Pursuant to published notice and public hearing, as required by law, the International Fire Code, 2018 Edition, including Appendix Chapters B, C, D, I, K, and N, (see International Fire Code Section 101.2.1, 2018 Edition), as published by the International Code Council, is hereby adopted in full as the Fire Code of the City of Waukee, for regulating and governing the safeguarding of life and property from fire and explosion hazards arising from the storage, handling, and use of hazardous substances, materials and devices, and from conditions hazardous to life or property in the occupancy of buildings and premises as herein provided; and each and all of the regulations, provisions, penalties, conditions, and terms of said Fire Code are hereby referred to, adopted, and made a part hereof, as if fully set out in this legislation, with the following additions, insertions, deletions, and changes. The following amendments, modifications, additions, and deletions to the International Fire Code, 2018 Edition, are hereby made:
1. Section 101.1 insert: City of Waukee.
2. Insert new code Section 105.3.9 with the following language:
3. 105.3.9 Revocation of Permit. It is the permit holder’s responsibility to schedule the required inspections and obtain final approvals. Failure to schedule the required inspections and receive approval of work authorized by the permit before covering said work or at completion shall result in revocation of the permit and void any associated approvals granted by the City. This failure shall also equate to working without a permit in violation of City ordinance and no future permits shall be issued to any person or company who has outstanding violations of this code or any other laws or ordinances of the City. Failure to contact the City for any inspection or follow-up prior to expiration of a permit shall be deemed a violation of this code section. Failure to contact the City for any inspection or follow-up prior to expiration of a Temporary Certificate of Occupancy shall also be deemed a violation of this code section. Allowing occupancy of a structure, for which a person or company holds a building permit, prior to or without a valid Certificate of Occupancy (temporary or final) shall be deemed a violation of this code section and no future permits shall be issued to any person or company who has outstanding violations of this code or any other laws or ordinances of the City.
4. Insert New Code Section IFC 105.4.1.2:
105.4.1.2 Fire Protection System Submittals. All life safety plans submitted for review to include, but not limited to, fire sprinkler system plans, fire alarm system plans, and clean agent system plans shall be designed and stamped by a person with a minimum of a NICET III certification, fire protection engineer, qualified engineer with two years demonstrated experience in life safety system design, or equivalency as determined by the code official. Plan approval will be based upon the plans submitted by the equipment supplier utilizing the above requirements.
5. Insert New Code Section IFC 105.4.1.3:
105.4.1.3 Life Safety Plan Review Technical Assistance. Fire sprinkler systems, fire alarm system, fire pumps, clean agent systems, kitchen hood suppression systems shall be submitted to the Waukee contracted third party engineer for review at the discretion of the fire code official. The code official has the authority to require additions/modifications to the existing fire sprinkler systems and fire alarm systems to be sent to the Waukee contracted third party for review.
6. Insert New Code Section 106.2:
7. 106.2 Construction Permit/Plan Review Fee. Refer to City of Waukee current fee schedule.
8. Insert New Code Section 106.2.1
9. 106.2.1 Work Commencing Before Permit Issuance Fee. If required lift safety plans are not received at the Waukee Fire Department prior to seven days before the final certificate of occupancy inspection is scheduled, a fee of $200.00 shall be paid by the submitting company prior to the inspections taking place and the inspection will be re-scheduled for a date as determined by the code official.
10. Insert New Code Section 106.4.1:
11. 106.4.1 Re-Inspection Fees. A fee for re-inspections for the construction, alteration, operation and/or fire life safety inspections shall be paid as required, in accordance with the schedule as established by the applicable governing authority. Refer to current City of Waukee fee schedule.
12. Insert New Code Section 106.4.2:
13. 106.4.2 Mitigation Reimbursement Fees. Reimbursement fees that are actual and necessary expenses incurred in carrying out the mitigation of specialized emergencies including, but not limited to, hazardous materials, specialized rescue, and crime scenes (including arson) shall be invoiced to the responsible person, firm, or corporation. An available fee schedule shall be reviewed and posted annually by the Fire Chief’s Office. Fees may include, but not limited to, personnel compensation, apparatus use, equipment use, and specialized contract labor associated with the mitigation of the specialized emergency.
14. Insert New Code Section 107.1.1:
15. 107.1.1 Inspection Tags. Tags for inspection of fire suppression systems, fire extinguishers, and fire alarm systems are required to be White West Metro Fire Prevention Bureau. These tags can be purchased from the West Des Moines Fire Prevention Bureau for use in the City of Waukee.
16. Delete Code Section IFC 108.3 and replace with the following language:
17. 108.3 Recordkeeping. A record of periodic inspections, tests, servicing, and other operations and maintenance shall be maintained on the premises or other approved location for not less than three years, or a different period of time where specified in this code or referenced standards. Records shall be made available for inspection by the fire code official, and a copy of the records shall be provided to the fire code official upon request.
18. The fire code official has prescribed the form and format of such record keeping to be electronically submitted through a web based system, the Compliance Engine.
19. The fire code official is authorized to require that certain required records be filed with the fire code official.
20. Owners or premise property manager designee shall have the contractor licensed to inspect fire prevention and lift safety systems within the State of Iowa are required to submit their reports of systems within he City of Waukee jurisdiction. All reports shall be submitted within 30 days of the inspection or maintenance completion. Systems with impairments should be reported immediately.
21. Code Section 109: Refer to Waukee Board of Appeals.
22. Delete Code Section IFC 1010.4 and replace with the following language:
110.4 Violation Penalties. Anyone who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair, or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate used under provisions of this code, shall be guilty of a simple misdemeanor unless declared to be a municipal infraction in this code or in any City ordinances. If the act is not declared to be a simple misdemeanor or a municipal infraction and if no specific penalty is provided therefore, the violation of any such provision shall be deemed to be a simple misdemeanor punishable by a civil penalty as outlined in Section 1.15 of the City Code. The City of Waukee may classify a violation of this code as a municipal infraction per Chapter 4 of the City Code. If classified as a municipal infraction, each day that a violation continues after due notice has been served shall be deemed a separate offense.
23. Section 112.4. Insert dollar amounts in accordance with 110.4.
24. Delete Code Section IFC 308.1.4 and replace with the following language:
308.1.4 Open-Flame Cooking Devices. Charcoal burners, other open-flame cooking devices, and other devices that produce ashes or embers shall not be operated on balconies or within 20 feet (3,048 mm) of combustible construction. Location of LP containers shall comply with Section 6104.
Exceptions:
1. One- and two-family dwellings, constructed in accordance with the International Residential Code.
2. LP-gas cooking devices having LP-gas container with a water capacity not greater than 20 pounds.
25. Insert New Code Section 319.11:
26. 319.11 Location. Mobile food vehicles shall not be located within 20 feet (6,096 mm) of buildings, tents, canopies, or membrane structures.
27. Inset New Code Section 503.1.4:
28. 503.1.4 Outdoor Venue Access. A 10 ft. wide emergency access road designed to support a 36,000 lb. weight load shall be provided within 350-feet of all portions of an outdoor venue (e.g. soccer complex, park, skate park, sports fields) to facilitate emergency vehicle access.
29. Exception: The fire code official is authorized to increase the dimension of 350 feet where emergency access roads cannot be installed because of location on property, topography, waterway, nonnegotiable grades, or other similar conditions, and an approved alternative means of emergency access is provided.
30. Delete Code Section IFC 503.2.1 and replace with the following language:
31. 503.2.1 Dimensions. Fire apparatus access roads shall have a minimum unobstructed width of not less than 20 feet (6,096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4,268 mm).
32. Delete Code Section IFC 505.1 and replace with the following language:
33. 505.1 Address Identification. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall be black or white and shall contrast with their background. Where required by the fire code official, address numbers shall be provided in greater dimension or additional approved locations to facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters. Numbers and letters shall be a minimum height and a minimum stroke width as dictated by Table 505.1. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole, or other sign or means shall be used to identify the structure. Address numbers shall be maintained.
34. TABLE 505.1 – Minimum Height and Stroke Width
Distance From the Centerline of the Public Way (ft) | Minimum Height (in) | Minimum Stroke Width (in) | ||
Less than 100 | 4 | ½ | ||
100 | 199 | 6 | ¾ | |
200 | 299 | 8 | 1 | |
For each additional 100 | Increase 2 | Increase 1/2 |
a Exterior suite identification, minimum height shall be four inches and stroke width shall be ½ inch.
b Interior suite identification, minimum height shall be two inches and stroke width shall be ¼ inch.
35. Delete Code Section IFC 507.5.1.1 and replace with the following language:
36. 507.5.1.1 Hydrant For Fire Department Connection. Buildings equipped with a Fire Department connection installed in accordance with Section 912 shall have a fire hydrant located on a fire access road within 100 feet (30 m) of the Fire Department connection as measured by an approved route around the exterior of the building.
37. Exception: The distance shall be permitted to exceed 100 feet (30 m) where approved by the fire code official.
38. Delete Code Section IFC 507.5.5 and replace with the following language:
39. 507.5.5 Clear Space Around Hydrants. A five-foot (1,524 mm) horizontal clear space shall be maintained around the circumference of fire hydrants, as measured from the center-point of the hydrant, except as otherwise required or approved.
40. Insert New Code Section IFC 507.5.7:
41. 507.5.7 Fire Hydrant Markers and Identification Color. When required by the fire code official, hydrant locations shall be identified by the installation of an approved reflective marker. Both public and private hydrants shall comply with and be painted to local water utility specifications.
42. Insert New Code Section IFC 507.5.8:
43. 507.5.8 Fire Hydrant Installation. Fire hydrants shall be installed with the grade mark on the fire hydrant at the level of finished grade. The large diameter connection shall be installed such that the connection is oriented facing the Fire Department access road.
44. Delete Code Section IFC 508.1 and replace with the following language:
45. 508.1 General. Where required by other sections of this code, Table 508.1, and in all buildings classified as high-rise buildings by the International Building Code, a fire command center for Fire Department operations shall be provided and shall comply with Section 508.1.1 through 508.1.6.
46. Add Code Section IFC Table 508.1:
47. Table 508.1 Fire Command Center Thresholds
Occupancy | Threshold Requiring a Fire Command Center |
Group A | 1,000 occupants |
Group E | 100,000 gross square feet |
Group F | 200,000 gross square feet |
Group H | 100,000 gross square feet |
Group I-2 or I-3 | 100,000 gross square feet |
Group M | 100,000 gross square feet |
Group R1 | Greater than 200 dwelling units or sleeping units |
Group S | 200,000 gross square feet |
48. Insert New Code Section 511 Fire and Emergency Vehicle Lines:
49. 511.1 General. Fire and emergency vehicle lanes shall be provided and maintained in accordance with Section 511.1 through 511.6, and referred to as fire lanes in this Code.
50. 511.2 Purpose. The requirement that fire lanes be established in certain parking areas and the enforcement of restrictions on parking in such fire lanes established in this chapter are designed to ensure adequate access to commercial, office, multi-family, and other high density use facilities by fire-fighting and other emergency vehicles.
51. 511.3 Designation. The fire code official may designate fire lanes on private and public property as deemed necessary for the protection of life and property.
52. 511.4 Obstruction. No person shall park or place a vehicle or other obstruction in a designated fire lane that would prevent such fire lane from being immediately accessible to emergency vehicles, or deter or hinder emergency vehicles from gaining immediate access to the fire lane. A written request to the jurisdictional fire code official for temporary obstruction of a fire lane shall be submitted for approval.
53. 511.5 Signs and Markings. Whenever a fire lane has been designated, the Code Official shall cause appropriate signs and markings to be placed identifying such fire lanes. Signs or markings shall be maintained in a clean and legible condition at all times and shall be replaced or repaired when necessary to provide adequate visibility. Fire lanes may be established or relocated at the time of plan review, pre-construction site inspection, and/or post construction site inspection, as well as any time during the life of the occupancy as needed to provide and maintain emergency vehicle access. All designated fire lanes shall be clearly marked in the following manner:
54. Vertical curbs shall be painted red on the top and side, extending the length of the designated fire lane. Rolled curbs or surfaces without curbs shall have a red six-inch wide stripe painted the length of the designated fire lane. One of the following identification lettering methods shall be utilized:
55. 1. The words “NO PARKING – FIRE LANE (Except for Emergency Vehicles)” shall be stenciled with three-inch white letters and a minimum ¾ inch stroke on the face of the curbing, or in the absence of vertical curbing, on the red stripe, and spaced at 50 foot intervals or portions thereof, or
56. 2. The pavement adjacent to the painted curbs shall be marked with minimum 18 inch in height block lettering with a minimum three inch brush stoke reading: “NO PARKING – FIRE LANE.” Lettering shall be red and spaced at 50 foot intervals or portions thereof.
57. Signage identifying fire lanes shall conform to the following: Fire lane signs shall be 18 inches tall x 12 inches wide with red letters on a white reflective background to read “Fire Lane No Parking Except For Emergency Vehicle” or similar verbiage as approved by the code official. Fire lane signs shall be placed two to four feet from the edge of the fire lane. The bottom of fire lane signs shall be between five and seven feet from the ground. Intermediate fire lane signs shall be set every 100 feet in a continuous fire lane. The BEGINS sign shall mark the beginning of a fire lane and shall be mounted below the first fire lane sign. The ENDS sign shall mark the ending of a fire lane and shall be mounted below the last fire lane sign. The BEGINS and ENDS signage may be omitted by the code official due to the location of the fire lane. Signs may be placed on a building when approved by the fire code official.
58. 511.6 Maintenance. The owner, manager, or person in charge of any property upon which designated fire lanes have been established shall provide marking as required above and, shall maintain fire lanes at their expense as often as needed to clearly identify the designated area as being a fire lane.
59. Delete Code Section IFC 605.12.4 Item #5 “By other approved means.” Do not replace with any other additional language.
60. Modify Code Section IFC 705.2.4 and replace with and add the following language:
705.2.4 Door Operation. Swinging fire doors shall close from the full open position and latch automatically. The door closer shall:
1. Exert enough force to close and latch the door from any partially open position.
2. Be UL listed and of hydraulic type, spring type shall not be allowed.
61. Delete Code Section IFC 806.1 Exception #2 “Trees shall be allowed within dwelling units in Group R-2 occupancies.” Do not replace with any other additional language.
62. Insert New Code Section IFC 901.4.6.1.1 (correlation: IBC 902.1.1.1):
901.4.6.1.1 Fire Sprinkler Riser Room. A fire sprinkler riser room shall be separated from the electrical room. The riser room shall have no electrical panels, devices, or apparatus inside the room other than the outlets or support equipment (lighting, air compressor, and heater) required for the use of the fire sprinkler system and/or the fire alarm panel. The sprinkler riser room shall not be exclusively accessed from the electrical room, but the electrical room may be accessed from the fire riser room.
63. Insert New Code Section IFC 901.4.6.5 (correlation IBC 902.1.5):
64. 901.4.6.5 Temperature Sensors. Provide a low temperature sensor in the fire sprinkler riser room. Low temperature sensor shall be monitored to prevent freezing.
65. Modify Code Section IFC 901.6.3 and replace with the following language:
901.6.3 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained and submitted in accordance with Section 107.3.
66. Modify Code Section IFC 903.2 (correlation: IBC 903.2) replace with and add the following language:
903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12
1. An approved automatic fire extinguishing system is required if the gross square footage of a building is equal to or greater than described in Sections 903.2.1 through 903.2.12.
2. The square footage used for calculating total “gross square footage” of a building or structure shall be measured using the outside dimensions of the total building or structure to include attached or detached buildings or structures.
3. To exempt detached buildings or structures from the total gross square footage from meeting the requirements to have fire sprinklers systems installed, the buildings or structures per legal lot or contiguous lots under common ownership, must be separated by 20 feet and have one-hour rated exterior walls on both buildings or structures so as not to have the combined total of their gross square footage applied to this section of the code.
4. For the purposes of Section 903.2, “fire separations” shall not be permitted to reduce the total gross square footage of a building or area for the purpose of calculating the fire sprinkler square footage requirements.
5. For the purposes of Section 903.2, “story” shall be defined as any level of a structure, whether above or below grade capable of occupancy.
6. Additions to buildings or structures shall comply with all of the requirements of Section 903.2 of this code for new buildings or structures. The entire building or structure, existing and proposed additions, shall comply with all of the requirements of the fire sprinkler Section 903.2 of the fire code for new buildings and structures, when the total of all the additions to the building or structure made exceeds 25 percent of the gross area of the building or structure.
7. When a building is used for more than one occupancy purpose or use, the entire building shall meet the requirements of the fire sprinkler Section 903.2 of the fire code based on the requirements for the most restrictive occupancy group as defined in Chapter 2 of the 2018 International Fire Code.
Exceptions: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separate from the remainder of the building by not less than one-hour fire barriers constructed in accordance with Section 707 of the International Building Code or not less than two-hour horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both.
67. Delete Code Section IFC 903.2.1.1 Item #1 (correlation: IBC 903.2.1.1) replace with the following language:
Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
The gross square footage exceeds 6,000 square feet (1,115 m2).
The fire area has an occupant load of 300 or more.
The fire area is located on a floor other than a level of exit discharge serving such occupancies.
The fire area contains a multiple-theater complex.
68. Delete Code Section: IFC 903.2.1.2 (correlation: IBC 903.2.1.2) replace with the following language:
Group A-2. An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
The occupant load of 50 or more.
The fire area is located on a floor other than a level of exit discharge serving such occupancies.
69. Delete Code Section: IFC 903.2.1.3 (correlation: IBC 903.2.1.3) replace with the following language:
Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The gross square footage exceeds 6,000 square feet (1,115 m2).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
70. Delete Code Section: IFC 903.2.1.4 (correlation: IBC 903.2.1.4) replace with the following language:
Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The gross square footage exceeds 6,000 square feet (1,115 m2).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
71. Delete Code Section: IFC 903.2.2 (correlation: IBC 903.2.2) replace with the following language:
903.2.2 Group B. An automatic sprinkler system shall be provided throughout buildings containing a Group B occupancy where one of the following conditions exists:
1. The gross square footage exceeds 6,000 square feet (557.5 m2).
2. Group B fire area is located more than three stories above grade plane.
72. Insert Code Section: IFC 903.2.2.1 (correlation: IBC 903.2.2.1) insert the following language:
73. 903.2.2.1 Ambulatory Care Facilities. An automatic sprinkler system shall be installed throughout the entire floor containing an ambulatory care facility where either of the following conditions exist at any time:
74. 1. Four or more care recipients are incapable of self-preservation.
75. 2. One or more care recipients that are incapable of self-preservation are located at other than the level of exit discharge serving such a facility.
76. In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as all floors below where such care is provided, and all floors between the level of ambulatory care and the nearest level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge.
77. Exception: Floors classified as an open parking garage are not required to be sprinklered.
78. Delete Code Section: IFC 903.2.3 (correlation: IBC 903.2.3) replace with the following language:
Group E. An automatic sprinkler system shall be provided for Group E occupancies.
79. Delete Code Section: IFC 903.2.4 (correlation: IBC 903.2.4) replace with the following language:
Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists:
The gross square footage exceed 6,000 square feet (557.5 m2).
A Group F-1 fire area is located more than three stories above grade plane.
A Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceed 2,500 square feet (232 m2).
80. Delete Code Section: IFC 903.2.7 (correlation: IBC 903.2.7) replace with the following language:
903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists:
1. The gross square footage exceeds 6,000 square feet (557.5 m2).
2. A Group M fire area is located more than three stories above grade plane.
3. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m2).
81. Delete Code Section: IFC 903.2.9 (correlation: IBC 903.2.7) replace with the following language:
903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:
1. The gross square footage exceeds 6,000 square feet (557.5 m2).
2. A Group S-1 fire area is located more than three stories above grade plane.
3. A Group S-1 fire area used for the storage of commercial motor vehicles where the gross square footage exceeds 5,000 square feet (464 m2).
4. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2).
82. Delete Code Section: IFC 903.2.9.1 (correlation: IBC 903.2.9.1) replace with the following language:
903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406.8 of the International Building Code, as shown:
1. The gross square footage exceeding 3,500 square feet (325 m2).
2. Buildings with repair garages servicing vehicles parked in basements.
3. A Group S-1 used for the repair of commercial motor vehicles where the gross square footage exceeds 3,500 square feet (325 m2).
83. Insert New Code Section: IFC 903.2.10.2 (correlation: IBC 903.2.10.2):
903.2.10.2 Group S-2 All Other Occupancies Within a Group S-2. An automatic sprinkler system shall be provided throughout building with total gross square footage excess 12,000 square feet.
84. Insert New Code Section: IFC 903.3.1.1.3 (correlation: IBC 903.3.1.1.3)
903.3.1.1.3 Sprinkler Installed Under Exterior Projections. A canopy covering a door that is required to be marked as an exit shall be required to have fire sprinklers installed outside that door if the canopy extends more than four feet out from the door and is 12 feet or less in height from the ground regardless of whether the canopy is combustible or non-combustible. Canopies that have vehicle access under them with door openings shall be required to have fire sprinklers installed under the total canopy regardless of whether the canopy is combustible or non-combustible.
85. Modify Code Section: IFC 903.3.1.2 (correlation: IBC 903.3.1.2) and replace with the following language:
903.3.1.2 NFPA 13R Sprinkler Systems. Automatic sprinkler systems in Group R occupancies up to and including four stories in height in buildings not exceeding 60 feet (18,288 mm) in height above grade plane shall be permitted to be installed throughout in accordance with NFPA 13R. Attics shall be protected throughout with an automatic sprinkler system installed in accordance with NFPA 13.
86. Modify Code Section: IFC 903.2.11.1.3 (correlation: IBC 903.2.11.1.3) replace with the following language:
903.2.11.1.3 Basements. Where any portion of a basement is located more than 75 feet from openings required by Section 903.2.11.1, the basement shall be equipped throughout with an approved automatic sprinkler system.
87. Modify Code Section: IFC 903.4.2 (correlation: IBC 903.4.2) replace with the following language:
903.4.2 Alarms. An approved weather proof audible device suitable for outdoor use with 110 candela visual signal shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
88. Insert Code Section: IFC 905.3.9 (correlation: IBC 905.3.9) insert the following language:
905.3.9 Building Footprint and Access. Where the most remote portion of a floor or story is more than 400 feet from a hose connection or fire department access road the fire code official is authorized to require standpipes to be provided in approved locations. Class I manual standpipes shall be allowed.
89. Insert Code Section: IFC 907.1.4 (correlation: IBC 907.1.4) insert the following language
907.1.4 FACP (Fire Alarm Control Panels). Each building shall have no more than one FACP.
Installation of fire alarm panel shall not exceed six feet in height measured from the floor to the top of the unit.
Exception: Suppression system releasing panels are not required to meet the height requirement or the limitation in the number of panels.
90. Modify Code Section: IFC 907.2 (correlation: IBC 907.2) and replace with the following language:
907.2 Where required—New Buildings and Structures. An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 or when the gross square footage of a building is equal to or greater than the area as specified in Sections 903.2.1 through 903.2.11 inclusive, which shall be more restrictive and provide occupant notification in accordance with Section 907.5, unless other requirements are provided by another section of this code.
Not fewer than one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for fire alarm systems employing automatic fire detectors or water flow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire alarm box shall be installed. Manual fire alarm pull boxes “pull stations” shall be required where deemed necessary by the code official.
Where corridors and/or hallways are designed as the path of egress and are protected by fire sprinkler systems, they shall also be protected by smoke detection. Smoke detection shall be of the photo electric type or as approved by the Code Official.
Exceptions:
1. The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.
2. The manual fire alarm box is not required for Group R-2 occupancies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is accessible to the public.
91. Modify Code Section IFC 907.2.10.2 and replace with the following language:
92. 907.2.10.2 Automatic Smoke Detection System. An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in corridors, waiting areas open to corridors and habitable spaces other than sleeping units and kitchens.
93. Exceptions:
Smoke detection in habitable spaces is not required where the facility is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
94. Delete Code Section 907.2.10.3 and replace with the following language:
95. 907.2.10.3 Smoke Alarms. Single- and multiple-station smoke alarms shall be installed in accordance with Section 907.2.11.
96. Modify Code Section: IFC 907.2.11 and replace with the following language:
907.2.11 Single- and Multiple-Station Smoke Alarms. Listed single- and multiple-station smoke alarms complying with UL 217 shall be installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. Smoke alarms provided as part of the building fire alarm system and shall comply with the following:
1. The fire alarm system shall comply with all applicable requirements in Section 907.
2. Activation of a smoke alarm in a dwelling unit or sleeping unit shall initiate alarm notification in dwelling unit or sleeping unit in accordance with Section 907.5.2.
3. Activation of a smoke alarm in a dwelling unit or sleeping unit shall not activate alarm notification appliance outside the dwelling unit or sleeping unit, provided that a supervisory signal is generated and monitored in accordance with Section 907.6.6.
97. Modify Code Section: IFC 907.6.3 (correlation: IBC 907.6.3) and replace with the following language:
907.6.3 Initiating Device Identification. The fire alarm system shall identify the specific initiating device address, location, device type, and floor level where applicable and status including indication of normal, alarm, trouble, and supervisory status, as appropriate.
Exceptions:
1. Special initiating devices that do not support individual device identification.
2. Fire alarm systems or devices that are replacing existing equipment that does not support individual device identification.
98. Modify Code Section: IFC 907.6.6 (correlation: IBC 907.6.6) replace with the following language:
Monitoring. Fire alarm systems required by this chapter or by the International Building Code shall be monitored by a central station approved and listed under UL 827 in accordance with NFPA 72.
Exception: Monitoring station is not required for automatic sprinkler and fire alarm systems in one- and two- family dwellings.
99. Modify Code Section: IFC 910.2.1 (correlation: IBC 910.2.1) replace with the following language:
910.2.1 Group F-1 or S-1. Smoke and heat vents installed in accordance with Section 910.3 or a mechanical smoke removal system installed in accordance with Section 910.4 shall be installed in buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 30,000
square feet (2,787 m2) of undivided area. In occupied portions of a building equipped throughout with an automatic sprinkler system in accordance with 903.3.1.1, where the upper surface of the story is not a roof assembly, a mechanical smoke removal system in accordance with Section 910.4 shall be installed.
Exception: Group S-1 aircraft repair hangars.
100. Modify Code Section: IFC 1008.3.3 (correlation: IBC 1008.3.3) replace with the following language:
1008.3.3 Rooms and Spaces. In the event of a power supply failure, an emergency electrical system shall automatically illuminate all of the following areas:
1. Electrical equipment room.
2. Fire command centers.
3. Fire pump rooms.
4. Generator rooms.
5. Public restrooms that contain more than one water closet/urinal or that are accessible.
6. Meeting/conference rooms with an area greater than 400 square feet.
7. Classrooms in an E occupancy with an area greater than 400 square feet.
101. Modify Code Section: IFC 1009.2 (correlation: IBC 1009.2) insert Item # 11 with the following language:
11. Components of exterior walking surfaces shall be concrete, asphalt, or other approved hard surface.
102. Add Code Section: IFC 1010.1.6.1 (correlation: IBC 1010.1.6.1) insert the following language:
1010.1.6.1 Frost Protection. Landings required by Section 1010.1.5 to be at the same elevation on each side of the door exterior landings at doors shall be provided with frost protection.
103. Modify Code Section: IFC 1010.1.9.1 (correlation: IBC 1010.1.9.1) replace with the following language:
1010.1.9.1 Hardware. Door handles, pulls, latches, locks, and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching, or twisting of the wrist to operate. This includes thumb turn locks.
104. Insert Code Section: IFC 1013.1.1 (correlation: IBC 1013.1.1) language:
1013.1. 1 Additional Exit Signs. Exit signs may be required at the discretion of the Code Official to clarify an exit or exit access.
105. Modify Code Section: IFC 1014.4 (correlation: IBC 1014.4) insert Item No. 6 with the following language:
6. Handrails within a dwelling unit or serving an individual dwelling unit of Groups R-2 and R-3 shall be permitted to be interrupted at one location in a straight stair when the rail terminates into a wall or ledge and is offset and immediately continues.
106. Add Code Section: IFC 1015.9 (correlation: IBC 1015.9) insert the following language:
107. 1015.9 Walking Surfaces. A guard shall be provided along retaining walls where a finished walking surface such as sidewalks, patios, driveways, and parking lots or similar is located on the top side of a retaining wall. The guard shall be installed along any portion of the wall measuring 30 inches or greater in height measured at any point within 36 inches horizontally to the edge of the open side. A guard shall not be required along portions of the retaining wall where the horizontal distance between the edge of the finished walking surface and the face of the wall is greater than 72 inches.
108. Insert Code Section: IFC 1028.5.1 (correlation: IBC 1028.5.1) insert the following language:
1028.5.1 Hard Surfaces. Components of exterior walking surfaces shall be concrete, asphalt, or other approved hard surface.
109. Insert Code Section: IFC 1030.4.3 (correlation: IBC 1030.4.3) insert the following language:
1030.4.3 Window Wells Drainage. All window wells shall be provided with approved drainage.
110. Insert New Code Section: IFC Section 1107.1 insert the following language:
SECTION 1107
REQUIREMENTS FOR FUEL FIRED APPLIANCES
1107.1 Protection of Fuel Fired Appliances. Where required or upon notification from the fire code official an existing building or tenant space containing a fuel fired appliance(s) shall be protected with one hour rated construction enclosure or a limited area sprinkler system complying with Section 903.3.8.
Exception: Buildings protected by an approved automatic fire sprinkler system complying with Section 903.3.1.1 or 903.3.1.2.
111. Insert New Code Section: IFC Section 1107.2 insert the following language:
112. 1107.2 CSST Bonding Requirements in Rental Dwellings. All rental dwelling shall be bonded in accordance with Sections 310.2.1 through 310.2.5 of the International Fuel Gas Code, unless deemed technically infeasible by the code official.
113. Insert New Code Section: IFC Section 1107.3 insert the following language:
114. 1107.3 CSST Bonding Requirements for Alterations, Repairs, or Additions. For other than rental dwelling units, where alterations, repairs, or additions requiring a permit to occur, CSST shall be bonded in accordance with Sections 310.2.1 through 310.2.5 of the International Fuel Gas Code, unless deemed technically infeasible by the code official.
115. Insert New Code Section: IFC 1203.7 insert the following language:
116. 1203.7 Shutdown of Emergency and Standby Power Systems. In addition to the requirements of NFPA 110 for a remote manual stop, a switch of an approved type shall be provided to shut down the generator. The switch shall be provided at an approved location.
117. Insert New Code Section: IFC 1203.8 insert the following language:
118. 1203.8 Emergency Generator Signs. Main electrical disconnects and main breaker panels supplied by the generator shall be provided with approved signs.
119. Additionally, doors accessing emergency and standby power systems shall be provided with approved signs. When approved switches for emergency power shut-down are located remote from the fire alarm annunciator, an approved sign shall be provided at fire alarm annunciator. Approved signs shall contain the word CAUTION in black letters at least two inches (50 mm) high on a yellow background. Such warning signs shall be placed so as to be readily discernible.
120. Insert New Code Section: 3103.3.1.1
121. 3103.3.1.1 Temporary Special Amusement Buildings. Where the special amusement building is temporary, the sprinkler water supply shall be of an approved temporary means. The sprinkler piping shall be connected to a temporary water supply having sufficient capacity (flow and pressure) to supply residential or standard quick spray response sprinkler heads at a minimum design density of 0.15 gpm (0.57 LPM) per square foot of protected floor area. The design shall be based on flowing the six most hydraulically remote sprinkler heads. Should the temporary amusement building contain less than six heads, the design shall assume that all heads are flowing simultaneously.
122. The temporary water supply may be connected to a domestic water line, a fire line, or temporary on-site storage tank as long as the minimum design densities are met. An indicating type control valve shall be installed in an accessible location between the sprinkler system and the connection to the water supply.
123. Insert New Code Sections 3106.3.3, 3106.3.4, and 3106.3.5:
124. 3106.3.3 Occupancy and Means of Egress. The number and location of emergency egress and escape routes shall be approved by the fire code official. Exits shall comply with Chapter 10 and be as remote from each other as practical and shall be provided as follows:
Occupant Load | Minimum Number of Exits |
1 to 500 | 2 |
501 to 1,000 | |
1,001 to 1,500 | 4 |
Each additional 500 persons | 36 additional inches of exit width |
1. 3106.3.4 Width. The aggregate clear width of exits shall be a minimum of 36 inches wide (914 mm) for each 500 persons to be accommodated.
2. 3106.3.5 Signs. Exits shall be identified with signs that read “EXIT.” The signs shall be weather-resistant with lettering on a contrasting background. The lettering shall be of sufficient height and brush stroke to be immediately visible from 75 feet (22,860 mm). Placement of the exit signs shall be approved by the fire code official.
125. Insert New Code Section 3106.8:
126. 3106.8 Temporary Water Stations. When outdoor temperatures are expected to exceed 90OF (35OC), the event sponsor shall provide and maintain a minimum of one staffed water station for each 1,000-projected in attendance. The water station shall include adequate water supply, cups, and a means for rapid replenishing of exhausted water. Each water station shall be located as far apart as practicable to allow ease of access for event attendees.
127. Insert New Code Section 3107.12.3.1:
128. 3107.12.3.1 Public Isolation. Cooking appliances or devices shall be isolated from the public by not less than four feet (1,219 mm) or by a non-combustible three-sided barrier between the equipment and devices and the public.
129. Insert New Code Section 3107.12.4.1:
130. 3107.12.4.1 Protection. Single-well cooking equipment using combustible oils or solids shall meet the following:
131. 1. A noncombustible lid shall be immediately available. The lid shall be of sufficient size to cover the cooking well completely.
132. 2. The cooking surface shall not exceed 288 square inches (18,580 mm).
133. 3. The equipment shall be placed on a noncombustible surface.
134. 4. The equipment shall be separated from each other by a horizontal distance of not less than two feet (609 mm).
135. Insert New Code Section 3107.20:
136. 3107.20 Concession Stands, Food Booths, and Retail Booths. Concession stands, food booths, and retail booths shall be a minimum of 20 feet (6,096 mm) between every 150 linear feet (45,720 mm) of booth space. A minimum of 30 feet (9,144 mm) shall be provided between booths used for cooking and the vehicles, generators, or any other internal combustion engines. A minimum of 30 feet (9,144 mm) shall be provided between booths used for cooking and amusement rides or devices.
137. Insert New Code Section 3107.17.3:
138. 3107.17.3 Assistance. Adult monitors with flashlights shall be available to provide assistance in the event someone becomes lost of disoriented. One adult monitor shall be provided for every 60 persons.
139. Insert New Code Section 3108:
140. Section 3108 Mazes
141. 3108.1 General. Mazes including, but not limited to corn stalk or hedge mazes, shall be in accordance with Section 3808.
142. 3108.1.2 Safe Refuge Areas. Safe refuge areas shall be established outside of the maze or building and structure, and shall not be closer than 50 feet (15,240 mm),
143. 3108.1.3 Paths. Paths throughout the maze shall be a minimum of 36 inches (914 mm) in width and shall be clear and unobstructed width.
144. 3108.1.4 Separation. A minimum of 20 feet (6,096 mm) shall be provided between mazes and buildings and structures. The 20-foot (6,096 mm) clearance shall be free from vegetation and obstructions.
145. 3108.1.5 Means of Egress. Each exit shall be a minimum of six feet (1,828 mm) wide.
146. 3108.1.5.1 Travel Distance. The maximum travel distance to reach an exit access shall not exceed 75 feet (22,860 mm). The travel distance shall be determined by using the maze path.
147. 3108.1.5.2 Number. The travel distance required to reach an exit access shall determine the number of exits required. Locking devices shall remain unlocked on exits when the maze is occupied.
148. 3108.1.5.3 Exit Signs. Exit signs shall be provided next to or above each exit. The lettering shall be a minimum of 12 inches (305 mm) high with two-inch (51 mm) brushstroke. The signs shall read EXIT with lettering in a color contrasting to the sign’s background.
149. 3108.2 Event Plans. The following plans shall be submitted to the fire code official.
150. 3108.2.1 General Fire Safety Plan. The plan shall include, but not be limited to procedures that shall be used to prevent over-drying of vegetation throughout the site, documentation of decorative materials flame-retardancy, the maximum number of attendees.
151. 3108.2.2 Security Plan. The plan shall document who shall provide security (e.g., off-duty police officers, sheriff’s posse, and employees). All security personnel shall be provided with a two-way radio and flashlight.
152. 3108.2.3 Evacuation Plans. The plan shall document the responsibilities of all on-site employees plan shall also document how attendees will be evacuated, and where they will be evacuated.
153. 3108.3.2 Main Entrance Employee. Each maze shall be manned by an employee at the entrance. The employee shall be capable of communicating with the employees and shall be provided with a cellular telephone. When the main entrance employee receives a report of smoke, fire, or injury, the employee shall immediately call 9-1-1.
154. plan shall also document how attendees will be evacuated, and where they will be evacuated.
155. 3108.2.4 Maze Rules. Maze rules shall be posted at maze entrance.
156. 3108.3 Employee Responsibilities. Each employee shall be familiar with the evacuation plan and with fire extinguisher locations. Documentation of training shall be provided to the fire code official.
157. The 3108.3.1 Guides. An employee shall be responsible for guiding a group of not more than 14 attendees through the maze. Each employee shall be provided with a minimum of one flashlight and two-way radio. The employees shall be responsible for detecting and reporting fire or smoke to a competent person posted at the maze main entrance and begin evacuation procedures.
158. 3108.4 Watering. Corn stalk and hedge mazes shall be provided with sufficient water and at a frequency that prevents the vegetation from becoming dry or brittle. Failure to comply with this provision is an imminent hazard and the fire code official shall issue a stop order.
159. 3108.5 Buildings and Structures. When buildings and structures are intended to be occupied by attendees, the building and structure shall coply with Section 3105.
160. Insert New Code Section IFC Section 3202 insert the following language:
SECTION 3202
DEFINITIONS
3202.1 Definitions. The following terms are defined in Chapter 2:
Speculative building. A Group S, F, or M occupancy having an interior clear height greater than 12 feet (3,657 mm) where high-piled storage may accrue and the client leasing or the occupant owner does not know the commodity that will be stored or the method of storage.
3206.2.2 Speculative building. Group S, F, and M speculative buildings that have an interior clear height greater than 12 feet where high piled storage may accrue shall comply with this chapter.
3206.4.2 Sprinkler design.
3206.4.2.1 General. The design of automatic sprinkler systems for the protection of Group M and S occupancies containing high-piled storage or high-challenge commodities over an area equal to or greater than 2,500 square feet (232 m2) and designed for the protection of hazardous materials stored more than one pallet high in Group M, S, or H occupancies, shall be in accordance with this section. This section does not apply to miscellaneous storage within the scope of NFPA 13.
3206.4.2.2 Requirements for All Plan Submittals. See Section 903.1.9 and 3201.3 for plan submittal requirements.
3206.4.2.3 Minimum Design Requirements for Speculative Warehouses. The design of the automatic sprinkler system for speculative warehouses shall be based on storage of a cartoned Class A non-expanded plastic to the available storage height. The storage height shall be determined by subtracting 48 inches (from the highest point of the roof above each system for ESFR and 30 inches for area density applications.
3206.4.2.4 Minimum Requirements for Client Leased or Occupant-Owned Warehouses. The design of an automatic sprinkler system for client leased or occupant owned buildings containing high piled storage shall be based on the requirements of NFPA 13. The responsible Fire Protection Contractor shall perform a survey of the building to determine commodity classification, storage configuration, building height and other information related to the development of an appropriate sprinkler system design. The Contractor shall also make reasonable efforts to meet with the building owner or operator to understand seasonal or customer related fluctuations to the stored commodities, storage height, and configuration.
The sprinkler design shall be based on the most demanding requirements determined through the on-site survey and discussions with the building owner or operator. Technical Report shall clearly define the basis for determining the commodity and sprinkler design selection, along with how the commodities will be isolated or separated, and the referenced design document(s), including NFPA 13 or the current applicable Factory Mutual Data Sheets. If a specific fire test is used as the basis of design, a copy of the fire test report shall be provided at the time of plan review.
3206.4.2.5 Required Information at Plan Submittal. All plans, hydraulic calculations and technical reports shall be submitted with the plan submittal form. The individual submitting the design package shall ensure that all of the required information requested on the plan submittal form is included.
3206.4.2.6 Minimum Plan Information Requirements. In addition to the requirements of NFPA 13, the following information shall be included in the plans or technical report.
3206.4.2.6.1 Class I-IV and Group A Plastic Commodities.
A. An owner’s certificate in accordance with NFPA 13. The design criteria, e.g., NFPA 13, Factory Mutual Data Sheet, or a specific fire test report.
B. A Water Supply Flow and Pressure Test Report performed within 90 days of the plan submittal.
C. The type of design, e.g., Control Mode Density/Design Area Method; Specific Application Control Mode Method; Suppression Mode Method, including appropriate code references.
D. A description of the stored commodities and how the commodity classification was determined.
E. A layout of the proposed storage arrangement. If the storage is in racks, a plan and elevation detail illustrating rack heights, flue dimensions and arrangement. This detail is not required for speculation warehouses.
F. The aisle dimensions between each storage array.
G. If a high challenge commodity is separated using fire-resistive construction, the boundary of the fire-resistive construction shall be illustrated.
H. A data sheet for the backflow preventer. If a data sheet is not available, the design professional shall include a statement addressing the minimum required pressure loss.
I. A data sheet for each installed automatic sprinkler.
J. A data sheet for each pipe hanger used to hang or support the sprinkler piping.
K. If a fire pump will be installed or used, the manufacturer’s factory test curve shall be included in the submittal.
L. A cross-section view illustrating obstructions to the ceiling sprinklers, e.g., lights, structural members, cable trays, electrical bus ducts and HVAC ductwork.
3206.4.2.6.2 Hazardous materials. In addition to the requirements of this section, the following information shall be included in a hazardous materials technical report.
A. A hazardous materials inventory statement.
B. For flammable and combustible liquids, an analysis of the miscibility of Class I liquids, the size and type of the packaging, the packaging materials of construction, and if the containers have a pressure relieving mechanism.
C. For Level 2 or 3 aerosols, a statement indicating that the aerosols are cartoned or uncartoned.
3206.4.2.7 Identification of sprinkler system capabilities and limitations. A label shall be permanently installed at or adjacent to each sprinkler riser. When a building contains more than four risers, the sign shall be located at an approved location inside the building. The minimum sign dimension is six inches (152 mm) high by four inches (101 mm) wide. The sign shall specify the capabilities and limitations of the automatic sprinkler system. The sign shall include the following information:
a. The design base or basis, including the edition used.
b. A statement indicating if the sprinkler design is control mode density area method, control mode specific application, suppression mode, or any combination thereof.
c. When used, all of the storage conditions stipulated NFPA 13 for Special Designs.
d. The maximum storage height.
e. The minimum required aisle width.
f. If storage is in racks, the maximum rack width and minimum transverse and longitudinal flue widths.
g. Storage Capabilities: Commodities designed to be protected by the automatic sprinkler system.
h. Limits on storage heights of idle wood and plastic storage.
i. Limits on storage heights of miscellaneous Group A plastic, tire and rolled paper storage.
j. Locations where in-rack sprinklers are required.
k. Locations where horizontal and/or vertical barriers are required.
l. Information explaining the manufacturer, sprinkler identification number, k- factor, and operating temperature of the overhead sprinklers protecting the high-piled storage.
m. Fire Protection Contractor contact information.
The following example illustrates a suggested label or sign:
Automatic Sprinkler System Capabilities and Limitations
Stored Commodity Class I waste miscible flammable liquids in one- and five-gallon polyethylene containers in fiberboard cartons
Design Documents NFPA 13, 2013 edition and NFPA 30
Design Type Control Mode, Density/Area Method
Maximum Storage Height 25 feet
Aisle Width 8 feet
Rack Width 9 feet
Flue Dimensions Longitudinal: Min. 6 inches
Transverse: Min. 3 inches
System Capabilities Class I-IV commodities, stored commodity, solid pile or palletized Group A plastics to 12 feet; rack storage of Group A plastics to 25 feet
Idle Pallets 6 feet maximum storage height
Tire Storage 5 feet maximum storage height
Rolled Paper Storage 5 feet maximum storage height
In-rack sprinklers In-rack sprinklers are required at each of three rack tiers containing the stored commodity. In-rack sprinklers are Tyco/Central FS-B, 17/32-inch orifice, QR 155º F element, SIN TY0041
Horizontal Barriers Required at each rack tier containing the stored commodity
Ceiling Sprinkler Tyco ELO-231B, ¾-inch orifice, SR 286º F element, upright, SIN TY0030
FP Contractor ABC Sprinkler Co. Designer: John Smith
161. Delete Code Section: IFC Section 3301.2 replace with the following language:
3301.2 Purpose. This chapter prescribes minimum safeguards for construction, alteration and demolition operations to provide reasonable safety to life and property from fire and other emergencies during such operations.
162. Insert New Code Section: IFC Section 3310.1.1 insert the following language:
Section 3310.1.1 Construction Site Access. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building as soon as construction commences. The fire apparatus access road shall comply with the requirements of Section 503.2 and this section and shall extend to within 100 feet (45,720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility.
Exception: The fire code official is authorized to increase the dimension of 100 feet (45,720 mm) where:
1. The building is equipped throughout with an approved automatic sprinkler system that is fully functional and installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided.
163. Insert New Code Section: IFC Section 3311.1 replace with the following language:
164. 3311.1 Stairways Required. Where building construction exceeds 30-feet (9,144 mm) in height above the lowest level of Fire Department vehicle access, two temporary or permanent stairways shall be provided. As construction progresses, such stairways shall be extended to within one floor of the highest point of construction having secured decking or flooring.
165. Delete Code Section: IFC 3313.1 replace with the following language:
166. 3313.1 Where Required. In buildings required to have standpipes by Section 905.3.1, not less than one standpipe shall be provided for use during construction. Such standpipe shall be installed prior to construction exceeding 30-feet (9,144 mm) in heigh above the lowest level of Fire Department vehicle access. Such standpipe shall be provided with Fire Department hose connections at approved locations complying with Section 3311.1. As construction progresses, such standpipes shall be extended to within one floor of the highest point of construction having secured decking or flooring.
167. Add Exception to Code Section: IFC 5601.4 add he following language (exception):
Exception: Persons in charge of fireworks display or pyrotechnic special effect operations may be less than 21 years of age if they possess a valid PGI display fireworks operator certification or equivalent certification approved by the fire code official.
Section 5704.2.9.6.1 (geographic limits in which the storage of Class I and Class II liquids in above-ground tanks outside of buildings is prohibited): In accordance with zoning ordinance and approved by code official.
Section 5706.2.4.4 (geographic limits in which the storage of Class I and Class II liquids in above-ground tanks is prohibited): In accordance with zoning ordinance and approved by code official.
Section 5806.2 (geographic limits in which the storage of flammable cryogenic fluids in stationary containers is prohibited): In accordance with zoning ordinance and approved by code official.
Section 6104.2 (geographic limits in which the storage of liquefied petroleum gas is restricted for the protection of heavily populated or congested areas): In accordance with zoning ordinance and approved by code official.
168. Delete Code Section: IFC Section 6104.2 replace with the following language:
6104.2 Maximum Capacity Within Established Limits. Within the limits established by law restricting the storage of liquefied petroleum gas for the protection of heavily populated or congested areas, the installation of liquefied petroleum gas shall be prohibited unless specifically approved by the fire code official, and in that case the aggregate capacity of any one installation shall not exceed a water capacity of 1,000 gallons (3,785 L) (see Section 3 of the Sample Legislation for Adoption of the International Fire Code on page xxi).
Exception: Containers shall not exceed a water capacity of 20 gallons, must be located outside of the building, and used for cooking purposes only.
169. Insert Code Section: IFC 6104.3.3 insert the following language:
6104.3.3 LP Gas Containers in Group R Occupancies. LP gas shall not be stored or used inside of a building.
170. Add Code Section: IFC D104.5 add the following language:
171. D104.5 Fire Department Access Points. A minimum of two means of approved fire apparatus access points shall be provided for every facility, building, or portion of a building hereafter constructed or moved into or within the jurisdiction. Access points shall have a minimum clear width of 20 feet and shall support an imposed load of 75,000 lbs.
172. Exceptions: When alternative fire and life safety measures have been implemented, the number of required access points may be reduced to one.
173. Add Code Section: IFC D104.5.1 add the following language:
174. D104.5.1 Remoteness. Where two fire apparatus access points are required, they shall be placed a distance apart equal to not less than one half of the length of the maximum overall diagonal dimension of the lot or area to be served, measured in a straight line between accesses.
175. Exceptions: When alternative fire and life safety measures have been implemented, the distance between required access points may be reduced to a distance not less than one quarter of the length of the maximum overall diagonal dimension.
176. Delete Code Section: IFC D105.3 replace with the following language:
D105.3 Proximity to Building. At least one of the required access routes meeting this condition shall be positioned along a total of ¼ of the building perimeter and located within the minimum and a maximum dictated by the table below, Table D105.3. The arrangement of the aerial fire apparatus access road shall be approved by the fire code official and may be discontinuous with approval.
Building Height (ft) | Distance from Building (ft) | ||
Minimum | Maximum | Minimum | Maximum |
30 | 40 | 15 | 50 |
40 | 50 | 15 | 40 |
50 | N/A | 15 | 30 |
177. Delete Code Section: IFC D107.1 Exception No. 2 replace with the following language:
2. The number of dwelling units on a single fire apparatus access road shall not be increased unless alternative fire and life safety measures have been provided, as determined by the fire code official. When alternative fire and life safety measures have been implemented, at no time shall the number of dwelling units on a single fire apparatus access road exceed 60 units.
178. Insert New Code Section: N104.2.1:
179. N104.2.1 Materials. Shall be one of the following:
Noncombustible or limited-combustible materials.
Wood that is greater than ¼-inch (6 mm) nominal thickness.
Wood ¼-inch (6 mm) nominal thickness or less that is pressure-treated fire-retardant wood meeting the requirements of NFPA 703, Standard for Fire Retardant Impregnated Wood and Fire Retardant Coatings for building materials. The product shall be marked or labeled by the manufacturer. The product shall not be painted or similarly modified until the material has been inspected and the marking or labeling verified, or provide documentation acceptable to the fire code official.
180. Insert New Code Section: N107.2.1:
181. N107.2.1 Storage of Combustible Materials Quantity. Combustible materials shall be limited to a one-day supply.
182. Insert New Code Section: N107.2.2:
183. N107.2.2 Location. Storage of combustible materials behind exhibits, booths, or tents is prohibited. Combustible materials, including but not limited to wood crates, paper, and cardboard boxes, shall be stored outside the building in an approved area or in a storeroom having a fire-resistance rating of a least one hour and protected by an approved automatic fire-extinguishing system.
184. Insert New Code Section: N108.2.1:
185. N108.2.1 Travel Distance. The maximum travel distance from any point in an exhibit to an exit access aisle shall not exceed 50 feet (15,240 mm).
186. Insert New Code Section: N108.3.1:
187. N108.3.1 Aisle Width. Minimum aisle width inside a trade show or exhibition shall comply with the following:
188. Square Footage of Trade Show or Exhibition Minimum Aisle Width
189. Greater than 15,000 square feet (1,393 m2) 10 feet (3,048 mm)
190. 5,000 square feet (465 square meters) to 15,000 sq. ft (1,393 m2) 8 feet (2,438 mm)
191. Less than 5,000 square feet (465 m2) 6 feet (1,829 mm)