15-24-370 Standard fireproof vaults.
   The walls, floor and ceilings of a standard fireproof vault, whenever such a room is required by this Code, shall be built of reinforced concrete or masonry of not less than two-hour fire-resistive construction. The distance from the floor to the ceiling of a standard fireproof vault shall not exceed 11 feet. Where a standard fireproof vault is located within any building, the cubical contents of such standard fireproof vault shall not exceed 750 cubic feet. Where a standard fireproof vault is located outside of a building so that a safety clearance of not less than five feet is provided on not less than three sides of such fireproof vault, the cubical contents of such vault shall not exceed 1,500 cubic feet. Nothing in this chapter shall be construed as prohibiting more than one standard fireproof vault in any building or structure or on any lot or plot of ground. All openings in the floors, walls, or ceilings of standard fireproof vault, except required vent flue openings and window openings for ventilation, shall be equipped and protected with a 3-hour-rated fire door of the automatic type and shall have as its actuating mechanism to close such door, a thermostatic releasing device. No wood floor, wood racks, wood shelves, or any other combustible material other than the substance for which any standard fireproof vault is intended shall be allowed or permitted in such vault. Shelves or racks used to support the material stored in vault shall be of metal and of open construction, so arranged as to permit water from the sprinkler heads to pass between container or packages.
   Flammable Liquids. Whenever a standard fireproof vault is used for the storage of flammable liquids, there shall be a sill at every doorway thereto, constructed of noncombustible materials and six inches high above the level of the floor of the vault. All floor drains in a vault used for storing or keeping flammable or corrosive liquids shall have no connections with the drainage system of the building, but shall be arranged to drain to a location outside of the building remote from all connections or drains to the sewer system.
(Prior code § 129.1-29; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 34)