18-29-802.3.2 Air break.
   An air break shall be provided between the indirect waste pipe and the trap seal of the waste receptor.
(Added Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4 Waste receptors.
   For other than hub drains that receive only clear-water waste and standpipes, a removable strainer or basket shall cover the outlet of waste receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, crawl spaces, attics, or interstitial spaces above ceilings or below floors. Ready access shall be provided to waste receptors.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.1 Size of receptors.
   A waste receptor shall be sized for the maximum discharge of all indirect waste pipes served by the receptor. Receptors shall be installed to prevent splashing or flooding.
(Added Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.2 Open hub drains.
   Waste receptors shall be permitted in the form of a hub or pipe extending not less than 1 inch (25 mm) above a water-impervious floor and are not required to have a strainer.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.3 Standpipes.
   Standpipes shall be individually trapped. Standpipes shall extend a minimum of 18 inches (457 mm) and a maximum of 42 inches (1,066 mm) above the trap weir. Access shall be provided to all standpipe and drains for rodding.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-803 Special Wastes.
18-29-803.1 Deliberately omitted.