Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
TITLE 15 FIRE PREVENTION
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
15-24-221 Aboveground tanks.
   The use of aboveground storage tanks, tank cars, tank trucks, or portable tanks in connection with vending, gauging, or dispensing of flammable liquids, other than for equipment installed on tank vehicles complying with Section 15-24-1080, shall be permitted only under the following limited circumstances:
   (A)   The construction and installation of the tanks must satisfy each of the following conditions and restrictions:
      (1)   Tanks shall be enclosed within a two- hour fire-rated assembly.
      (2)   The tank assembly shall provide 100 percent secondary containment of the flammable liquid. Dikes as required in Section 15-24-170 need not be provided.
      (3)   Tanks shall be limited to a capacity of 1,000 gallons.
      (4)   No more than two such aboveground tanks shall be installed or located at any one site.
      (5)   The tank shall be completely surrounded by a protective guardrail which is located a minimum of two feet away from the tank.
      (6)   Dispensing of the flammable liquid shall be by means of a pump which is permanently attached to the top of the enclosing assembly described in subsection (A)(1) above and which is equipped with an anti-syphon valve.
      (7)   Such tanks shall be located a minimum of ten feet away from any building or property line, except that tanks containing Class II or Class III liquids, as defined in Section 15-24-020, may be located within three feet of a fire-resistive wall without openings.
      (8)   Each tank shall bear the words, "Flammable โ€“ Keep Fire Away", conspicuously on each side of the tank. The coloring of the letters shall be a color which contrasts with the color of the tank and the letters each must be a minimum of four inches high.
      (9)   A lockable fill cap shall be provided.
      (10)   Tanks shall be electrically grounded.
      (11)   Emergency vents conforming with Section 15-24-190 B shall be provided for both the primary tank and the secondary containment space.
   (B)   Aboveground tanks used pursuant to this section shall not be used for any retail sales.
(Added Coun. J. 5-2-95, p. 73)
15-24-230 Gasoline pumping prohibited.
   Pumping of gasoline from a tank truck into an underground tank shall be prohibited.
(Prior code ยง  129.1-18.2; Amend Coun. J. 2-16-89, p. 24942)
15-24-240 Warning signs.
   Warning signs prohibiting smoking and instructing customers to turn off ignition systems during filling operations shall be posted in a conspicuous location at each island. Such signs shall be metal or other material designed to withstand weather. Such signs shall have a white background with the words "No Smoking" and "Turn Off Engine" in red letters, a minimum of four inches high with a minimum of a one-half-inch stroke. Signs with directions for operation of the dispensing devices shall also be provided.
(Prior code ยง  129.1-18.3; Added Coun. J. 2-16-89, p. 24942)
15-24-250 Definition of safety clearance.
   Whenever in the following sections the words "safety clearance" are used, said words shall be construed to require a space open its entire area to the sky, and which shall be continuous on all sides of the building or structure; between such building and any other building, or property dividing lot line, or the lot line adjoining or adjacent to a public park, or any main line of street, electric, elevated railway or any other railway right-of-way.
(Prior code ยง  129.1-19)
15-24-260 Safety clearances.
   The minimum required safety clearance for aboveground flammable liquid storage tanks in reference to any building or lot line shall be regulated as follows:
   Wherever unstable liquid is used in this section it shall mean a liquid which in pure state or as commercially produced or transported will vigorously polymerize, decompose, condense or will become self- reactive under conditions of shock, pressure or temperature.
      (a)   Every aboveground tank for the storage of flammable or combustible liquids, except unstable liquids, operating at pressures not in excess of 2.5 p.s.i.g. shall be located in accordance with Table 15-24-260(a).(See Table 15-24-260(a).)
      (b)   Every aboveground tank for the storage of flammable liquids, except unstable flammable liquids, operating at pressures exceeding 2.5 p.s.i.g. shall be located in accordance with Table 15-24-260(b). (See Table 15-24-260(b).)
      (c)   Every aboveground tank for the storage of unstable liquids shall be located in accordance with Table 15-24-260(c). (See Table 15-24-260(c).)
      (d)   Reference Table 15-24-260(A) for Tables 15-24-260(a), 15-24-260(b) and 15-24-260(c).
Table 15-24-260(A)
Capacity Tank Gallons
Minimum Distance in Feet From Lot Line
Capacity Tank Gallons
Minimum Distance in Feet From Lot Line
275 or less
5
276 to 750
10
751 to 12,000
15
12,001 to 30,000
20
30,001 to 50,000
30
50,001 to 60,000
50
Over 60,000 gallons
โ€“
 
   The minimum distance for safety clearance shall be increased one foot for each additional 3,000 gallons increase in the capacity of tanks; provided, however, that the safety clearance need not exceed 250 feet. The aforesaid maximum safety clearance of 250 feet may be reduced to 175 feet where every tank is equipped with an approved floating raft or an approved permanently attached extinguishing system. No underground tank or dike shall be located nearer than 50 feet to the river, lake or other waterway. Truck loading docks and platforms shall be located not less than 25 feet from the storage tanks, plant buildings and property lines.
   The safety clearance between tanks shall be regulated according to capacity as follows:
Capacity of the Larger of the Two Tanks (Gallons)
Minimum Clearance Between Tanks (Feet)
Capacity of the Larger of the Two Tanks (Gallons)
Minimum Clearance Between Tanks (Feet)
300 or less
3
500
3
1,000
3
8,000
3
12,000
3
18,000
3
24,000
3
30,000
3
48,000
10
75,000
10
100,000
13
150,000
15
200,000
15
Over 200,000
Distance equal to the diameter or the greatest horizontal dimension of the larger tank.
 
   A tolerance of ten percent in capacity shall be allowed in all tanks. The minimum required safety clearance for flammable liquid storage tanks aboveground, required by this section may be reduced to the minimum safety clearance between tanks, as provided above, whenever such tank is individually diked and protected by fire walls of four-hour fire-resistive construction, extending not less than three feet above and beyond each tank, and provided with a fender or return wall for each such fire wall of the same height and thickness at each end and extending not less than three feet on each side of such fire wall.
   Nothing in this section shall be interpreted or construed to apply to any group of oil storage tanks, every part of which group has an open space of not less than 1,000 feet, continuous on all sides of the group of tanks or between such group of tanks and any building or property dividing line, or the opposite side of each adjoining and adjacent public way or public park or any main line of a steam, electric, elevated railway or any other railway right-of-way; provided, that the provisions of this paragraph shall apply only to oil storage tanks storing liquids above the ground, and which liquids have a flashpoint above 150 degrees Fahrenheit. This paragraph shall not apply to any liquids stored under the ground.
Table 15-24-260(a)
 
Type of Tank
Protection
Minimum Distance in Feet from Lot Line
Floating Roof
None
Diameter of tank but need not exceed 175 ft.
Vertical with weak roof to shell seam.
Approved foam or inerting system on the tank.
1/2 times diameter of tank and shall not be less than 5 ft.
None
2 times diameter of tank but need not exceed 350 feet.
Horizontal and vertical, with emergency relief venting to limit pressures to 2.5 p.s.i.g.
Approved inerting system on the tank or approved system on vertical tanks.
1/2 times Table 15-24-260(A) but shall not be less than 5 ft.
None
2 times Table 15-24-260(A)
 
Table 15-24-260(b)
 
Type of Tank
Minimum Distance in Feet from Lot Line
Any type
3 times Table 15-24-260(A) but shall not be less than 50 ft.
 
Table 15-24-260(c)
 
Type of Tank
Protection
Minimum Distance in Feet from Lot Line
Horizontal and vertical tanks with emergency relief venting to permit pressure not in excess of 2.5 p.s.i.g.
Tank protected with any one of the following: Approved water spray, approved inerting, approved insulation and refrigeration, approved barricade.
See Table 15-24-260(A), but the distance may not be less than 25 ft.
None
5 times Table 15-24-260(A), but not less than 100 ft.
 
(Prior code ยง 129.1-20)