Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
TITLE 15 FIRE PREVENTION
CHAPTER 15-4 BUREAU OF FIRE PREVENTION
CHAPTER 15-8 RESERVED*
CHAPTER 15-12 RESERVED*
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
CHAPTER 15-20 EXPLOSIVES AND FIREWORKS
CHAPTER 15-24 FLAMMABLE LIQUIDS
CHAPTER 15-26 FUME AND FLAMMABLE COMPRESSED GASES
CHAPTER 15-28 HAZARDOUS MATERIALS AND COMBUSTIBLE SOLIDS
CHAPTER 15-30 RESERVED*
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
15-16-260 System tests.
   Upon completion of the installation of an automatic sprinkler system, an acceptance test shall be performed by the installing contractor.
   All portions of each system shall be tested for two hours at a cold water pressure of not less than 200 pounds per square inch if the normal pressure in the system does not exceed 150 pounds per square inch or at a pressure of not less than 50 pounds per square inch above the normal pressure, if such normal pressure is more than 150 pounds per square inch. Interior piping shall show no leaks. Underground piping shall show a leakage rate not greater than two quarts per hour per 100 gaskets or joints irrespective of pipe diameter.
   Dry pipe systems, if tested during seasons of the year which will not permit the use of water, may be tested with air under a pressure of not less than 50 pounds per square inch.
   Brine or other corrosive or toxic chemicals shall not be used for testing.
   If the dry pipe valves are of the differential type, they shall be pumped up and allowed to stand 24 hours and shall show not more than one and one-half pounds per square inch loss of pressure during that period of time. A working test of each dry pipe valve shall be made before acceptance. When dry pipe valves are subjected to hydrostatic test pressures, the clapper of a differential type valve shall be held off its seat to prevent damaging the valve.
   Fire pumps, air compressors, filling pumps and other equipment shall be tested for a period of two hours or such portion of this time as is necessary to show they are of the required capacities. Initial tests of fire pumps shall be made in the presence of a representative of the Fire Commissioner and the installing contractor.
   Every fire pump shall provide its rated capacity at its rated pressure. Fire pumps rated at less than 1,500 GPM shall furnish at least 150 percent of the rated capacity at 65 percent of its rated pressure. The pressure at the intake side of the pump shall not be less than five pounds per square inch under any flow rate.
   Fire pumps shall be tested annually by an independent contractor licensed under the Illinois Fire Sprinkler Contractor Licensing Act. Such inspections shall be scheduled with, and may be overseen by or in the presence of, the Fire Commissioner.
(Prior code § 91-10; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 121; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 12)
15-16-270 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-270, which pertained to water supply requirements.
15-16-280 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-280, which pertained to use of pressure tank for other services.
15-16-290 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-290, which pertained to gravity tanks.
15-16-300 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-300, which pertained to pressure tanks.
15-16-310 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-310, which pertained to fire pumps.
15-16-311 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-311, which pertained to test manifold.
15-16-320 Reserved.
Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-320, which pertained to supply to tanks.
Loading...