SECTION 1704 – SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPONSIBILITY AND STRUCTURAL OBSERVATION
1704.2  Replace Exception 2 as follows:
   2.   The special inspections and verifications for foundation concrete, other than cast-in-place drilled piles or caissons, are not required for occupancies in Group R-3 and occupancies in Group U that are accessory to a residential occupancy, but not limited to, those listed in Section 312.1.
      This exception shall not apply to foundations serving as retaining walls of soil over 5 feet (1829 mm) in height measured from the base of the foundation, or the structural design of the footing based on a specified compressive strength, f'c, greater than 2,500 pounds per square inch (psi) (17.2 MPa), regardless of the com- pressive strength specified in the construction documents or used in the footing construction.