In any existing building classified in occupancy group J-1, either seventy-five feet or more in height or containing thirty or more sleeping rooms:
(a) Where a corridor or space above a ceiling in a corridor is being used on or after February first, nineteen hundred eighty-four to furnish direct ventilation to a sleeping room or suite, such use shall, unless continued use is permitted by the commissioner, be discontinued by closing all openings between the corridor and sleeping room with construction having a fire-resistance rating equal to the construction in which the opening occurs. When continued use of corridor spaces as a plenum is permitted, smoke detecting devices shall be installed in accordance with the requirements of section 27-981 of article six of subchapter seventeen of this chapter and activation of any two detectors on a floor shall cause closure of all openings to that floor and shut-off of ventilation service to the floor.
(b) All corridors and other public areas not provided with natural ventilation meeting the requirements of section 27-761 of article eight of subchapter twelve of this chapter shall be provided with manual smoke purging by means of existing ventilation systems.
(c) The requirements of this section shall be complied with on or before April first, nineteen hundred eighty-seven.
Article 2: Inspections and Tests for Equipment Use Permits
No required ventilating system, no voluntary air duct system containing smoke detection or fire protection devices that are required by this subchapter, and no refrigeration system shall be placed in operation, until it has been tested and inspected in accordance with the requirements of this subchapter and until an equipment use permit has been issued by the commissioner, except as hereinafter provided.
The following tests and inspection requirements shall be complied with in order to obtain an equipment use permit for a required ventilating system.
(a) Procedure. A required ventilating system shall be subject to the requirements for controlled inspection as provided in article eight of subchapter one of this chapter except that it shall not be required that the architect or engineer be in the employ of the owner. Such requirements shall include (1) a controlled inspection to verify that the installation and operation of the completed system comply with the requirements of this subchapter, comprising tests to ascertain that the amount of air being supplied to and exhausted from each space conforms with the requirements of this code, and tests that all required smoke detection and fire protection devices are functioning properly; and (2) a controlled inspection comprising tests to verify that required fire dampers are installed and functioning properly as provided for in subdivision (d) of section 27-343 of this code. When a required ventilating system handles five thousand cfm or less, it shall be subject to controlled inspection except that the person making the inspection may be an architect, engineer or a person with at least five years of experience installing ventilating systems. However, if such a system exhausts any of the following:
(1) fumes, dusts, vapors or other noxious or injurious substances,
(2) substances that create a fire hazard, then the person making the inspection shall be an architect or engineer. It shall not be required that the architect or engineer be in the employ of the owner. The test reports required under the provisions of article eight of subchapter one of this chapter shall be filed in the form prescribed by the commissioner. The form shall include the quantity of air supplied or exhausted by each outlet.
(b) Fire extinguishing systems. No equipment use permit for a required ventilating system containing a required fire extinguishing system shall be issued until a signed statement has been obtained from a representative of the fire commissioner who has witnessed the test of the extinguishing system and its control devices, certifying the fire commissioner's acceptance of such a system.
(c) Owner's statement. A statement shall be filed with the commissioner by the owner or lessee of the building that the required ventilating system will be kept in continuous operation at all times during the occupancy of the building and, if any smoke or fire detection devices or fire extinguishing systems have been installed, that he or she will have such devices and the fan shut-offs actuated by them tested and inspected by a competent person or agency at one year intervals or less. The owner or lessee shall also state that he or she will promptly make any necessary adjustments and repairs to keep the ventilating system and its safety devices in proper operating condition. A record of each inspection and test shall be maintained on the premises by the owner or lessee, and records for at least the last two years shall be made available for inspection by the commissioner and the fire commissioner.
The following test and inspection requirements shall be complied with in order to obtain an equipment use permit for a voluntary ventilating system or other air duct system when smoke detectors or fire protection devices are required.
(a) Procedure. A voluntary ventilating system or other voluntary air duct system shall be subject to test and inspection to ascertain that all smoke detection and fire protection devices are functioning properly, and that the installation conforms with the requirements of this subchapter.
(b) Fire extinguishing systems. No equipment use permit for a voluntary ventilating system containing a required fire extinguishing system shall be issued until a signed statement has been obtained from a representative of the fire commissioner who has witnessed the test of the extinguishing system and its control devices, certifying the fire commissioner's acceptance of such system.
(c) Owner's statement. A statement shall be filed with the commissioner by the owner or lessee of the building that he or she will have such devices and the fan shut-offs actuated by them tested and inspected by a competent person or agency at one year intervals or less. The owner or lessee shall also state that he or she will promptly make any necessary adjustments and repairs to keep these devices in operation. A record of each inspection and test shall be maintained on the premises by the owner or lessee, and the records for at least the last two years of operation shall be made available for inspection by the commissioner and the fire commissioner.
The following test and inspection requirements shall be complied with in order to obtain an equipment use permit for a refrigerating system, except as hereinafter provided.
(a) Procedure. A refrigeration system shall be designated for test and inspection under the requirements for controlled inspection as provided in article eight of subchapter one of this chapter, except that it shall not be required that the architect or engineer be in the employ of the owner. Test information and all other information required by reference standard RS 13-6 shall be posted, and the inspection shall be made of the completed system to verify that the installation complies with the requirements of this subchapter.
(b) Temporary permits. A temporary equipment use permit shall be required for a nonoperating system in which a charge is maintained. See subchapter one of this chapter for provisions governing temporary permits.
(c) Exception. No equipment use permit or temporary equipment use permit shall be required for any refrigerating system exempted under the provisions of section 27-189 of article eighteen of subchapter one of this chapter; for any system using a group A2, B1 or B2 refrigerant and having a prime mover of one horsepower or less; or for any system using water or air as a refrigerant.
Article 3: Operation and Maintenance
All systems shall be maintained in a clean and orderly condition, free from accumulations of dust, oily waste, or debris. All machinery and all operating devices on piping and ductwork shall be kept readily accessible for inspections and repair. Plenum chambers, air ducts, and cooling and heating coils shall be kept clean. Filters shall be cleaned or renewed at proper intervals to insure safe operation and adequate air flow and shall comply with the applicable requirements of the fire prevention code.