3208.2.2.1 Fire protection.
Fire protection for racks with solid shelving shall be in accordance with NFPA 13, as modified by FC Appendix B.
Rack Configuration | Sprinkler Protection | Sprinkler at the Ceiling with or Without Minimumin-Rack Sprinklers | In-Rack Sprinklers at Every Tier | Non- sprinklered | |||
25 feet | > 25 feet | Any height | Any height | ||||
Storage Height | Option 1 | Option 2 |
Rack Configuration | Sprinkler Protection | Sprinkler at the Ceiling with or Without Minimumin-Rack Sprinklers | In-Rack Sprinklers at Every Tier | Non- sprinklered | |||
25 feet | > 25 feet | Any height | Any height | ||||
Storage Height | Option 1 | Option 2 | |||||
Single-row rack | Transverse flue space | Size b | 3 inches | Not Applicable | 3 inches | Not Required | Not Required |
Vertically aligned | Not Required | Not Applicable | Yes | Not Applicable | Not Required | ||
Longitudinal flue space | Not Required | Not Applicable | Not Required | Not Required | Not Required | ||
Double-row rack | Transverse flue space | Size b | 6 inches a | 3 inches | 3 inches | Not Required | Not Required |
Vertically aligned | Not Required | Not Required | Yes | Not Applicable | Not Required | ||
Longitudinal flue space | Not Required | 6 inches | 6 inches | Not Required | Not Required | ||
Multi-row rack | Transverse flue space | Size b | 6 inches | Not Applicable | 6 inches | Not Required | Not Required |
Vertically aligned | Not Required | Not Applicable | Yes | Not Applicable | Not Required | ||
Longitudinal flue space | Not Required | Not Applicable | Not Required | Not Required | Not Required | ||
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Three-inch transverse flue spaces shall be provided at least every 10 feet where ESFR sprinkler protection is provided.
b. Random variations are allowed, provided that the configuration does not obstruct water penetration.
3208.3 Flue spaces.
Flue spaces shall be provided in accordance with FC Table 3208.3. Required flue spaces shall be maintained. When the flue spaces are not being maintained, the department may require the installation of approved devices to protect the flue spaces by preventing the placement or storage of obstructing materials in such spaces. Such protective devices shall not be removed or modified without department approval.
3208.4 Column protection.
Steel building columns shall be protected in accordance with NFPA 13, as modified by FC Appendix B.
3208.5 Extra-high-rack storage systems.
Approval of the commissioner shall be obtained prior to installing extra-high-rack combustible storage.
3208.5.1 Fire protection.
Buildings with extra-high-rack combustible storage shall be protected with a specially engineered sprinkler system. Extra-high-rack combustible storage shall be provided with additional special fire protection, such as separation from other buildings and additional built-in fire protection features and fire department access, when required by the commissioner.