(a) When standpipes are required by this Fire Prevention Code, buildings seventy-five (75) feet or less in height above grade level shall have standpipes not less than four (4) inches in diameter.
(b) Buildings exceeding seventy-five (75) feet in height above grade level shall have standpipes not less than six (6) inches in diameter.
(c) Standpipes intended only for first-aid streams and provided in addition to and supplementary to required four (4) inch or six (6) inch standpipes shall be not less than the following:
(1) Two (2) inch for buildings up to and not exceeding four (4) stories or fifty (50) feet in height;
(2) Two and one-half (2-1/2) inch for buildings in excess of four (4) stories in height.
(d) Standpipes in theaters and assembly halls regulated by the Ohio Building Code shall be not less than the size specified in that Code.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)