18-28-908.3 Location.
   Cooling towers, evaporative condensers and fluid coolers shall be located to prevent the discharge vapor plumes from entering occupied spaces. Plume discharges shall be not less than 5 feet (1524 mm) above or 20 feet (6096 mm) away from any ventilation inlet to a building. Location on the property shall be as required for buildings in accordance with the Chicago Building Code.
(Amend Coun. J. 9-14-21, p. 35949, Art. IX, § 5)