Materials exposed within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84 or UL 723. No floor drains or sanitary waste and vent piping, storm drain piping or condensate drain piping may be exposed within a supply plenum. No material which has the potential of contaminating the air stream may be located in a supply plenum.
Exceptions:
1. Rigid and flexible ducts and connectors shall conform to Section 18-28-603.
3. This section shall not apply to materials exposed within plenums in Group R-5 occupancies.
4. This section shall not apply to smoke detectors.