SEC. 99.12.508.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
   Section A5.602 of the 2016 CALGreen Code is adopted with amendments to read as follows:
 
TABLE A5.602
CALGREEN VERIFICATION GUIDELINES MANDATORY MEASURES CHECKLIST
 
Application: This checklist shall be used for nonresidential projects that meet one of the following: new construction, building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3 AND do not trigger a Tier 1 or Tier 2 requirement:
 
Y   =   Yes (section has been selected and/or included)
N/A   =   Not Applicable (code section does not apply to the project – mainly used for additions and alterations)
O   =   Other (provide explanation)
[N]   =   New construction pursuant to Section 301.3
[A]   =   Additions and/or Alterations pursuant to Section 301.3
 
CHAPTER 5 DIVISIONS
SECTION TITLE
CODE SECTION
Y
N/A
O
PLAN SHEET, SPEC, OR ATTACH REFERENCE
CHAPTER 5 DIVISIONS
SECTION TITLE
CODE SECTION
Y
N/A
O
PLAN SHEET, SPEC, OR ATTACH REFERENCE
DIVISION 5.1
Planning and Design
Mandatory
Storm water pollution prevention for projects that disturb less than 1 acre of land
5.106.1 through 5.106.2
 
 
 
 
Mandatory
Short-term bicycle parking (with exception)
5.106.4.1.1
 
 
 
 
Mandatory
Long-term bicycle parking
5.106.4.1.2 through 5.106.4.1.5
 
 
 
 
Mandatory
Electric vehicle (EV) charging [N] w/ exceptions
5.106.5.3
 
 
 
 
Mandatory
EV capable spaces [N]
5.106.5.3.1
 
 
 
 
Mandatory
Electric vehicle charging stations (EVCS)
5.106.5.3.2
 
 
 
 
Mandatory
Use of automatic load management systems (ALMS)
5.106.5.3.3
 
 
 
 
Mandatory
Accessible EVCS
5.106.5.3.4
 
 
 
 
Mandatory
Note for EVCS signs
 
 
 
 
Mandatory
Table 5.106.5.3.1 w/ footnotes
5.106.3.1,
5.106.3.2 and
5.106.3.3
 
 
 
 
Mandatory
Electric vehicle (EV) charging: medium-duty and heavy-duty [N]
5.106.5.4
 
 
 
 
Mandatory
Electric vehicle charging readiness requirements for warehouses, grocery stores and retail stores with planned off-street loading spaces [N]
5.106.8
 
 
 
 
Mandatory
Table 5.106.5.4.1
5.106.5.4 and 5.106.5.4.1
 
 
 
 
Mandatory
Light pollution reduction [N] (with exceptions, notes and table)
5.106.8 through 5.106.8.2
 
 
 
 
Mandatory
Grading and paving (exception for additions and alterations not altering the drainage path)
5.106.10
Mandatory
Heat island effect
5.106.11
Mandatory
Hardscape alternatives [N]
5.106.11.1
 
 
 
 
Division 5.2
Energy Efficiency
Mandatory
Meet the minimum energy efficiency standard
5.201.1
 
 
 
 
Division 5.3
Water Efficiency and Conservation
Mandatory
Separate meters (new buildings or additions > 50,000 sf that consume more than 100 gal/day)
5.303.1.1
Mandatory
Separate meters (for tenants in new buildings or additions that consume more than 1,000 gal/day)
5.303.1.2
Mandatory
Water Reduction
5.303.2
Mandatory
Water closets shall not exceed 1.28 gallons per flush (gpf)
5.303.3.1
 
 
 
 
Mandatory
Wall-mounted urinals shall not exceed 0.125 gpf
5.303.3.2.1
 
 
 
 
Mandatory
Floor-mounted urinals shall not exceed 0.5 gpf
5.303.3.2.2
 
 
 
 
Mandatory
Single showerhead shall have maximum flow rate of 1.8 gpm (gallons per minute) at 80 psi
5.303.3.3.1
 
 
 
 
Mandatory
Multiple showerheads serving one shower shall have a combined flow rate of 1.8 gpm at 80 psi
5.303.3.3.2
 
 
 
 
Mandatory
Nonresidential lavatory faucets
5.303.3.4.1
 
 
 
 
Mandatory
Kitchen faucets
5.303.3.4.2
 
 
 
 
Mandatory
Wash fountains
5.303.3.4.3
 
 
 
 
Mandatory
Metering faucets
5.303.3.4.4
 
 
 
 
Mandatory
Metering faucets for wash fountains
5.303.3.4.5
 
 
 
 
Mandatory
Pre-rinse spray valve
5.303.3.4.6
Mandatory
Food waste disposers
5.303.4.1
 
 
 
 
Mandatory
Areas of additions or alterations
5.303.5
 
 
 
 
Mandatory
Standards for plumbing fixtures and fittings
5.303.6
 
 
 
 
Mandatory
Outdoor potable water use in landscape areas (with notes)
5.304.1
 
 
 
 
Division 5.4
Material Conservation and Resource Efficiency
Mandatory
Weather protection
5.407.1
 
 
 
 
Mandatory
Moisture control: sprinklers
5.407.2.1
 
 
 
 
Mandatory
Moisture control: exterior door protection
5.407.2.2.1
 
 
 
 
Mandatory
Moisture control: flashing
5.407.2.2.2
 
 
 
 
Mandatory
Construction waste management – comply with either: Sections 5.408.1.1, 5.408.1.2, 5.408.1.3 or more stringent local ordinance
5.408.1.1,
5.408.1.2,
5.408.1.3
 
 
 
 
Mandatory
Construction waste management: documentation
5.408.1.4
 
 
 
 
Mandatory
Universal waste [A]
5.408.2
 
 
 
 
Mandatory
Excavated soil and land clearing debris (100% reuse or recycle)
5.408.3
 
 
 
 
Mandatory
Recycling by occupants (with exception)
5.410.1
 
 
 
 
Mandatory
Recycling by occupants: additions (with exception)
5.410.1.1
 
 
 
 
Mandatory
Recycling by occupants: sample ordinance
5.410.1.2
 
 
 
 
Mandatory
Commissioning new buildings ( 10,000 sf) [N]
5.410.2
 
 
 
 
Mandatory
Owner’s or owner representative’s Project Requirements (OPR) [N]
5.410.2.1
 
 
 
 
Mandatory
Basis of Design (BOD) [N]
5.410.2.2
Mandatory
Commissioning plan [N]
5.410.2.3
Mandatory
Functional performance testing [N]
5.410.2.4
Mandatory
Documentation and training [N]
5.410.2.5
Mandatory
Systems manual [N]
5.410.2.5.1
Mandatory
Systems operation training [N]
5.410.2.5.2
Mandatory
Commissioning report [N]
5.410.2.6
Mandatory
Testing and adjusting for new buildings < 10,000 sf or new systems that serve additions or alterations [A]
5.410.4
Mandatory
System testing plan for renewable energy, landscape irrigation and water reuse [A]
5.410.4.2
Mandatory
Procedures for testing and adjusting
5.410.4.3
Mandatory
Procedures for HVAC balancing
5.410.4.3.1
Mandatory
Reporting for testing and adjusting
5.410.4.4
Mandatory
Operation and maintenance (O&M) manual
5.410.4.5
Mandatory
Inspection and reports
5.410.4.5.1
Division 5.5
Environmental Quality
Mandatory
Fireplaces
5.503.1
Mandatory
Woodstoves
5.503.1.1
Mandatory
Temporary ventilation
5.504.1
Mandatory
Covering of ducts openings and protection of mechanical equipment during construction
5.504.3
Mandatory
Adhesives, sealants and caulks
5.504.4.1
Mandatory
Paints and coatings
5.504.4.3
Mandatory
Aerosol paints and coatings
5.504.4.3.1
Mandatory
Aerosol paints and coatings: verification
5.504.4.3.2
Mandatory
Carpet systems
5.504.4.4
Mandatory
Carpet cushion
5.504.4.4.1
Mandatory
Carpet adhesives per Table 5.504.4.1
5.504.4.4.2
Mandatory
Composite wood products
5.504.4.5
Mandatory
Composite wood products: documentation
5.504.4.5.3
Mandatory
Resilient flooring systems
5.504.4.6
Mandatory
Resilient flooring: verification of compliance
5.504.4.6.1
Mandatory
Thermal insulation
5.504.4.7
Mandatory
Verification of compliance
5.504.4.7.1
Mandatory
Acoustical ceilings and wall panels
5.504.4.8
Mandatory
Verification of compliance
5.504.4.8.1
Mandatory
Filters (with exceptions)
5.504.5.3
Mandatory
Filters: labeling
5.504.5.3.1
Mandatory
Environmental tobacco smoke (ETS) control
5.504.7
Mandatory
Indoor moisture control
5.505.1
Mandatory
Outside air delivery
5.506.1
Mandatory
Carbon dioxide (CO2) monitoring
5.506.2
Mandatory
Acoustical control (with exception)
5.507.4
Mandatory
Exterior noise transmission, prescriptive method (with exceptions)
5.507.4.1
Mandatory
Noise exposure where noise contours are not readily available
5.507.4.1.1
Mandatory
Performance method
5.507.4.2
Mandatory
Site features
5.507.4.2.1
Mandatory
Documentation of compliance
5.507.4.2.2
Mandatory
Interior sound transmission (with note)
5.507.4.3
Mandatory
Ozone depletion and greenhouse gas reductions
5.508.1
Mandatory
Chlorofluorocarbons (CFCs)
5.508.1.1
Mandatory
Halons
5.508.1.2
Mandatory
Supermarket refrigerant leak reduction for retail food stores 8,000 square feet or more Sections 5.508.2 through 5.508.2.6.3
5.508.2 through 5.508.2.6.3
END OF MANDATORY PROVISIONS