Skip to code content (skip section selection)
Compare to:
New York City Overview
The New York City Charter
The New York City Administrative Code
The Rules of the City of New York
THE RULES OF THE CITY OF NEW YORK
Title 1: Department of Buildings
Title 2: Board of Standards and Appeals
Title 3: Fire Department
Title 6: Department of Consumer and Worker Protection
Title 9: Procurement Policy Board Rules
Title 12: Franchise and Concession Review Committee
Title 15: Department of Environmental Protection
Title 16: Department of Sanitation
Title 17: Business Integrity Commission
Title 19: Department of Finance
Title 20: Tax Appeals Tribunal
Title 21: Tax Commission
Title 22: Banking Commission
Title 24: Department of Health and Mental Hygiene
Title 25: Department of Mental Health and Retardation [Repealed]
Title 28: Housing Preservation and Development
Title 29: Loft Board
Title 30: Rent Guidelines Board
Title 31: Mayor's Office of Homelessness and Single Room Occupancy
Title 34: Department of Transportation
Title 35: Taxi and Limousine Commission
Title 38: Police Department
Title 38-A: Civilian Complaint Review Board
Title 39: Department of Correction
Title 40: Board of Correction
Title 41: Department of Juvenile Justice
Title 42: Department of Probation
Title 43: Mayor
Title 44: Comptroller
Title 45: Borough Presidents
Title 46: Law Department
Title 47: Commission on Human Rights
Title 48: Office of Administrative Trials and Hearings (OATH)
Title 49: Department of Records and Information Services
Title 50: Community Assistance Unit
Title 51: City Clerk
Title 52: Campaign Finance Board*
Title 53: Conflicts of Interest Board
Title 55: Department of Citywide Administrative Services
Title 56: Department of Parks and Recreation
Title 57: Art Commission
Title 58: Department of Cultural Affairs
Title 60: Civil Service Commission
Title 61: Office of Collective Bargaining
Title 62: City Planning
Title 63: Landmarks Preservation Commission
Title 66: Department of Small Business Services
Title 67: Department of Information Technology and Telecommunications
Title 68: Human Resources Administration
Title 69: Department of Aging
Title 70: In Rem Foreclosure Release Board
Title 71: Voter Assistance Commission
Title 72: Office of Emergency Management
Title 73: Civic Engagement Commission
Title 74: Community Hiring
Loading...
1010.1.10.1 Rooms with electrical equipment.
Exit or exit access doors serving transformer vaults, rooms designated for batteries or energy storage systems, or modular data centers shall be equipped with panic hardware or fire exit hardware. Where rooms contain electrical rooms with equipment rated 800 amperes or more that contain overcurrent devices, switching devices or control devices and where the exit or exit access door is less than 25 feet (7629 mm) from the equipment working space, shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.
1010.1.10.2 Refrigeration machinery room.
Swinging doors in refrigeration machinery rooms, where required by Section 1006.2.2.3, shall not be provided with a latch or lock other than panic hardware or fire exit hardware.
1010.1.10.3 Installation.
Where panic or fire exit hardware is installed, it shall comply with the following:
   1.   Panic hardware shall be listed in accordance with UL 305.
   2.   Fire exit hardware shall be listed in accordance with UL 10C and UL 305.
   3.   The actuating portion of the releasing device shall extend not less than one-half of the door leaf width.
   4.   The maximum unlatching force shall not exceed 15 pounds (66.7 N).
1010.1.10.4 Balanced doors.
If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
1010.2 Gates.
Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors.
   Exception: Horizontal sliding or swinging gates exceeding the 4-foot (1220 mm) maximum leaf width limitation are permitted in fences and walls surrounding a stadium.
1010.2.1 Stadiums.
Panic hardware is not required on gates surrounding stadiums where such gates are under constant immediate supervision while the public is present, and where safe dispersal areas based on 3 square feet (0.28 m 2 ) per occupant are located between the fence and enclosed space. Such required safe dispersal areas shall not be located less than 50 feet (15 240 mm) from the enclosed space. See Section 1028.5 for means of egress from safe dispersal areas.
1010.3 Turnstiles.
Turnstiles or similar devices that restrict travel to one direction shall not be placed so as to obstruct any required means of egress. Where portable turnstiles are installed for ticketing purposes, such turnstiles shall be moved from the egress path for proper exiting.
   Exceptions:
      1.   Manually-operated turnstiles. Manually-operated turnstiles that consist of revolving devices that turn freely in the direction of exit travel may be used in any occupancy where revolving doors are permitted. Each manually-operated turnstile or similar device shall be credited with no more than a 50-person capacity where all of the following provisions are met:
         1.1.   Each device shall turn free manually in the direction of egress travel when primary power is lost, and upon the manual release by an employee in the area.
         1.2.   Such devices are not given credit for more than 50 percent of the required egress capacity or width.
         1.3.   Each device is not more than 39 inches (990.6 mm) high.
         1.4.   Each device has not less than 16 1/2 inches (419.1 mm) clear width at and below a height of 39 inches (990.6 mm) and not less than 22 inches (558.8 mm) clear width at heights above 39 inches (990.6 mm).
         1.5.   Where located as part of an accessible route, turnstiles shall have not less than 36 inches (914.4 mm) clear at and below a height of 34 inches (863.4 mm), not less than 32 inches (812.8 mm) clear width between 34 inches (863.4 mm) and 80 inches (2032 mm) and shall consist of a mechanism other than a revolving device.
      2.   Automatic turnstiles. Automatic turnstiles that consist of mechanisms other than revolving devices, and are operated by power, such as turnstiles with a photoelectric-actuated mechanism to open the turnstile upon the approach of a person, may be used in any occupancy where revolving doors are permitted. Automatic turnstiles may serve a means of egress system where all of the following provisions are met:
         2.1.   Each automatic turnstile shall have minimum widths sufficient for the occupant load served and shall provide at least 32 inches (812.8 mm) of clear width at and below a height of 80 inches (2032 mm).
         2.2.   The design shall be such that in the event of power failure, each automatic turnstile is capable of breaking away manually to permit means of egress travel. The force required to break away these turnstiles manually shall not exceed 13 pounds (57.8 N). The turnstile shall be capable of swinging from any position to the full, clear opening width of the turnstile when a force is applied to the turnstile on the side from which egress is made.
         2.3.   Each automatic turnstile shall be operable from the egress side without special knowledge or effort.
         2.4.   Each automatic turnstile shall be connected to the building fire alarm system. Activation of the building fire alarm system shall automatically release each such turnstile to its full, clear opening width, and each such turnstile shall remain in its open position until the fire alarm system has been reset.
         2.5.   Each automatic turnstile shall, upon actuation of a manual release device, automatically open to its full, clear opening width, and shall remain in its open position until the automatic turnstile's access control system is reset. The manual release device shall be clearly identified with ready access that results in direct interruption of power to each turnstile. The manual release device shall be positioned at the fire command center or, if a fire command center is not required, at an approved location near the building entrance where the automatic turnstiles are located.
         2.6.   Each automatic turnstile shall have an integrated emergency power supply.
         2.7.   Each automatic turnstile power supply shall be electrically supervised.
         2.8.   Turnstiles provided for egress purposes in numbers greater than the egress capacity required by this code shall meet the requirements of this section.
         2.9.   Where located as part of an accessible route, such turnstiles shall have at least 36 inches (914.4 mm) clear width at and below a height of 34 inches (863.4 mm), at least 32 inches (812.8 mm) clear width between 34 inches (863.4 mm) and 80 inches (2032 mm).
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)