SEC. 14-12. AMENDMENTS.
   (A)   Article 90-10: Add Article 90-10 to read as follows:
      Article 90-10. Administration. The legal jurisdiction and administration of this electrical code is regulated by the administrative sections as adopted in Chapter 14, Article II of the Oxnard City Code.
   (B)   Article 695.3: Amend Article 695.3 to read as follows:
      Article 695.3. Power Source(s) for Electric Motor-Driven Fire Pumps. Electric motor-driven fire pumps shall have a reliable source of power. Power provided by the local serving utility company shall only be considered a reliable source of power where an onsite generator is provided as an alternate source of power. [OSHPD 1, 1R, 2, 3, 4, & 5] Such reliable source of power shall consist of a normal source and an onsite generator as the alternate source.
(Ord. No. 3021)