Fume or Flammable Compressed Gas Buildings. Every fume or flammable compressed gas building shall have a floor area limited by the provisions of Title 14B for Group F-1 occupancies.
Fume or Flammable Compressed Gas Rooms. No fume or flammable compressed gas room shall have a floor area of more than 600 square feet; provided, however, that this requirement shall not apply to a room used for no purpose other than the operation of a water purification plant or refrigerating unit. Two sides, or two ends, or one side and one end of every fume or flammable compressed gas room shall be enclosed by an outside wall. Not more than two fume or flammable compressed gas rooms shall be permitted in any building; provided, however, that in a building equipped throughout with a standard system of automatic sprinklers not more than six such rooms shall be permitted.
Manufactured Gas Building. Any building used exclusively for the production, distribution or storage of manufactured gas as public utility shall be exempt from the provisions of this section.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 55)