§ 53.11 REGULATIONS RELATIVE TO CUSTOMER’S PIPING, FACILITIES, APPLIANCES AND NECESSARY VENTING.
   (A)   All house piping shall be of rigid construction. The pipe from the outlet of the meter shall be of iron pipe not less than one-inch inside diameter and shall enter the house wall or be securely fastened to the wall by means of suitable metal strap or clamp at a point not more than 18 inches from the outlet connection of the meter, and if extended along the outside wall shall be fastened throughout. In instances where piping from meter enters the wall, the opposite end shall be securely fastened so that the pipe will not turn when fittings at the meter are put on. The piping from the meter through or along the wall shall constitute, and hereinafter be called the “house pipe manifold”. The one-inch manifold will be used where the total hourly demand for gas does not exceed 400 cubic feet per hour. Where the total hourly demand of a building or house is in excess of 400 cubic feet of gas per hour, the Village Gas Department must be consulted for specifications for the house pipe manifold.
   (B)   From any house pipe manifold, pipe to the various appliances shall be of the same dimensions as the fitting on the appliance where such appliance is designed and approved for natural gas. Where appliances are to be converted from liquefied petroleum gas, pipe from the manifold to the appliance shall be of such size as would be approved by the American Gas Association for natural gas appliances having the same BTU input rating.
   (C)   From the house pipe manifold any appliance pipe may be extended a maximum distance of 40 lineal feet. For each 90-degree turn in the appliance pipe, three lineal feet shall be deducted from the maximum distance. Copper pipe may be substituted for iron pipe from the manifold to the appliance. Copper pipe must have O.D. dimension equivalent to I.D. of standard iron pipe. Only type K copper pipe may be used. All copper fittings must be of flare type only. When copper tubing is used, insulated copper to iron fittings must be used at the meter end and appliance end of tubing.
   (D)   No connection will be made with any house type manifold that has not been tested for leakage.
   (E)   All gas conversion burners to be installed shall be AGA approved. All designated heating plants shall be AGA approved and the manufacturer’s recommendations for the installation shall be followed.
   (F)   No conversion burner shall be installed in an old or inefficient warm air furnace which is in poor repair or in an old or leaky boiler which is in poor repair. Test for leakage shall be with oil of wintergreen or smoke bomb on any warm air heating plant before installing a conversion burner. Furnaces must be reset if found to be leaking.
   (G)   Before connecting a flue or vent connector into any chimney, the chimney shall be examined to ascertain that it is properly constructed, clear, clean and will freely conduct the products of combustion from the gas heating appliance in question to the outer air.
   (H)   All appliances, excepting cook stoves, with over 8,000 BTU per hour input rating must be vented. No unvented appliance, excepting cook stoves, shall be placed in the same room with a gas refrigerator. An approved type vent pipe and draft diverter shall be installed on all gas burning space heating and water heating appliances. Vent pipe shall be installed with not less than one-half inch rise per foot of horizontal run. General rules for venting as prescribed by AGA must be followed.
   (I)   All positive type catches on firing door shall be eliminated and a hinge pin and spring be installed.
   (J)   All heating plants of the down draft type shall be vented by connecting a one-inch black iron pipe from the highest point of the flue passage of the heating plant to the flue pipe. The one-inch iron pipe shall be welded or screwed into the furnace in a manner to assure no leakage.
   (K)   A gas shut-off shall be installed in the fuel line directly above the appliance manifold connection. Such shut-off to be plainly marked. Gas pilot line shall be connected to fuel line ahead of main shut-off valve.
   (L)   A high limit control shall be installed on all heating plants. A low water cut-off control shall be installed on all gas fired steam boilers.
   (M)   All gas burning appliances shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas and proper venting under normal conditions of use. The necessary measures shall be taken to ascertain that the above ventilation conditions are present.
   (N)   The final tie-in of the gas line to the meter shall be made by the village. Before the final tie-in is made, it shall be the duty of the Village Gas Department to make a complete inspection.
(Prior Code, § 51.015) (Ord. 121, passed 9-2-1958)