Skip to code content (skip section selection)
Compare to:
New York City Overview
The New York City Charter
The New York City Administrative Code
The Rules of the City of New York
THE RULES OF THE CITY OF NEW YORK
Title 1: Department of Buildings
Title 2: Board of Standards and Appeals
Title 3: Fire Department
Title 6: Department of Consumer and Worker Protection
Title 9: Procurement Policy Board Rules
Title 12: Franchise and Concession Review Committee
Title 15: Department of Environmental Protection
Title 16: Department of Sanitation
Title 17: Business Integrity Commission
Title 19: Department of Finance
Title 20: Tax Appeals Tribunal
Title 21: Tax Commission
Title 22: Banking Commission
Title 24: Department of Health and Mental Hygiene
Title 25: Department of Mental Health and Retardation [Repealed]
Title 28: Housing Preservation and Development
Title 29: Loft Board
Title 30: Rent Guidelines Board
Title 31: Mayor's Office of Homelessness and Single Room Occupancy
Title 34: Department of Transportation
Title 35: Taxi and Limousine Commission
Title 38: Police Department
Title 38-A: Civilian Complaint Review Board
Title 39: Department of Correction
Title 40: Board of Correction
Title 41: Department of Juvenile Justice
Title 42: Department of Probation
Title 43: Mayor
Title 44: Comptroller
Title 45: Borough Presidents
Title 46: Law Department
Title 47: Commission on Human Rights
Title 48: Office of Administrative Trials and Hearings (OATH)
Title 49: Department of Records and Information Services
Title 50: Community Assistance Unit
Title 51: City Clerk
Title 52: Campaign Finance Board*
Title 53: Conflicts of Interest Board
Title 55: Department of Citywide Administrative Services
Title 56: Department of Parks and Recreation
Title 57: Art Commission
Title 58: Department of Cultural Affairs
Title 60: Civil Service Commission
Title 61: Office of Collective Bargaining
Title 62: City Planning
Title 63: Landmarks Preservation Commission
Title 66: Department of Small Business Services
Title 67: Department of Information Technology and Telecommunications
Title 68: Human Resources Administration
Title 69: Department of Aging
Title 70: In Rem Foreclosure Release Board
Title 71: Voter Assistance Commission
Title 72: Office of Emergency Management
Title 73: Civic Engagement Commission
§ 3616-04 National Fire Protection Association ("NFPA") 72 Amendment Relating to the National Fire Alarm and Signaling Code.
Pursuant to § 28-103.19 of the New York City Administrative Code, NFPA 72 (2016 edition) is hereby amended as follows:
18.11 Delete and replace with the following: Standard Emergency Service Interface. Where required by the enforcing authority; governing laws, codes, or standards; or other parts of this Code, annunciators, information display systems, and controls for portions of a system provided for use by emergency service personnel must be designed, arranged, and located in accordance with the requirements of Sections 18.11.1 through 18.11.3.
Add 18.11.1 Fire Service Access Elevators Annunciator Location. The Fire Service Access Elevator (FSAE) annunciator panel must be located at the Fire Command Center (FCC) and installed in such a way that the control switches are protected against tampering by unauthorized individuals. Location of the FCC must be approved by FDNY. Where a building contains more than one FCC, one FSAE annunciator panel must be installed at each FCC.
Add 18.11.2 Listing. All FSAE annunciator panels must be listed to UL Standard 864 (Standard for Control Units and Accessories for Fire Alarm Systems).
Add 18.11.3 Display. FSAE annunciator panels must include a green LED indicating POWER ON, a yellow or amber LED indicating SYSTEM TROUBLE, and a LAMP TEST feature. All LEDs and switches must be arranged to graphically represent the spatial relationship between floors and associated system components. Each individual floor must be labeled with the corresponding floor number. Where marketing floor designations are used, only the marketing floor designation must be displayed on the FSAE annunciator panel. Where approved by FDNY, designs may utilize touchscreen or similar graphic annunciator technologies in lieu of a physical cabinet containing LEDs and switches.
21.5 Delete and replace with the following: Fire Service Access Elevators. Where one or more elevators are specifically designated and marked as FSAE, elevator status, power, and temperature and presence of smoke in elevator lobbies, machine rooms, control rooms, machinery spaces, or control spaces must be continuously monitored and displayed on a building fire alarm system annunciator(s) complying with Section 18.11 and the requirements of Section 21.5.1 through 21.5.5.
21.5.1 Delete and replace with the following: Elevator Status. Status of the elevator(s), including elevator location within the hoistway, direction of travel, position of landing doors, and occupied/unoccupied status of each such elevator car must be indicated on the annunciator panel or represented on a separate panel(s) provided it is also located at the FCC.
21.5.2 Delete and replace with the following: Power. Availability of main and emergency power to operate the elevator(s), elevator controller(s) and machine room ventilation must be displayed on a building fire alarm system annunciator. Individual yellow or amber LEDs for fault condition monitoring must be provided for the following:
   (A)   Elevator Normal Power Fault – upon loss of normal power source supplying the FSAE(s), the associated yellow or amber LED must activate and remain lit until such power source is restored.
   (B)   Elevator Emergency Power Fault – upon loss of the emergency power source that serves supply to the FSAE(s), the associated yellow or amber LED must activate and remain lit until such power source is restored.
   (C)   Elevator Hoistway Ventilation Power Fault – where elevator hoistway ventilation is provided, either through passive or active/mechanical means, loss of power to the associated equipment must activate the yellow or amber LED and the LED must remain lit until such power source is restored.
21.5.3 Delete and replace with the following: Temperature and Smoke. Temperature and presence of smoke in associated lobbies and machine rooms must be monitored and displayed as follows:
   (A)   Temperature Monitoring: Three separate LEDs for each machine room and for each floor/elevator bank utilized for FSAEs must be provided to indicate associated temperatures in the elevator lobby or elevator landing served by the FSAE. These LEDs must be provided under the headings NORMAL <100°F (for green), MONITORING 100°F< > 135°F (for yellow), and UNSAFE >135°F (for red). These temperatures must be monitored utilizing a heat detector or temperature monitoring device listed by a Nationally Recognized Testing Lab (See UL Standard 521 (Heat Detectors for Fire Protective Signaling Systems)).
      (1)   When said device in an elevator machine room, lobby, or landing reaches 100°F, it must send a supervisory signal to the FCC and must light the associated yellow LED.
      (2)   When said device in an elevator machine room, lobby, or landing reaches 135°F, it must send an alarm signal to the FCC and must light the associated red LED. Activation of any red LED must be latching and must only clear upon reset initiated from the fire alarm control panel.
      (3)   The associated green LED must be lit at all other times when no heat condition at or above 100°F has been detected in the corresponding elevator lobby or elevator landing.
   (B)   Smoke Monitoring: Activation of an elevator machine room, elevator lobby or elevator landing smoke detector must send an alarm signal to the FCC and must light a red LED indicating the associated floor/elevator bank and indicating the device type that activated. Activation of any red LED must be latching and must only clear upon reset initiated from the fire alarm control panel.
      (1)   Where hoistway smoke detection is required by the NYC Construction Codes, the status of the hoistway smoke detector must be displayed on this panel.
      (2)   Where cross-zoning of multiple smoke detectors is used, the activation of the second smoke detector in that corresponding area must light the red LED.
      (3)   Where alarm verification for a single smoke detector is used, the activation of the detector in verified alarm mode must light the red LED.
Add 21.5.3.1 Machine Room-less Elevator. Where a machine room-less (MRL) elevator is provided, smoke and temperature monitoring from the elevator hoistway must be displayed on this panel in the same manner as requirements applicable to a traditional elevator machine room.
Add 21.5.4 Hoistway Lighting. Activation of the FSAE hoistway lighting controls to either on or off must generate a supervisory signal reported to the buildings' fire alarm system.
Add 21.5.5 Occupant Evacuation Elevator. Where a building is provided with both FSAE(s), and Occupant Evacuation Elevator(s), a single graphic annunciator may be provided to indicate all required signals.
(Amended City Record 9/8/2015, eff. 10/8/2015; amended City Record 1/20/2023, eff. 2/19/2023)