Except as otherwise provided in this article, or otherwise provided by rule, on and after January 1, 2024 a covered building shall not have annual building emissions higher than the annual building emissions limit for such building as determined in accordance with this section based on the occupancy group of the building.
(L.L. 2019/097, 5/19/2019, eff. 11/15/2019)
For calendar years 2024 through 2029 the annual building emissions limits for covered buildings shall be calculated pursuant to items 1 through 10 of this section. For the purposes of such calculation the department shall provide a method for converting categories of uses under the United States environmental protection agency Portfolio Manager tool to the equivalent uses and occupancy groups set forth in this section. For a covered building with spaces classified in more than one occupancy group, the annual building emissions limit shall be the sum of the calculated values from items 1 through 10 of this paragraph, as applicable for each space.
1. For spaces classified as occupancy group A: multiply the building emissions intensity limit of 0.01074 tCO
2
e/sf by the corresponding gross floor area (sf);
2. For spaces classified as occupancy group B other than as described in item 6: multiply the building emissions intensity limit of 0.00846 tCO
2
e/sf by the corresponding gross floor area (sf);
3. For spaces classified as occupancy groups E and I-4: multiply the building emissions intensity limit of 0.00758 tCO
2
e/sf by the corresponding gross floor area (sf);
4. For spaces classified as occupancy group I-1: multiply the building emissions intensity limit of 0.01138 tCO
2
e/sf by the corresponding gross floor area (sf);
5. For spaces classified as occupancy group F: multiply the building emissions intensity limit of 0.00574 tCO
2
e/sf by the corresponding gross floor area (sf);
6. For spaces classified as occupancy groups B civic administrative facility for emergency response services, B nonproduction laboratory, Group B ambulatory health care facility, H, I-2 and I-3: multiply the building emissions intensity limit of 0.02381 tCO
2
e/sf by the corresponding gross floor area (sf);
7. For spaces classified as occupancy group M: multiply the building emissions intensity limit of 0.01181 tCO
2
e/sf by the corresponding gross floor area (sf);
8. For spaces classified as occupancy group R-1: multiply the building emissions intensity limit of 0.00987 tCO
2
e/sf by the corresponding gross floor area (sf);
9. For spaces classified as occupancy group R-2: multiply the building emissions intensity limit of 0.00675 tCO
2
e/sf by the corresponding gross floor area (sf);
10. For spaces classified as occupancy groups S and U: multiply the building emissions intensity limit of 0.00426 tCO
2
e/sf by the corresponding gross floor area (sf).
(L.L. 2019/097, 5/19/2019, eff. 11/15/2019; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
The annual building emissions of a covered building in accordance with this section, greenhouse gas emissions shall be calculated as follows for calendar years 2024 through 2029:
1. Utility electricity consumed on the premises of a covered building that is delivered to the building via the electric grid shall be calculated as generating 0.000288962 tCO
2
e per kilowatt hour or, at the owner's option, shall be calculated based on time of use in accordance with referenced emissions factors promulgated by rules of the department. The department, in consultation with the office of long-term planning and sustainability, shall promulgate rules governing the calculation of greenhouse gas emissions for campus-style electric systems that share on-site generation but make use of the utility distribution system and for buildings that are not connected to the utility distribution system.
2. Natural gas combusted on the premises of a covered building shall be calculated as generating 0.00005311 tCO
2
e per kbtu.
3. #2 fuel oil combusted on the premises of a covered building shall be calculated as generating 0.00007421 tCO
2
e per kbtu.
4. #4 fuel oil combusted on the premises of a covered building shall be calculated as generating 0.00007529 tCO
2
e per kbtu.
5. District steam consumed on the premises of a covered building shall be calculated as generating 0.00004493 tCO
2
e per kbtu.
6. The amount of greenhouse gas emissions attributable to natural gas powered fuel cells shall be credited compared to the electricity grid marginal emissions factor that will be determined by the commissioner and promulgated into rules of the department.
Exception: Natural gas powered fuel cells that commence operation prior to the later of January 1, 2023 or the promulgation of such rules, shall be credited compared to the electricity grid marginal emissions factor published in the most recent New York state energy research and development authority renewable energy standard program impact evaluation and clean energy standard triennial review, or a successor to such report issued by the New York state energy research and development authority.
7. The amount of greenhouse gas emissions attributable to other energy sources, including but not limited to distributed energy resources, shall be determined by the commissioner and promulgated into rules of the department.
(L.L. 2019/097, 5/19/2019, eff. 11/15/2019; Am. L.L. 2019/147, 7/27/2019, eff. 11/15/2019; Am. L.L. 2020/095, 9/27/2020, eff. 9/27/2020; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
For calendar years 2030 through 2034, the annual building emissions limits for covered buildings shall be calculated pursuant to items 1 through 10 of this section. For the purposes of such calculation the department shall provide a method for converting categories of uses under the United States environmental protection agency Portfolio Manager tool to the equivalent uses and occupancy groups set forth in this section. For a covered building with spaces classified in more than one occupancy group, the annual building emissions limit shall be the sum of the calculated values from items 1 through 10 of this paragraph, as applicable for each space. The department may establish different limits, including a different metric or method of calculation, set forth in the rules of the department, where the department determines that different limits are feasible and in the public interest. Where such limits are set by rule, the average emission limits for all covered buildings shall not be less restrictive than the average emissions impact of the building emissions limits outlined in items 1 through 10 of this section. The advisory board and the office of long-term planning and sustainability shall provide advice and recommendation regarding such limits.
1. For spaces classified as occupancy group A: multiply the building emissions intensity limit of 0.00420 tCO
2
e/sf by the corresponding gross floor area (sf);
2. For spaces classified as occupancy group B other than as described in item 6: multiply the building emissions intensity limit of 0.00453 tCO
2
e/sf by the corresponding gross floor area (sf);
3. For spaces classified as occupancy groups E and I-4: multiply the building emissions intensity limit of 0.00344 tCO
2
e/sf by the corresponding gross floor area (sf);
4. For spaces classified as occupancy group I-1: multiply the building emissions intensity limit of 0.00598 tCO
2
e/sf by the corresponding gross floor area (sf);
5. For spaces classified as occupancy group F: multiply the building emissions intensity limit of 0.00167 tCO
2
e/sf by the corresponding gross floor area (sf);
6. For spaces classified as occupancy groups B civic administrative facility for emergency response services, B nonproduction laboratory, Group B ambulatory health care facility, H, I-2 or I-3: multiply the building emissions intensity limit of 0.01330 tCO
2
e/sf by the corresponding gross floor area (sf);
7. For spaces classified as occupancy group M: multiply the building emissions intensity limit of 0.00403 tCO
2
e/sf by the corresponding gross floor area (sf);
8. For spaces classified as occupancy group R-1: multiply the building emissions intensity limit of 0.00526 tCO
2
e/sf by the corresponding gross floor area (sf);
9. For spaces classified as occupancy groups R-2: multiply the building emissions intensity limit of 0.00407 tCO
2
e/sf by the corresponding gross floor area (sf);
10. For spaces classified as occupancy groups S and U: multiply the building emissions intensity limit of 0.00110 tCO
2
e/sf by the corresponding gross floor area (sf).
(L.L. 2019/097, 5/19/2019, eff. 11/15/2019; Am. L.L. 2019/147, 7/27/2019, eff. 11/15/2019; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.