18-29-802.3 Installation.
   Indirect waste piping shall discharge through an air gap or air break into a waste receptor. Waste receptors shall be trapped and vented and shall connect to the building drainage system. Waste receptors shall not be located in a toilet facility, closet, storeroom or any inaccessible space. Indirect waste piping that exceeds 30 inches (762 mm) in developed length measured horizontally or 54 inches (1372 mm) in total developed length shall be trapped. Indirect waste pipes shall not exceed 15 feet (4572 mm) in total length and shall be provided with cleanouts at every 90 degree (1.57 rad) turn.
   Exception: Where a waste receptor receives only clear-water waste and does not directly connect to a sanitary drainage system, the receptor shall not require a trap.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.3.1 Air gap.
   The air gap between the indirect waste pipe and the flood level rim of the waste receptor shall be not less than twice the effective opening of the indirect waste pipe and not less than 1 inch (25 mm).
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.3.2 Air break.
   An air break shall be provided between the indirect waste pipe and the trap seal of the waste receptor.
(Added Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4 Waste receptors.
   For other than hub drains that receive only clear-water waste and standpipes, a removable strainer or basket shall cover the outlet of waste receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, crawl spaces, attics, or interstitial spaces above ceilings or below floors. Ready access shall be provided to waste receptors.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.1 Size of receptors.
   A waste receptor shall be sized for the maximum discharge of all indirect waste pipes served by the receptor. Receptors shall be installed to prevent splashing or flooding.
(Added Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.2 Open hub drains.
   Waste receptors shall be permitted in the form of a hub or pipe extending not less than 1 inch (25 mm) above a water-impervious floor and are not required to have a strainer.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)
18-29-802.4.3 Standpipes.
   Standpipes shall be individually trapped. Standpipes shall extend a minimum of 18 inches (457 mm) and a maximum of 42 inches (1,066 mm) above the trap weir. Access shall be provided to all standpipe and drains for rodding.
(Amend Coun. J. 10-14-21, p. 37722, Art. VIII, § 1)