Section A5.602 of the 2016 CALGreen Code is adopted with amendments to read as follows:
Application: This checklist shall be used for nonresidential projects that meet one of the following: new construction, building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3 AND do not trigger a Tier 1 or Tier 2 requirement:
Y = Yes (section has been selected and/or included)
N/A = Not Applicable (code section does not apply to the project – mainly used for additions and alterations)
O = Other (provide explanation)
[N] = New construction pursuant to Section 301.3
[A] = Additions and/or Alterations pursuant to Section 301.3
CHAPTER 5 DIVISIONS | SECTION TITLE | CODE SECTION | Y | N/A | O | PLAN SHEET, SPEC, OR ATTACH REFERENCE |
CHAPTER 5 DIVISIONS | SECTION TITLE | CODE SECTION | Y | N/A | O | PLAN SHEET, SPEC, OR ATTACH REFERENCE | |
DIVISION 5.1 Planning and Design | Mandatory | Storm water pollution prevention for projects that disturb less than 1 acre of land | 5.106.1 through 5.106.2 | ||||
Mandatory | Short-term bicycle parking (with exception) | 5.106.4.1.1 | |||||
Mandatory | Long-term bicycle parking | 5.106.4.1.2 through 5.106.4.1.5 | |||||
Mandatory | Electric vehicle (EV) charging [N] w/ exceptions | 5.106.5.3 | |||||
Mandatory | EV capable spaces [N] | 5.106.5.3.1 | |||||
Mandatory | Electric vehicle charging stations (EVCS) | 5.106.5.3.2 | |||||
Mandatory | Use of automatic load management systems (ALMS) | 5.106.5.3.3 | |||||
Mandatory | Accessible EVCS | 5.106.5.3.4 | |||||
Mandatory | Note for EVCS signs | ||||||
Mandatory | Table 5.106.5.3.1 w/ footnotes | 5.106.3.1, 5.106.3.2 and 5.106.3.3 | |||||
Mandatory | Electric vehicle (EV) charging: medium-duty and heavy-duty [N] | 5.106.5.4 | |||||
Mandatory | Electric vehicle charging readiness requirements for warehouses, grocery stores and retail stores with planned off-street loading spaces [N] | 5.106.8 | |||||
Mandatory | Table 5.106.5.4.1 | 5.106.5.4 and 5.106.5.4.1 | |||||
Mandatory | Light pollution reduction [N] (with exceptions, notes and table) | 5.106.8 through 5.106.8.2 | |||||
Mandatory | Grading and paving (exception for additions and alterations not altering the drainage path) | 5.106.10 | |||||
Mandatory | Heat island effect | 5.106.11 | |||||
Mandatory | Hardscape alternatives [N] | 5.106.11.1 | |||||
Division 5.2 Energy Efficiency | Mandatory | Meet the minimum energy efficiency standard | 5.201.1 | ||||
Division 5.3 Water Efficiency and Conservation | Mandatory | Separate meters (new buildings or additions > 50,000 sf that consume more than 100 gal/day) | 5.303.1.1 | ||||
Mandatory | Separate meters (for tenants in new buildings or additions that consume more than 1,000 gal/day) | 5.303.1.2 | |||||
Mandatory | Water Reduction | 5.303.2 | |||||
Mandatory | Water closets shall not exceed 1.28 gallons per flush (gpf) | 5.303.3.1 | |||||
Mandatory | Wall-mounted urinals shall not exceed 0.125 gpf | 5.303.3.2.1 | |||||
Mandatory | Floor-mounted urinals shall not exceed 0.5 gpf | 5.303.3.2.2 | |||||
Mandatory | Single showerhead shall have maximum flow rate of 1.8 gpm (gallons per minute) at 80 psi | 5.303.3.3.1 | |||||
Mandatory | Multiple showerheads serving one shower shall have a combined flow rate of 1.8 gpm at 80 psi | 5.303.3.3.2 | |||||
Mandatory | Nonresidential lavatory faucets | 5.303.3.4.1 | |||||
Mandatory | Kitchen faucets | 5.303.3.4.2 | |||||
Mandatory | Wash fountains | 5.303.3.4.3 | |||||
Mandatory | Metering faucets | 5.303.3.4.4 | |||||
Mandatory | Metering faucets for wash fountains | 5.303.3.4.5 | |||||
Mandatory | Pre-rinse spray valve | 5.303.3.4.6 | |||||
Mandatory | Food waste disposers | 5.303.4.1 | |||||
Mandatory | Areas of additions or alterations | 5.303.5 | |||||
Mandatory | Standards for plumbing fixtures and fittings | 5.303.6 | |||||
Mandatory | Outdoor potable water use in landscape areas (with notes) | 5.304.1 | |||||
Division 5.4 Material Conservation and Resource Efficiency | Mandatory | Weather protection | 5.407.1 | ||||
Mandatory | Moisture control: sprinklers | 5.407.2.1 | |||||
Mandatory | Moisture control: exterior door protection | 5.407.2.2.1 | |||||
Mandatory | Moisture control: flashing | 5.407.2.2.2 | |||||
Mandatory | Construction waste management – comply with either: Sections 5.408.1.1, 5.408.1.2, 5.408.1.3 or more stringent local ordinance | 5.408.1.1, 5.408.1.2, 5.408.1.3 | |||||
Mandatory | Construction waste management: documentation | 5.408.1.4 | |||||
Mandatory | Universal waste [A] | 5.408.2 | |||||
Mandatory | Excavated soil and land clearing debris (100% reuse or recycle) | 5.408.3 | |||||
Mandatory | Recycling by occupants (with exception) | 5.410.1 | |||||
Mandatory | Recycling by occupants: additions (with exception) | 5.410.1.1 | |||||
Mandatory | Recycling by occupants: sample ordinance | 5.410.1.2 | |||||
Mandatory | Commissioning new buildings (≥ 10,000 sf) [N] | 5.410.2 | |||||
Mandatory | Owner’s or owner representative’s Project Requirements (OPR) [N] | 5.410.2.1 | |||||
Mandatory | Basis of Design (BOD) [N] | 5.410.2.2 | |||||
Mandatory | Commissioning plan [N] | 5.410.2.3 | |||||
Mandatory | Functional performance testing [N] | 5.410.2.4 | |||||
Mandatory | Documentation and training [N] | 5.410.2.5 | |||||
Mandatory | Systems manual [N] | 5.410.2.5.1 | |||||
Mandatory | Systems operation training [N] | 5.410.2.5.2 | |||||
Mandatory | Commissioning report [N] | 5.410.2.6 | |||||
Mandatory | Testing and adjusting for new buildings < 10,000 sf or new systems that serve additions or alterations [A] | 5.410.4 | |||||
Mandatory | System testing plan for renewable energy, landscape irrigation and water reuse [A] | 5.410.4.2 | |||||
Mandatory | Procedures for testing and adjusting | 5.410.4.3 | |||||
Mandatory | Procedures for HVAC balancing | 5.410.4.3.1 | |||||
Mandatory | Reporting for testing and adjusting | 5.410.4.4 | |||||
Mandatory | Operation and maintenance (O&M) manual | 5.410.4.5 | |||||
Mandatory | Inspection and reports | 5.410.4.5.1 | |||||
Division 5.5 Environmental Quality | Mandatory | Fireplaces | 5.503.1 | ||||
Mandatory | Woodstoves | 5.503.1.1 | |||||
Mandatory | Temporary ventilation | 5.504.1 | |||||
Mandatory | Covering of ducts openings and protection of mechanical equipment during construction | 5.504.3 | |||||
Mandatory | Adhesives, sealants and caulks | 5.504.4.1 | |||||
Mandatory | Paints and coatings | 5.504.4.3 | |||||
Mandatory | Aerosol paints and coatings | 5.504.4.3.1 | |||||
Mandatory | Aerosol paints and coatings: verification | 5.504.4.3.2 | |||||
Mandatory | Carpet systems | 5.504.4.4 | |||||
Mandatory | Carpet cushion | 5.504.4.4.1 | |||||
Mandatory | Carpet adhesives per Table 5.504.4.1 | 5.504.4.4.2 | |||||
Mandatory | Composite wood products | 5.504.4.5 | |||||
Mandatory | Composite wood products: documentation | 5.504.4.5.3 | |||||
Mandatory | Resilient flooring systems | 5.504.4.6 | |||||
Mandatory | Resilient flooring: verification of compliance | 5.504.4.6.1 | |||||
Mandatory | Thermal insulation | 5.504.4.7 | |||||
Mandatory | Verification of compliance | 5.504.4.7.1 | |||||
Mandatory | Acoustical ceilings and wall panels | 5.504.4.8 | |||||
Mandatory | Verification of compliance | 5.504.4.8.1 | |||||
Mandatory | Filters (with exceptions) | 5.504.5.3 | |||||
Mandatory | Filters: labeling | 5.504.5.3.1 | |||||
Mandatory | Environmental tobacco smoke (ETS) control | 5.504.7 | |||||
Mandatory | Indoor moisture control | 5.505.1 | |||||
Mandatory | Outside air delivery | 5.506.1 | |||||
Mandatory | Carbon dioxide (CO2) monitoring | 5.506.2 | |||||
Mandatory | Acoustical control (with exception) | 5.507.4 | |||||
Mandatory | Exterior noise transmission, prescriptive method (with exceptions) | 5.507.4.1 | |||||
Mandatory | Noise exposure where noise contours are not readily available | 5.507.4.1.1 | |||||
Mandatory | Performance method | 5.507.4.2 | |||||
Mandatory | Site features | 5.507.4.2.1 | |||||
Mandatory | Documentation of compliance | 5.507.4.2.2 | |||||
Mandatory | Interior sound transmission (with note) | 5.507.4.3 | |||||
Mandatory | Ozone depletion and greenhouse gas reductions | 5.508.1 | |||||
Mandatory | Chlorofluorocarbons (CFCs) | 5.508.1.1 | |||||
Mandatory | Halons | 5.508.1.2 | |||||
Mandatory | Supermarket refrigerant leak reduction for retail food stores 8,000 square feet or more Sections 5.508.2 through 5.508.2.6.3 | 5.508.2 through 5.508.2.6.3 | |||||
END OF MANDATORY PROVISIONS | |||||||
Documentation Author's / Responsible Designer's Declaration Statement __ Mandatory: I attest that this mandatory provisions checklist is accurate and complete. | |||||||
Signature: | |||||||
Company: | Date: | ||||||
Address: | License: | ||||||
City/State/Zip: | Phone: | ||||||