Air intake and exhaust that terminate outdoors shall be suitably protected against Chicago weather conditions, with corrosion resistant screens, louvers and grilles. Area of the outside air intake shall be sized so that at least 100 percent of the code-required outside air as required in Section 18-28-403.1 can be taken from outside at velocities not in excess of 1,000 feet per minute (304.8 mpm) through free area except for systems defined in paragraph 18-28-403.1.3.
Outdoor Opening Type | Minimum and Maximum Opening Sizes in Louvers, Grilles and Screens Measured in Any Direction |
Exhaust openings | Not less than 1/4 inch and not greater than 1/2 inch |
Intake openings in residential occupancies | Not less than 1/4 inch and not greater than 1/2 inch |
Intake openings in other than residential occupancies | Not less than 1/4 inch and not greater than 1 inch |
For SI: 1 inch = 25.4 mm.