2603.2 Sources of ignition.
Open flames and similar sources of ignition shall be removed from the space in which fumigation or insecticidal fogging operations are being conducted. Heating, where needed, shall be of an approved type.
2603.2.1 Electricity.
Electricity in any part of the building or structure where operation of switches or electrical devices, equipment and systems could serve as a source of ignition during and for a reasonable time after any fumigation or insecticidal fogging operation shall be shut off.
Exception: Circulating fans that have been specifically designed for utilization in hazardous atmospheres and installed in accordance with the Electrical Code.
2603.2.2 Electronic devices.
Electronic devices, including portable equipment and cellular phones, shall be shut off. Telephone lines shall be disconnected from telephones.