6704.2.3 Distance to exposures from Class 1 and Class 2 material outdoor storage areas.
Outdoor storage of Class 1 and Class 2 water-reactive solids and liquids shall not be within 20 feet (6096 mm) of buildings, lot lines, public streets, private roads or means of egress. A 2-hour fire barrier wall without openings or penetrations, and extending not less than 30 inches (762 mm) above and to the sides of the storage area, is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
6704.2.4 Storage conditions.
Class 3 water-reactive solids and liquids shall be limited to piles not greater than 500 cubic feet (14 m3).
6704.2.4.1 Class 1 and Class 2 piles.
Class 1 and Class 2 water-reactive solids and liquids shall be limited to piles not greater than 1,000 cubic feet (28 m3).
6704.2.4.2 Aisle widths.
Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
6704.2.5 Containment.
Secondary containment shall be provided in accordance with FC 5004.2.2.
6705.1 General.
Water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.