Section 507.5.1 is hereby amended in its entirety to read as follows:
"507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is located a greater distance from a hydrant on a fire apparatus access road than allowed in Appendix C - "Fire Hydrant Locations and Distribution", as measured by an approved route around the exterior of the facility or building, on-site hydrants and mains shall be provided where required by the fire code official."
Exceptions:
1. Group R-3 and U occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with CFC 903.3.1.1 or CFC 903.3.1.2 or CFC 903.3.1.3, provided the distance requirements shall not be more than 300 feet (91.5 m), unless otherwise approved by the fire code official."
(Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)