION COMMISSION CODES
BUILDING CODE 2016 Edition
ELECTRICAL CODE 2016 Edition
EXISTING BUILDING CODE 2016 Edition
PUBLISHER’S NOTE
PREFACE
Chapter 1 SCOPE AND ADMINISTRATION
Chapter 2 DEFINITIONS
Chapter 3 PROVISIONS FOR ALL COMPLIANCE METHODS
Chapter 4 PRESCRIPTIVE COMPLIANCE METHOD
Chapter 4A EARTHQUAKE HAZARD REDUCTION IN UNREINFORCED MASONRY BEARING WALL BUILDINGS
Chapter 4B SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS
Chapter 4C PARAPETS AND APPENDAGES - RETROACTIVE PROVISIONS
Chapter 4D MANDATORY EARTHQUAKE RETROFIT OF WOOD-FRAME BUILDINGS
Chapter 4E BUILDING FACADE INSPECTION AND MAINTENANCE - RETROACTIVE PROVISIONS
Chapter 5 to Chapter 15
Chapter 16 REFERENCED STANDARDS
CALIFORNIA EXISTING BUILDING CODE (CEBC) APPENDICES
(CEBC) APPENDIX A CHAPTER A1 SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS
REFERENCED STANDARDS
(CEBC) APPENDIX A CHAPTER A3 PRESCRIPTIVE PROVISIONS FOR SEISMIC STRENGTHENING OF CRIPPLE WALLS AND SILL PLATE ANCHORAGE OF LIGHT, WOOD-FRAME RESIDENTIAL BUILDINGS
(CEBC) APPENDIX A CHAPTER A4 EARTHQUAKE RISK REDUCTION IN WOOD-FRAME RESIDENTIAL BUILDINGS WITH SOFT, WEAK OR OPEN FRONT WALLS
(CEBC) APPENDIX A CHAPTER A6 REFERENCED STANDARDS
GREEN BUILDING CODE 2016 Edition
HOUSING CODE 2016 Edition
MECHANICAL CODE 2016 Edition
PLUMBING CODE 2016 Edition
Table of Amendments

You are viewing an archived code

Loading...
SECTION 405B – GENERAL REQUIREMENTS
405B.1  General.  All buildings shall have a seismic resisting system conforming with ASCE 7-10 Section 12.2, except as modified by this chapter.
405B.2  Alterations and Repairs.  Alterations and repairs required to meet the provisions of this chapter shall comply with all other applicable structural requirements of this code unless specifically provided for in this chapter.
405B.3  Requirements for Plans.  In addition to the requirements of San Francisco Building Code Section 106A.3.3 of this code, the following construction information shall be included in the plans required by this chapter:
   1.   Dimensioned floor and roof plans showing existing walls and the size and spacing of floor and roof framing members and sheathing materials. The plans shall indicate all existing and new crosswalls and shear walls and their materials of construction. The location of these walls and their openings shall be fully dimensioned and drawn to scale on the plans.
   2.   Dimensioned wall elevations showing openings, piers, wall classes as defined in Section 406B.3.3.6, thickness, heights, wall shear test locations, and cracks or damaged portions requiring repairs. Where the exterior face is veneer, the type of veneer, its thickness and its bonding and/or ties to the structural wall masonry shall also be noted.
   3.   The type of interior wall and ceiling materials and framing.
   4.   The extent and type of existing wall anchorage to floors and roof when used in the design.
   5.   The extent and type of parapet and appendage corrections which were previously performed, if any.
   6.   Repair details, if any, of cracked or damaged unreinforced masonry wall walls required to resist forces specified in this chapter.
   7.   All other plans, sections and details necessary to delineate required retrofit construction.
   8.   The design procedure used shall be stated on both the plans and the permit application.
   9.   Details of the anchor prequalification program required by Section 415B, if utilized, including location and results of all tests.
   10.   In buildings with party walls, the details of construction on both sides of each party wall shall be shown. Where required by Section 411B.1, Item 5 the owners’ consent statements shall be included with the plans.
SECTION 406B – MATERIALS REQUIREMENTS
406B.1  General.  All materials permitted by this chapter, including their appropriate allowable design values and those existing configurations of materials specified herein, may be utilized to meet the requirements of this chapter.
406B.2  Existing Materials.  All existing materials utilized as part of the required vertical load-carrying or lateral force-resisting system shall be in sound condition or shall be repaired or removed and replaced with new materials. All unreinforced masonry materials shall comply with the following requirements:
   1.   The construction (lay-up) of the masonry units complies with Section 406B.3.2 and the quality of bond between the units has been verified to the satisfaction of the Building Official.
   2.   Concrete masonry units are verified to be load-bearing units complying with ASTM Standard Specification C 90 or such other standard as is acceptable to the Building Official.
   3.   Hollow clay tile units are verified to be structural load-bearing units complying with ASTM Standard Specification C 34 or such other standard as is acceptable to the Building Official.
   4.   The compressive strength of plain concrete walls shall be determined based on cores taken from each class of concrete wall. The location and number of tests shall be the same as prescribed for strength tests in Sections 406B.3.3.2 and 406B.3.3.3.
406B.3  Existing Unreinforced Masonry Walls.
406B.3.1  General.  All unreinforced masonry walls utilized to carry vertical loads or seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this section. All masonry that does not meet the minimum standards established by this chapter shall be removed and replaced with new materials, repaired or alternatively shall have its structural functions replaced with new materials and shall be anchored to supporting elements.
406B.3.2  Construction (lay-up) of walls.
406B.3.2.1  Multi-wythe solid brick.  The facing and backing shall be bonded so that not less than 10 percent of the exposed face area is composed of solid headers extending not less than 4 inches (101.6 mm) into the backing. The clear distance between adjacent full-length headers shall not exceed 24 inches (609.6 mm) vertically or horizontally. Where the backing consists of two or more wythes, the headers shall extend not less than 4 inches (101.6 mm) into the most distant wythe or the backing wythes shall be bonded together with separate headers whose area and spacing conform to the foregoing. Wythes of walls not bonded as described above shall be considered as veneer. Veneer wythes shall not be included in the effective thickness used in calculating the height to thickness and the shear capacity of the wall.
406B.3.2.2  Grouted or ungrouted hollow concrete or clay block and structural hollow clay tile.  These materials shall be laid in a running bond pattern.
   Other lay-up patterns may be acceptable if their performance can be justified as being at least equal to those specified above.
406B.3.3  Mortar.
406B.3.3.1  Tests.  The quality of mortar in all masonry walls shall be determined by performing in-place shear tests in accordance with Section 414B. Alternative methods of testing may be approved by the Building Official for masonry walls other than brick.
406B.3.3.2  Location of tests.  The shear tests shall be taken at locations representative of the mortar conditions throughout the entire building, taking into account variations in workmanship at different building height levels, variations in weathering of the exterior surfaces, and variations in the condition of the interior surfaces due to deterioration caused by leaks and condensation of water and/or by the deleterious effects of other substances contained within the building. The exact test locations shall be determined at the building site by the engineer or architect in responsible charge of the structural design work. An accurate record of all such tests and their location in the building shall be recorded, and these results shall be submitted to the Department for approval as part of the structural analysis.
406B.3.3.3  Number of tests.  The minimum number of tests per class shall be as follows:
   1.   At each of both the first and top stories, not less than two tests per wall or line of wall elements providing a common line of resistance to lateral forces.
   2.   At each of all other stories, not less than one test per wall or line of wall elements providing a common line of resistance to lateral forces.
   3.   In any case, not less than one test per 1,500 square feet (139.355 m2) of wall surface nor less than a total of eight tests.
406B.3.3.4  Minimum quality of mortar.
   1.   Mortar shear test values, vto, in psi shall be obtained for each in-place shear test in accordance with the following equation:
      vto = (Vtest/Ab) - p D+L      (4B-1)
   2.   The mortar shear strength, vt, is the value in psi that, after discarding the lowest 20 percent of the mortar shear test values, vto, is the lowest of the remaining 80 percent of the mortar shear test values.
   3.   Any unreinforced masonry bearing wall with vto, or with mortar shear strength, vt, less than 30 psi (206.84 kPa) shall be either removed, entirely pointed and retested or have its structural function replaced and shall be anchored to supporting elements in accordance with Section 406B.3.1 and Section 413B.8. When existing mortar in any wythe is pointed to increase its shear strength and retested, the condition of the mortar in the adjacent bed joints of the inner wythe or wythes and the opposite outer wythe shall be examined for extent of deterioration. The shear strength of any wall class shall be no greater than that of the weakest wythe of that class.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
406B.3.3.5  Collar joints.  The collar joints shall be inspected at the test locations during each in-place shear test, and estimates of the percentage of the surfaces of adjacent wythes which are covered with mortar shall be reported along with the results of the in-place shear tests.
406B.3.3.6  Unreinforced masonry classes.  All existing unreinforced masonry shall be categorized into one or more classes based on quality of construction, state of repair, deterioration and weathering. A class shall be characterized by the allowable masonry shear stress determined in accordance with Section 408B.2. Classes shall be defined for whole walls, not for small areas of masonry within a wall.
406B.3.3.7  Pointing.  All deteriorated mortar joints in unreinforced masonry bearing walls shall be pointed according to Section 416B. Nothing shall prevent pointing of any deteriorated masonry wall joints before the tests are made, except as required in Section 407B.1.
SECTION 407B – QUALITY CONTROL
407B.1  Pointing.  All preparation and mortar pointing shall be performed with special inspection.
   EXCEPTION:  At the discretion of the Building Official, incidental pointing may be performed without special inspection.
407B.2  Masonry Shear Tests.  In-place shear tests shall comply with Section 414B.
407B.3  Existing Wall Anchors.  Existing wall anchors utilized as all or part of the required tension anchors shall be tested in pullout according to Section 415B. The minimum number of anchors tested shall be four per floor, with two tests at walls with joists framing into the wall and two tests at walls with joists parallel to the wall, but not less than 10 percent of the total number of existing tension anchors at each level.
407B.4  New Bolts.  Twenty-five percent of all new embedded bolts resisting only shear forces in unreinforced masonry walls shall be tested using a calibrated torque wrench in accordance with Section 415B.
   EXCEPTION: The number of bolts tested may be reduced to 10 percent when special inspection in accordance with Section 1704 is provided during installation but in no case shall less than two bolts per 500 square feet (46.45 m2) of wall or four bolts per wall be tested.
   All new embedded bolts resisting tension forces or a combination of tension and shear forces shall be subject to periodic special inspection in accordance with San Francisco Building Code Section 1704 prior to placement of the bolt and grout or adhesive in the drilled hole. Five percent of all embedded bolts resisting tension forces, but not less than two bolts, shall be subject to a direct tension test and an additional 20 percent, but not less than three bolts, shall be tested using a torque calibrated wrench. Testing shall be performed in accordance with Section 415B.
   New through bolts and existing bolts installed under the Parapet Safety Program need not be tested.
SECTION 408B – ALLOWABLE DESIGN VALUES
408B.1  Allowable Values.
408B.1.1  Existing materials.  Allowable values for existing materials are given in Table 4B-D, and for new materials in Table 4B-E.
408B.1.2  Values not specified.  Allowable values not specified in this chapter shall be as specified elsewhere in this code.
408B.2  Masonry shear.  The allowable unreinforced masonry shear stress, va shall be determined for each masonry class from the following equation:
      va = 0.1vt + 0.15P D /A       (4B-2)
   The mortar shear test value, vt, shall be determined in accordance with Section 406B.3.3, and shall not exceed 100 psi (689.476 kPa) for the determination of va.
   The one-third increase in allowable values of this code for short-term loading is not allowed for va.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
408B.3  Masonry Compression.  Where any increase in dead plus live compression stress occurs, the allowable compression stress in unreinforced masonry shall not exceed 100 psi (689.476 kPa). The one-third increase in allowable stress of this code is allowed.
408B.4  Masonry Tension.  Unreinforced masonry shall be assumed as having no tensile capacity.
408B.5  Unreinforced Masonry Materials Other Than Solid Brick.  The provisions of this chapter are primarily intended for brick construction but are also applicable to other unreinforced masonry materials when the following conditions are satisfied:
   1.   The building does not exceed two stories in height.
   2.   In the case of hollow concrete and clay block, the shear stress is limited to that permitted by Equations 4B-1 and 4B-2 based on the net area in contact through the bed joints but not more than that calculated using a mortar shear strength, vt, of 100 psi (689.476 kPa).
   3.   In the case of plain concrete, the compressive strength (f´c) shall be not less than 900 psi (6,205.28 kPa) and the allowable shear strength is limited to not more than 0.02f´c.
   4.   In the case of all other unreinforced masonry materials, the shear stress is limited to 3 psi (20.684 kPa) based on the net area in contact through the bed joint.
   Unreinforced masonry not meeting the above criteria shall have its structural function replaced and shall be resupported, if required, in accordance with Section 413B.8.
408B.6  Existing Tension Anchors.  The allowable resistance values of the existing anchors shall be 40 percent of the average of the tension tests of existing anchors having the same wall thickness and joist orientation. The one-third increase in allowable value of this code is not allowed for existing tension anchors.
408B.7  Foundations.  For existing foundations, new total dead loads may be increased over existing dead load by 25 percent. New total dead load plus live load plus seismic forces may be increased over existing dead load plus live load by 50 percent.
   EXCEPTION:  In buildings located in poor soil areas as defined in Chapter 4A, any increase in dead load shall require an evaluation of the existing foundation system.
   Higher values may be justified only in conjunction with a geotechnical investigation. A foundation investigation shall be also submitted with the building permit application when:
      1.   A building has an existing full or partial pile supported, or similar foundation system or whenever the installation of such a system is proposed as part of the strengthening.
      2.   Whenever there is evidence of significant distress attributable to foundation or geotechnical conditions.
      3.   An investigation is required by San Francisco Building Code Section 1803 or 1804.
      4.   It is desired to prove that the building is not on poor soil as permitted by the exception to Section 403A.
SECTION 409B – SELECTION OF PROCEDURE
409B.1  General.  Except as modified herein, the analysis and design relating to the structural alteration of existing buildings shall be in accordance with this code.
409B.2  Selection of Procedure.  All buildings shall be analyzed by either the General Procedure of Section 410B or, when applicable, buildings may be analyzed by the Special Procedure of Section 411B.
   EXCEPTIONS:
      1.   A building may be strengthened to the Bolts-plus level by complying only with the requirements for wall anchorage (tension bolts), diaphragm shear transfer (shear bolts) and out-of-plane wall and parapet and appendage bracing, provided the entire building complies with all of the following requirements:
         (1)   The building does not have any vertical irregularities of Types 1a or 1b (Soft Story), 4 (In-Plane Discontinuity) or 5a or 5b (Weak Story) as defined in ASCE 7-10 Table 12.3-2 or horizontal irregularities of Types 3 (Diaphragm Discontinuity) or 4 (Out-of-Plane Offset) as defined in ASCE 7-10 Table 12.3-1 or those irregularities are corrected.
         (2)   The building does not contain any Group A Occupancies with an occupant load of 300 or more, or Group E, Group I or Group H-1, H-2 or H-4 Occupancies.
         (3)   The building has a mortar shear strength, vt, as determined by Section 406B.3.3, of 30 psi (206.843 kPa) or more for all masonry classes.
         (4)   The building has wood or plywood diaphragms at all levels above the base of building.
         (5)   The building contains a maximum of six stories above the base of the building. The base shall be the ground level and basement or basements shall be excluded from the story count.
            EXCEPTION: In an otherwise qualifying building of greater than six stories, a maximum of six of the uppermost contiguous stories may be retrofitted using the Bolts-Plus Procedure, providing the building is not located on poor soil as defined in Section 403A. The masonry walls required by Item 7 below shall occupy not less than 50 percent of the wall length in the lowest two of the uppermost six stories. Nonqualifying stories and stories below the uppermost six shall be retrofitted to any other procedure for which they qualify.
         (6)   The building has or will be provided with crosswalls as defined in Section 411B.3 at a spacing that does not exceed 40 feet (12.192 m) on center. Any story which does not have or is not provided with complying crosswalls and all stories below that story shall be analyzed using the General Procedure of Section 410B or, where applicable, the Special Procedure of Section 411B. The floor structure that separates the Bolts-Plus and General or Special Procedure stories shall be investigated for its adequacy to act as a diaphragm in accordance with Section 410B.1 or, where the Special Procedure is applicable, Section 411B.4.
         (7)   The building has or will be provided with a minimum of two lines of vertical elements of the lateral force resisting system parallel to each axis. Masonry walls shall have wall piers with a height-to-width ratio that does not exceed 2 to 1 and shall occupy not less than 40 percent of the wall’s length in order to be considered as providing a line of resistance. Existing moment frames and other lines of resistance added or altered to comply with this requirement shall fully comply with Section 412B. At least one line in each direction shall be a masonry or concrete shear wall.
         (8)   In buildings containing one or more party walls, the Bolts-Plus Procedure shall not be used unless each building sharing a party wall individually complies with all of the limitations set forth above and the owner of each such building consents to the use of the procedure in writing.
            When the Bolts-Plus Procedure is applicable, the forces to be used for diaphragm shear transfer and irregularity correction shall be those specified in Sections 411B.5 and 411B.6 and h/t ratios shall be evaluated in accordance with Section 411B.7. When the intersection of the diaphragm span and demand capacity ratio falls outside the three regions of Figure 4B-1, the h/t ratios for “all other buildings” in Table 4B-B shall be used. The measures used to comply shall be part of, and be coordinated with, the complete strengthening scheme described in the engineering report required by Section 404A.2.3.
      2.   Buildings which are strengthened to conform to the requirements of SFEBC Section 301.2 in effect on or after May 21, 1973, are exempt from com- pliance with the provisions of this chapter.
SECTION 410B – GENERAL PROCEDURE
410B.1  Minimum Design Lateral Forces.  Buildings shall be analyzed to resist minimum lateral forces assumed to act nonconcurrently in the direction of each of the main axes of the structure in accordance with the following:
      V = 0.10 W         (4B-3)
   EXCEPTION:  The lateral forces need not exceed those prescribed by San Francisco Building Code Section 1613.
   For buildings more than one story in height, the total force shall be distributed over the height of the building in accordance with the procedures of San Francisco Building CodeChapter 16.
   For the purpose of this chapter, a dynamic analysis need not be performed for those buildings with irregularities, as defined in ASCE 7-10 Table 12.3-2 and ASCE 7-10 Table 12.3-1 which would otherwise require such analysis. All other design and analysis requirements of those tables shall apply.
410B.2  Lateral Forces on Elements of Structures.  Parts of structures shall be analyzed and designed as required in San Francisco Building Code Chapter 16 .
   EXCEPTIONS:
      1.   Unreinforced masonry walls for which height-to-thickness ratios do not exceed ratios set forth in Table 4B-B need not be analyzed for out-of-plane loading. Unreinforced masonry walls which exceed the allowable h/t ratios of Table 4B-B shall be braced according to Section 413B.5.
      2.   Parapets complying with Section 413B.6 need not be analyzed for out-of-plane loading.
      3.   Out-of-plane anchorage of the walls shall be designed to 0.3 times the mass of the wall.
410B.3  Shear Walls (In-Plane Loading).  Shear walls shall comply with Section 412B.
410B.4  Chords.  When required by the structural analysis, chord forces of horizontal diaphragms shall be developed in existing materials or by the addition of new materials.
SECTION 411B – SPECIAL PROCEDURE
411B.1  Limits for Application.  The Special Procedure of this section may only be applied to buildings with the following characteristics:
   1.   The building is not an essential or hazardous facility.
   2.   Wood or plywood diaphragms at all levels above the base of structure.
   3.   A maximum of six stories above the base of the building. The base shall be the ground level, and basement or basements shall be excluded from the story count.
      EXCEPTION: An otherwise qualifying building of greater than six stories may also be retrofitted using the Special Procedure, provided the building is not located on poor soil as defined in Section 403A or does not contain any Group A Occupancies with an occupant load of 300 or more, or Group E, or Group I Occupancies.
   4.   Except for single-story buildings with an open front on one side only, a minimum of two lines of vertical elements of the lateral force resisting system complying with Section 412B parallel to each axis. At least one line in each direction shall be a masonry or concrete shear wall. Requirements for open front buildings are contained in Section 411B.8.
   5.   In buildings containing one or more party walls, the Special Procedure shall not be used unless each building sharing a party wall individually complies with all of the limitations set forth above, and the owner of each such building consents to the use of the procedure in writing.
411B.2  Lateral Forces on Elements of Structures.  With the exception of the diaphragm provisions in Section 411B .4, elements of structures shall comply with Section 410B.2.
411B.3  Crosswalls.  Crosswalls when used shall meet the requirements of this section.
411B.3.1  Crosswall definition.  A “crosswall” is a wood-framed wall sheathed with any of the materials described in Table 4B-D or 4B-E or other system as defined in Section 411B .3.5. Spacing of crosswalls shall not exceed 40 feet (12.19 m) on center measured perpendicular to the direction of consideration and shall be placed in each story of the building. Crosswalls shall extend the full story height between diaphragms.
   EXCEPTIONS:
      1.   Crosswalls need not be provided at all levels in accordance with Section 411B.4.2(4).
      2.   Existing crosswalls need not be continuous below a wood diaphragm at or within 4 feet (1.219 m) of grade, provided:
         (1)   Shear connections and anchorage requirements, Section 411B.5 are satisfied at all edges of the diaphragm.
         (2)   Crosswalls with total shear capacity of 0.08åWd interconnect the diaphragm to the foundation.
         (3)   The demand-capacity ratio of the diaphragm between the crosswalls that are continuous to their foundations shall be calculated as:
      DCR = (0.332Wd + Vca)/2vuD      (4B-4)
and DCR shall not exceed 2.5.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
411B.3.2  Crosswall shear capacity.  Within any 40 feet (12.19 m) measured along the span of the diaphragm, the sum of the crosswall shear capacities shall be at least 30 percent of the diaphragm shear capacity of the strongest diaphragm at or above the level under consideration.
411B.3.3  Existing crosswalls.  Existing crosswalls shall have a maximum height-to-length ratio between openings of 1.5 to 1. Existing crosswall connections to diaphragms need not be investigated as long as the crosswall extends to the framing of the diaphragm above and below.
411B.3.4  New crosswalls.  New crosswall connections to the diaphragm shall develop the crosswall shear capacity. New crosswalls shall have the capacity to resist an overturning moment equal to the crosswall shear capacity times the story height. Crosswall overturning moments need not be cumulative over more than two stories.
411B.3.5  Other crosswall systems.  Other systems, such as moment resisting frames, may be used as crosswalls, provided that the yield story drift does not exceed 1 inch (25.4 mm) in any story.
411B.4  Wood Diaphragms.
411B.4.1  Acceptable diaphragm span.  A diaphragm is acceptable if the point (L,DCR) on Figure 4B-1 falls within Regions 1, 2 or 3.
411B.4.2  Demand-capacity ratios.  Demand-capacity ratios shall be calculated for the diaphragm at any level according to the following formulas:
   1.   For a diaphragm without qualifying crosswalls at levels immediately above or below:
      DCR = 0.332Wd/ΣvuD      (4B-5)
   2.   For a diaphragm in a single-story building with qualifying crosswalls:
      DCR = 0.332Wd/(ΣvuD + Vcb )      (4B-6)
   3.   For diaphragms in a multi-story building with qualifying crosswalls in all levels:
      DCR = 0.332ΣWd /(ΣΣvuD + Vcb)      (4B-7)
         DCR shall be calculated at each level for the set of diaphragms at and above the level under consideration. In addition, the roof diaphragm shall also meet the requirements of Formula (4B-6).
   4.   For a roof diaphragm and the diaphragm directly below if coupled by crosswalls:
      DCR = 0.332ΣW d /ΣΣvuD      (4B-8)
411B.4.3  Chords.  An analysis for diaphragm flexure need not be made and chords need not be provided.
411B.4.4  Collectors.  An analysis of diaphragm collector forces shall be made for the transfer of diaphragm edge shears into vertical elements of the lateral force resisting system. Collector forces may be resisted by new or existing elements.
411B.4.5  Diaphragm openings.
411B.4.5.1  Forces.  Diaphragm forces at corners of openings shall be investigated and shall be developed into the diaphragm by new or existing materials.
411B.4.5.2  Demand-capacity ratio.  In addition to the demand-capacity ratios of Section 411B .4.2, the demand-capacity ratio of the portion of the diaphragm adjacent to an opening shall be calculated using the opening dimension as the span.
411B.4.5.3  End quarter of diaphragm.  Where an opening occurs in the end quarter of the diaphragm span, vuD for the demand-capacity ratio calculation shall be based on the net depth of the diaphragm.
411B.5  Diaphragm Shear Transfer.  Diaphragms shall be connected to shear walls with connections capable of developing a minimum force given by the lesser of the following formulas:
      V = 0.2CpWd      (4B-9)
using the Cp values in Table 4B-C, or
      V = vuD            (4B-10)
411B.6  Shear Walls (In-Plane Loading).
411B.6.1  Wall story force.  The wall story force distributed to a shear wall at any diaphragm level shall be the lesser value calculated as:
   1.   For buildings without crosswalls:
         Fwx = 0.132 (Wwx + Wd /2)   (4B-11)
      but need not exceed
         Fwx = 0.132Wwx + vuD      (4B-12)
   2.   For buildings with crosswalls in all levels:
         Fwx = 0.1 (Wwx + Wd /2)      (4B-13)
      but need not exceed
         Fwx = 0.1 [Wwx + ΣWd (vuD/ΣΣvuD)]        (4B-14)
      and need not exceed
         Fwx = 0.1W wx + vuD         (4B-15)
411B.6.2  Wall story shear.  The wall story shear shall be the sum of the wall story forces at and above the level of consideration.
      Vwx = ΣFwx            (4B-16)
411B.6.3  Shear wall analysis.  Shear walls shall comply with Section 412B .
411B.6.4  Moment frames.  Moment frames used in place of shear walls shall be designed as required in San Francisco Building CodeChapter 16 except that the forces shall be as specified in Section 411B.6.1 and the story drift ratio shall be limited to 0.005, except as further limited by Section 412B.4.2.
411B.7  Out-of-Plane Forces – Unreinforced Masonry Walls.
411B.7.1  Allowable unreinforced masonry wall height-to-thickness ratios.  The provisions of Section 410B.2 are applicable except the allowable height-to-thickness ratios given in Table 4B-B shall be determined from Figure 4B-1 as follows:
   1.   In Region 1, height-to-thickness ratios for buildings with crosswalls may be used if qualifying crosswalls are present in all stories.
   2.   In Region 2, height-to-thickness ratios for buildings with crosswalls may be used whether or not qualifying crosswalls are present.
   3.   In Region 3, height-to-thickness ratios for “all other buildings” shall be used whether or not qualifying crosswalls are present.
411B.7.2  Walls with diaphragms in different regions.  When diaphragms above and below the wall under consideration have demand-capacity ratios in different regions of Figure 4B-1, the lesser height-to-thickness ratio shall be used.
411B.8  Open Front Design Procedure.  A single-story building with an open front on one side and crosswalls parallel to the open front may be designed by the following procedure:
   1.   Effective diaphragm span, Li, for use in Figure 4B-1 shall be determined in accordance with the following formula:
      Li = 2 [(Ww /Wd )L + L]x      (4B-17)
   2.   Diaphragm demand-capacity ratio shall be calculated as:
      DCR = 0.332 (Wd + W w ) / [(vuD) + Vcb ]        (4B-18)
Loading...