15.12.380 Amendment - Tables B105.1(l), B105.1(2) and B105.2 of Appendix B -Minimum required fire flow and flow duration for buildings.
   Tables B105.1(1), B105.1(2) and B105.2 of Appendix B are deleted in their entirety and replaced with the following:
   "TABLE B105.1
   MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGS*
 
Use
Required Flow (gallons per minute)
Duration
One- and Two-Family Dwelling
1500 gpm
2 hours
Multi-Family Dwelling
2500 gpm
2 hours
Commercial
3000 gpm
3 hours
Industrial
3500 gpm
4 hours
*Or as otherwise required by the Fire code official"