(A) Receptacles shall be located a minimum of every six feet measured horizontally along the wall. Any 2-foot interruption in wall space shall be included in the six feet. This shall also apply to kitchens; except, as outlet every four feet, with no more than two outlets per circuit, shall be provided for usable counter space.
(B) Each two outlets shall be fused for 20-amp capacity. No overhead fixtures shall be allowed on any outlet circuit. No more than eight outlets shall be allowed on any circuit.
(Ord. 7-1992, passed 12-21-1992)