15-28-060 General safety clearances.
   Every building hereafter designed, erected, altered or converted for the purpose of storing more of any hazardous chemical than the limited quantity provided for such chemical in Section 15-28-040 shall be isolated by a safety clearance of not less than 100 feet except as otherwise provided by this section.
   Type I or IIA Construction. Every such hazardous chemical building of Type IA, IB or IIA construction shall be isolated from any other building on the same premises by a safety clearance of not less than ten feet; provided, however, that such safety clearance shall not be required for any such building having no openings within ten feet of any openings in any other wall or building on the same premises, or for any such building which is separated from any adjoining buildings by a fire wall without openings therein.
   Types IIB, III, or IV Construction. Every such hazardous chemical building of Type IIB, IIIA, IIIB, or IV construction shall be isolated from any other building on the same premises by a safety clearance of not less than 20 feet; provided, however, that such safety clearance will not be required for any such building having no openings within ten feet of any openings in any other wall or building on the same premises or for any such building which is separated from any adjoining building by a fire wall without openings therein.
(Prior code § 92-6; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 66)