(a) Standpipe locations in theaters and assembly halls regulated by the Ohio Building Code shall be as specified in that Code.
(b) Other required standpipes shall be in such number and so located that all parts of all floor areas are within thirty (30) feet of a nozzle attached to one hundred (100) feet of Fire Division hose connected to a standpipe outlet provided for use of the Division and can be reached by a stream from such nozzle.
(c) Where first-aid hose is required by this Fire Prevention Code, it shall be provided and so located that all parts of every floor area are within twenty (20) feet of a nozzle attached to seventy-five (75) feet of hose connected to the valve at a first-aid hose station and can be reached by a stream from such nozzle.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)