15.12.180 Amendment - Section 503.2.1 Dimensions.
   Section 503.2.1 is amended in its entirety to read as follows:
   "503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 28 feet (85,344mm) exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 15 feet (4,572mm).
   Exception: Vertical clearance may be reduced, provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance approved by the fire code official."
(Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)