1. The following design standards apply to the construction of new underground storage tanks storing more than 110 gallons of hazardous materials, excluding heating oil tanks of 3,000 gallons or less used by homes or businesses:
A. The design and construction of underground storage facilities shall be in accordance with applicable Federal and State requirements, including the Pennsylvania Underground Storage Act, Pennsylvania Storage Tank and Spill Prevention Act, and the rules and regulations of PA DEP.
B. The tank shall be constructed of fiberglass-reinforced plastic, coated and cathodically protected steel, or fiberglass-reinforced plastic composite.
C. The tank and associated tank piping shall provide for secondary containment for release detection purposes which may include double-walled tanks and piping, a concrete vault in which the tank and piping is placed, or an impermeable liner in the excavation zone in which the tank and piping is placed.
D. The tank shall be equipped with spill and overfill prevention equipment and an approved leak detection system.
E. The tank must be installed by a PA DEP certified installer.
F. The Operating Requirements described in § 26-242 shall be applicable for the operation of new underground storage tanks.
(Ord. 2004-14, 6/28/2004, § 2)