18-28-1102.1 General.
   The system classification, allowable refrigerants, the maximum quantity, enclosure requirements, location limitations, and field pressure test requirements shall be determine as follows:
   1.   The refrigeration system's classification shall be determined in accordance with Section 18-28-1103.3.
   2.   The refrigerant classification shall be determined by Table 18-28-1103.1, Refrigerant and Amounts.
   3.   The system enclosure requirements shall be determined by Section, 18-28-1104, Systems Application Requirements, based on type of refrigerant, system classification, and occupancy.
   4.   The system enclosure shall be determined in accordance with Section 18-28-1104, Systems Application Requirements.
   5.   Refrigeration equipment and appliance location and installation shall be subject to the limitations of Article 3, General Regulations.
   6.   Non-factory-tested, field-erected equipment and appliances shall be pressure tested in accordance with Section 18-28-1108, Field Test.