18-28-918.6 Prohibited sources.
   Outside or return air for a forced-air heating system shall not be taken from the following locations:
   1.   Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet (914 mm) above the outside air inlet.
   2.   Where there is the presence of objectionable odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway.
   3.   A hazardous or insanitary location or a refrigeration machinery room as defined in the building code.
   4.   A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Sections 18-28-918.2 and 18-28-918.3, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces.
   Exception: The minimum volume requirement shall not apply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space.
   5.   A closet, bathroom, toilet room, kitchen, garage, mechanical room, boiler room or furnace room.
   6.   A room or space containing a fuel-burning appliance where such room or space serves as the sole source of return air.
   Exceptions:
      1.   This shall not apply where the fuel-burning appliance is a direct-vent appliance.
      2.   This shall not apply where the room or space complies with the following requirements:
         2. 1   The return air shall be taken from a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9.6 L/W) of combined input rating of all fuel-burning appliances therein.
         2.2   The volume of supply air discharged back into the same space shall be approximately equal to the volume of return air taken from the space.
         2.3   Return-air inlets shall not be located within 10 feet (3048 mm) of any appliance firebox or draft hood in the same room or space.
      3.   This shall apply to rooms or spaces containing solid fuel-burning appliances, provided that return-air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances.