(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Appendix A5 of the California Green Building Standards Code (CALGreen) is adopted by reference with the following exceptions: CALGreen Sections A5.105.1.1, A5.105.1.2, A5.106.4.3, A5.106.6.1, A5.106.11.1, A5.303.2.3.1, A5.303.2.3.2, A5.303.2.3.3, A5.303.2.3.4, A5.406.1, and Tables A5.106.4.3 A5.106.11.2.2, A5.106.11.2.3, A5.601, and A5.602 are not adopted; and in lieu, Los Angeles Municipal Code Section 99.12.508 and Subsections A5.105.1.1, A5.105.1.2, A5.106.4.3, A5.106.6, A5.106.6.1, A5.106.11.1, A5.303.2.3.1, A5.303.2.3.2, A5.303.2.3.3, A5.303.2.3.4, A5.406.1, A5.410.3, and Tables A5.106.4.3, A5.106.11.2.2, A5.106.11.2.3, A5.601, and A5.602 are added or amended as provided in this article.
EXCEPTIONS:
1. Window assemblies and nonstructural roofing material.
2. Hazardous materials that are remediated as a part of the project.
A5.106.4.3. Changing Rooms. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Provide changing/shower facilities for tenant-occupants only in accordance with LAMC Table A5.106.4.3 or document arrangements with nearby changing/shower facilities.
Number of Tenant- Occupants | Shower/Changing Facilities Required | 2-Tier (12"x15"x72") Personal Effects Lockers Required |
0 - 10 | 1 unisex shower | 1 |
11 - 50 | 1 unisex shower | 2 |
51 - 100 | 1 unisex shower | 3 |
101 - 200 | 1 shower stall per gender | 4 |
Over 200 | 1 shower stall per gender for each 200 additional tenant-occupants | One 2-tier locker for each 50 additional tenant-occupants |
Note: Additional information on recommended bicycle accommodations may be obtained from Sacramento Area Bicycle Advocates.
1. Use of on street parking or compact spaces, illustrated on the site plan; or
2. Implementation and documentation of programs that encourage occupants to carpool, ride share or use alternate transportation.
Note: Strategies for programs may be obtained from local TMAs.
1. Provide shade (mature within 15 years of occupancy);
2. Use light colored materials with an initial solar reflectance value of at least .30 as determined in accordance with American Society for Testing and Materials (ASTM) Standards E 1918 or C 1549;
3. Use open-grid pavement system or pervious or permeable pavement system; or
4. Use solar panel arrays to create a canopy shade system.
ROOF SLOPE | MINIMUM 3-YEAR AGED SOLAR REFLECTANCE | THERMAL EMITTANCE | 3-YEAR AGED SRI |
≤ 2 : 12 | 0.68 | 0.85 | 82 |
> 2 : 12 | 0.28 | 0.85 | 27 |
ROOF SLOPE | MINIMUM 3-YEAR AGED SOLAR REFLECTANCE | THERMAL EMITTANCE | 3-YEAR AGED SRI |
≤ 2 : 12 | 0.70 | 0.85 | 85 |
> 2 : 12 | 0.34 | 0.85 | 35 |
A5.303.2.3.1. Tier 1 - 12 Percent Savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 12% shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fitting as required by the Los Angeles Building Standards Code in Article 1, Chapter IX of the LAMC.
A5.303.2.3.2. Tier 2 - 20 Percent Savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 20% shall be provided. A calculation demonstrating a 20% reduction in the building shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fitting as required by the Los Angeles Municipal Code.
A5.303.2.3.3. 25 Percent Savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 25% shall be provided. A calculation demonstrating a 25% reduction in the building "water use baseline" shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fitting as required by the Los Angeles Municipal Code.
A5.303.2.3.4. Nonpotable Water Systems for Indoor Water Use. Utilizing nonpotable water systems (such as captured rainwater, treated graywater, and recycled water) intended to supply water closets, urinals, and other allowed uses, may be used in the calculations demonstrating the 12%, 20%, or 25% reduction. The nonpotable water system shall comply with the current edition of the Los Angeles Plumbing Code at Article 4, Chapter IX of the LAMC.
A5.410.3. Commissioning. For new buildings under 10,000 square feet (929.03 m2) or for additions, building commissioning shall be included in the design and construction processes of the building project to verify that the building systems and components meet the owner's or owner representative's project requirements. Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of comparable size and complexity. Commissioning requirements shall include:
1. Owner's or owner representative's project requirements;
2. Basis of design;
3. Commissioning measures shown in the construction documents;
4. Commissioning plan;
5. Functional performance testing;
6. Documentation and training;
7. Commissioning report.
All building operating systems covered by California Code of Regulations Title 24, Part 6, as well as process equipment and controls and renewable energy systems shall be included in the scope of the commissioning requirements. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
Note: This table is intended only as an aid in illustrating the nonresidential tier structure
(Refer to Checklists A5.602, A5.602.1, and A5.602.2 for CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist, and Tier 2 Checklist.)
CATEGORY | ENVIRONMENTAL PERFORMANCE GOAL | TIER 1 | TIER 2 |
CATEGORY | ENVIRONMENTAL PERFORMANCE GOAL | TIER 1 | TIER 2 |
All | Minimum Mandatory (See Mandatory Checklist) | Meet all of the provisions of Chapter 5 (See Tier 1 Checklist) | Meet all of the provisions of Chapter 5 (See Tier 2 Checklist) |
DIVISION 5.1 Planning and Design | Designated Parking for Fuel Efficient Vehicles | Meet Table A5.106.5.1.1 | Meet Table A5.106.5.1.2 |
Electric Vehicle Charging | Approx. 8% of total spaces | Approx. 10% of total spaces | |
Cool Roof to Reduce Heat Island Effect | Meet Table A5.106.11.2.2 | Meet Table A5.106.11.2.3 | |
1 additional Elective from Division A5.1 | 3 additional Electives from Division A5.1 | ||
DIVISION 5.2 Energy Efficiency | Energy Performance2 | Outdoor lighting power 90% of Part 6 allowance | Outdoor lighting power 90% of Part 6 allowance |
If applicable, solar water-heating system with minimum solar savings fraction of 0.15 | If applicable, solar water-heating system with minimum solar savings fraction of 0.15 | ||
Warehouse door seals | Warehouse door seals | ||
Comply with day lighting requirements | Comply with day lighting requirements | ||
Exhaust heat recovery | Exhaust heat recovery | ||
Energy Budget 95% or 90% of Part 6 calculated value of allowance | Energy Budget 90% or 85% of Part 6 calculated value of allowance | ||
DIVISION 5.3 Water Efficiency and Conservation | Indoor Water Use | 12% Savings | 20% Savings |
1 additional Elective from Division A5.3 | 3 additional Electives from Division A5.3 | ||
DIVISION 5.4 Material Conservation and Resource Efficiency3 | Construction Waste Reduction | At least 65% reduction | At least 80% reduction |
Recycled Content | Utilize recycled content materials for 10% of total material cost | Utilize recycled content materials for 15% of total material cost | |
1 additional Elective from Division A5.4 | 3 additional Electives from Division A5.4 | ||
Division 5.5 Environmental Quality | Low-VOC Resilient Flooring | 90% of flooring meets VOC limits | 100% of flooring meets VOC limits1 |
Low-VOC Thermal Insulation | Comply with VOC limits | Install no-added formaldehyde insulation and comply with VOC limits | |
1 additional Elective from Division A5.5 | 3 additional Electives from Division A5.5 | ||
Additional Measures | 1 Additional Elective from any division | 3 Additional Electives from any division | |
Approximate Total Measures | 15 | 25 | |
1. Exception: Allowance may be permitted in Tier 2 for up to 5 percent specialty purpose flooring.
2. Solar water-heating system requirement for newly constructed restaurants as per A5.203.1.1.2.
Exceptions:
a. Buildings with a natural gas service water heater with a minimum of 95 percent thermal efficiency.
b. Buildings where greater than 75 percent of the total roof area has annual solar access that is less than 70 percent. Solar access is the ratio of solar insolation including shade to the solar insolation without shade. Shading from obstructions located on the roof or any other part of the building shall not be included in the determination of annual solar access.
3. Life cycle assessment compliant with Section A5.409.4 in this code may be substituted for prescriptive measures from Division A5.4.