18-29-802.4.2 Open hub drains.
   Waste receptors shall be permitted in the form of a hub or pipe extending not less than 1 inch (25 mm) above a water-impervious floor and are not required to have a strainer.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.3 Standpipes.
   Standpipes shall be individually trapped. Standpipes shall extend a minimum of 18 inches (457 mm) and a maximum of 42 inches (1,066 mm) above the trap weir. Access shall be provided to all standpipe and drains for rodding.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-803 Special Wastes.
18-29-803.1 Deliberately omitted.
18-29-803.2 Neutralizing device required for corrosive wastes.
   Corrosive liquids, spent acids or other harmful chemicals that destroy or injure a drain, sewer, soil or waste pipe, or create noxious or toxic fumes or interfere with sewage treatment processes, shall not be discharged into the plumbing system device for corrosive waste. No corrosive wastes which are equal or greater in corrosive action than a ph lower than 4.5 or higher than 10.0, having corrosive properties sufficient to cause damage or hazards to structures, equipment, or personnel, shall discharge into any house sewer without first discharging into a dilution tank or basin. Such devices shall be automatically provided with a sufficient supply of diluting water or neutralizing medium so as to make the contents noninjurious before discharge into the drainage system. No other waste pipe shall connect to a dilution basin. Every dilution tank used for this purpose shall be constructed of earthenware, polyethylene, propylene or glass and shall be provided with a standing waste and overflow or other approved means to insure dilution.
(Amend Coun. J. 3-27-02, p. 82090, § 3)