15-16-150  Substitution of sprinklers for heat detectors.
   No automatic heat detector shall be required in any room or portion of a building which is equipped with an approved installation of automatic sprinklers and provided with a waterflow alarm which is connected to the fire alarm system. Provided, however, that the foregoing exception shall not apply to any intermediate care facility for the developmentally disabled – 15 or fewer persons.
(Prior code §  64-14; Amend Coun. J. 12-21-84, p. 12140; Amend Coun. J. 9-8-86, p. 33588)