5706.4.10 Fire protection.
Fire protection shall be in accordance with FC Chapter 9 and FC 5706.4.10.1 through 5706.4.10.8.
5706.4.10.1 Portable fire extinguishers.
Portable fire extinguishers with a rating of not less than 20-B and complying with the requirements of FC 906 shall be located within 75 feet (22 860 mm) of hose connections, pumps and separator tanks.
5706.4.10.2 Fire hoses.
Fire hose connected to a water supply in a size appropriate for the water supply shall be provided in accordance with FC 905 and the construction codes, including the Building Code, so that manifolds where connections are made and broken can be reached by at least one hose stream.
5706.4.10.3 Obstruction of equipment.
Material shall not be placed on wharves in such a manner that would obstruct access to firefighting apparatus or equipment or important pipeline or other delivery control valves.
5706.4.10.4 Fire apparatus access.
An unobstructed fire apparatus access road to the shore end of the wharf shall be maintained in accordance with FC Chapter 5.