Tables B105.1(1), B105.1(2) and B105.2 of Appendix B are deleted in their entirety and replaced with the following:
"TABLE B105.1
MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGS*
Use | Required Flow (gallons per minute) | Duration |
One- and Two-Family Dwelling | 1500 gpm | 2 hours |
Multi-Family Dwelling | 2500 gpm | 2 hours |
Commercial | 3000 gpm | 3 hours |
Industrial | 3500 gpm | 4 hours |
*Or as otherwise required by the Fire code official"
(Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)