18-28-706.2 Mechanical combustion air supply for gas-fired appliances.
   Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft 3 /min per 1,000 Btu/hr (0.034 mm 3 /kW) for all appliances located within the space.