5706.4.10.8.1 Color coding.
Fire protection systems shall be color-coded as follows:
1. Standpipe and/or yard hydrant systems:
1.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting white bands.
1.2. Fire department connections: Red.
2. Sprinkler systems (wet or dry):
2.1. Piping and valve bodies and handles: Red with contrasting bright green bands.
2.2. Fire department connections: Red with green caps.
3. Nonautomatic sprinkler systems (including fog spray systems):
3.1. Piping and valve bodies and handles: Red with contrasting aluminum bands.
3.2. Fire department connections: Aluminum.
4. Carbon dioxide extinguishing systems – piping, valve bodies and handles: Red with contrasting brown bands.
5. Steam extinguishing systems – piping, valve bodies and handles: Red with contrasting black bands.
6. Foam extinguishing systems:
6.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting bright orange bands.
6.2. Department water connections: Red. A durable sign that reads "WATER FOR FOAM SYSTEM", shall be conspicuously posted immediately adjacent to such connections.
6.3. Department foam connection: Red with contrasting bright orange band or caps. A durable sign that reads "CHEMICAL FOAM DIRECT TO TANKS" or "...% MECHANICAL FOAM SOLUTION DIRECT TO TANKS", shall be conspicuously posted immediately adjacent to such connections.